Sie sind auf Seite 1von 62

EHV SUBSTATIONS

EHV SUBSTATION AND SUBSTATION EQUIPMENTS


Karikalan.M, 21FEBRUARY 2012. Siemens Ltd.

Energy Transmission Power Transmission Solutions, Secondary Engineering

Siemens Ltd

Objective

Deals with the overall aspects of sub-station Covering all the equipments installed in a sub-station.

SUBSTATION Sub-stations are basically points in the power network where power can be pooled from generating sources, voltage levels transformed and power delivered to the load points

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Voltage levels in AC Substations Ultra High Voltages 765KV,1200KV Extra High Voltages EHV - 132kV, 220kV, 400kV High Voltage HV -66KV

Medium Voltages 6.6KV,11KV,33KV


Low Voltages - 415V and below.

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

COMPONENTS & TYPES OF SUB-STATION

A sub-station has the following components either partly or wholly:


1) bus-bars 2) incoming and outgoing feeders 3) surge arrestors 4) voltage transformers 5) current transformers 6) circuit breakers 7) disconnectors 8) earthing switches 9) wave traps 10) reactors
4 E T PS-HVDC-COE- Karikalan.M Siemens Ltd

COMPONENTS & TYPES OF SUB-STATION

11) battery banks 12) emergency diesel generator set 13) power line carrier communication 14) protection relays 15) control systems

16) illumination system


17) air-conditioning & ventilation system

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

COMPONENTS & TYPES OF SUB-STATION


Sr. No. Equipment Function

1. 2.

Bus-bar Circuit breakers

Incoming and outgoing circuits connected to bus-bar. Automatic switching during normal or abnormal conditions. Disconnection under no loan condition for safety, isolation and maintenance. To discharge the voltage on dead lines to earth To step down currents for measurement, control and protection.

3. 4. 5.

Isolators (Disconnections) Earthing Switch Current Transformer

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

6.

Voltage Transformer To step down voltage for measurement, control and protection. Lighting Arrester (Surge Arrester) Shunt reactor To discharge lightning over voltage and switching over voltage to earth. To provide reactive power compensation during low loads.

7.

8.

9.

Series Reactors

To reduce the short circuit current or starting currents.


To limit the earth fault current.

10.

Neutral-Grounding Reactors.

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

11 12.

Line trap

13.

19.

To prevent high frequency signals from entering other zones. Power Transformer To step-up or step down the voltage and transfer power from one AC voltage to another AC voltage at the same frequency. Substation To provide an earth mat for connecting neutral Earthing points, equipment body, support structures to (Grounding) earth. For safety of personnel and for enabling System earth fault protection.. -Earth mat -Earthing spikes -Earthing risers Protection System To provide alarm or automatic tripping of faulty -Protection relay part from healthy part and also to minimize -Panels damage to faulty equipment and associated -Control cables system. -Circuit-breakers -CTs., VTs. etc.
E T PS-HVDC-COE- Karikalan.M Siemens Ltd

Circuit Breakers

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Why do we have Circuit Breakers?

To switch Transmission Lines, Transformers, Shunt Reactors, Capacitor Banks etc. To close/reclose an open circuit

And of course the most important to clear a fault to protect equipment, Power Grid and human life!

10

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Basic Schematic
Fault analysing equipment

Protection relays

Instrument Transformers

Station control

Power System
Circuit breaker

Communication Equipment

11

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

CB CONTACT ASSEMBLY

A Look at Contact Assembly


Incoming Flange Outgoing Flange

Main Contact, Moving

Main Contact, Fixed Fixed contact Holder

Moving contact Holder

Arcing Contact, Moving

Arcing contact, Fixed

12

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Moving Contact

13

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Fixed Contact

14

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Current transformers

15

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

CURRENT TRANSFORMERS

CTs are used to provide isolation from the power system and reduction in magnitude to a level usable by relays and meters. TYPES OF CTS 1.LIVE TANK CT 2.DEAD TANK CT

Hair Pin Design Eye Bolt Design

16

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

LIVE TANK CT

17

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

DEAD TANK CT

18

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Eye Bolt Design

Primary steel pipe

Paper insulation

Seconday cores

19

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Hair-Pin design

1. Dome 2. Nitrogen filling valve 3. Primary terminal 4. Collar 5. Porcelain insulator 6. Primary conductor with insulation 7. Adaptor cylinder 8. Secondary cores

9. Base
10. Oil drain plug

20

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Current Transformers Protection accuracy classes

Accuracy classes (Protection) Maximum current error in % of IP Accuracy limit primary current = fL.IN Burden :SN
Class e 5 P 10 P Ratio error at In 1 % 3 % Phase displacemen t at In 60 min. Composite error at fL.IN 5 % 10 %

21

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Factors for Protection

1. Accuracy Limiting Factor What is Accuracy Limiting factor ? It is the factor of over current above the rated current which determines the capability of CT to maintain the error at such a condition. 2. Composite error It is the error of the CT when this over current is applied.

22

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Example

Accuracy Limiting Factor/composite error For e.g if the class designation is 5P20 20 is the Accuracy limiting factor which signifies that when 20 times the rated primary current is applied the composite error of 5P( +/- 5%) is maintained.

Typical Class designations are 5P10, 5P20, 10P10, 10P20 etc.,

23

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

CVT

24

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Capacitor Voltage Transformer

P1 C1

Intermediate Voltage : 10 to 20 kV/3

S1

C2

P2
25 E T PS-HVDC-COE- Karikalan.M

S2
Siemens Ltd

CVT Capacitor stack

Inductive VT
26 E T PS-HVDC-COE- Karikalan.M Siemens Ltd

CVT Secondary Voltage

CVT Secondary Voltage v = k * V * C1/ (C1+C2) V Primary Voltage k Secondary Transformation ratio Note: Puncturing of C1 Secondary Voltage will increase Puncturing of C2 Secondary Voltage will decrease

27

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

VT

28

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Voltage Transformer :

Primary

U1

n1
K: Transformation ratio

U1 n1 K U2 n2

n2

U2

Secondary
29 E T PS-HVDC-COE- Karikalan.M Siemens Ltd

Transformer

30

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Transformer A transformer is a device that transfers electrical energy from one circuit to another through inductively coupled conductors (the transformer's coils) without change in frequency. A major application of transformers is to increase voltage before transmitting electrical energy over long distances through wires. By transforming electrical power to a high-voltage (and therefore low-current) form for transmission and back again afterward, transformers enable economical transmission of power over long distances.

31

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Power Transformer

32

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Convertor Transformer

33

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Isolators and Disconectors

34

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

ISOLATORS/DIS CONNECTORS

Isolators (also referred as disconnectors) are off-load type switches. TYPES OF ISOLATORS

35

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

ISOLATORS/DIS CONNECTORS

36

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Wave Trap

37

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

38

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Surge arrester

39

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Surge Arrestor An electrical appliance used to protect electronic equipment against lightning overvoltage transients. It is usually connected to wires (power phase line, signal line, zero line) and ground between being protective devices in parallel.

During the lightning over-voltage the arrestor immediately limits the over-voltage amplitude which leads to protection of the equipment and systems, enabling the system to work properly.

40

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Surge Arrestor

41

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Bus Bar

42

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Sub Station Clearances


Highest system voltage Minimum clearance (KV) phase & earth (mm) between Minimum clearance between phases (mm) Sectional clearance (mm)

36
72.5 123 145

320
630 900 (1100*) 1100 (1300*)

320
630 900 (1100*) 1100 (1300*)

2800
3000 3500 (4000*) 4000

245 420 800

1900 (2100*) 3400 6400

1900 (2100*) 4200 10000

4500 (5000*) 6500 10000

43

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

AC C&P Design

SUB-STATION BUSBAR ARRANGEMENT Bus-bars are the part of the sub-station where all the power is concentrated.

The power from the sources is collected on the bus-bars by connecting the incoming lines.
The power is distributed from the bus-bars by connecting the outgoing lines to them.

44

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Auxillary Power Engineering SINGLE BUSBAR SCHEME In this arrangement of bus-bars, all incoming and outgoing feeders are connected to the same bus. This type of bus-bar system is used mostly in small AC stations (low & medium voltage stations) This arrangement has the following advantages: Low initial cost since each feeder has only one bus-bar Relaying scheme is simple Due to single breaker for one circuit, operation is very simple Low Maintenance cost.

45

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Software Design

This arrangement has the following disadvantages: All generators and incoming lines connected to the same bus lead to a high fault level on the bus In case of any maintenance work on any part of the bus-bar, the whole station has to be shut down In case of any fault on the bus-bar, there is complete outage of the whole station

In case of maintenance work on any feeder circuit breaker, the feeder has to be disconnected till the work is completed

46

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

SECTIONALISED SINGLE BUSBAR SCHEME

This scheme is an improvement over the single bus-bar scheme . The bus-bar has been split up into two parts with the feeders distributed over the two sections. This arrangement has the following advantages: Fault level of the bus due to incoming feeders can be reduced by operating the system with the bus-sectionaliser open

During fault on bus-bar, the whole station does not suffer complete outage Maintenance work can be carried out on one half of the bus-bars by taking it out of service instead of the whole station
47 E T PS-HVDC-COE- Karikalan.M Siemens Ltd

SECTIONALISED SINGLE BUSBAR SCHEME

This scheme is very common in low and medium voltage substations, particularly for indoor switchboards. Grid sub-stations do not adopt this arrangement since it does not offer a completely reliable bus-bar system.

48

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

SINGLE MAIN AND TRANSFER BUSBAR SCHEME

The single bus-bar scheme can be provided some flexibility by adding an additional bus-bar called the transfer bus-bar.

With this transfer bus, one feeder from the main bus can be connected to the transfer bus, thus freeing the circuit breaker of the feeder for maintenance. This scheme is mostly used in 132 KV or lower voltage sub-stations at the distribution level.

49

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

SINGLE MAIN AND TRANSFER BUSBAR SCHEME Advantages and Disadvantages This scheme combines the low cost and simplicity of single bus-bar scheme with a limited degree of flexibility. Whenever any feeder circuit breaker has to be taken for maintenance, the feeder is connected to the transfer bus through the transfer bus isolator and the transfer breaker. This arrangement does not offer any increased degree of reliability, it only provides the flexibility of maintenance of a circuit breaker without taking outage of line or bus-bar

50

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

DOUBLE MAIN BUSBAR SCHEME

In this system, there are two main bus-bars and each feeder has disconnectors that can connect the feeder to any bus-bar.

Thus some generators and feeders can be connected to any one bus-bar and the remaining generators and feeders to other bus-bar.

we can have two systems running in the same station and any generator or feeder can be switched to any one system

51

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

SINGLE MAIN AND TRANSFER BUSBAR SCHEME

52

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

DOUBLE MAIN BUSBAR SCHEME

The double bus-bar systems are mostly used in generating stations and grid sub-stations at higher voltages (usually 220KV and 132KV in India) where reliability and availability are critical issues.

53

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Limitation of Double Bus Scheme

Limitation of Double Bus Scheme: With this arrangement, any change-over from one bus to another has to be done under off-load conditions since the disconnectors are not made for switching loads and the two bus-bars are not connected together and hence there is no synchronism between the two bus-bars

54

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

DOUBLE MAIN BUSBAR WITH BUS COUPLER

Now, any feeder can be changed over from one bus-bar to another without switching off, the only condition for doing so is that the bus-coupler should be closed with its disconnectors and the feeder disconnector connecting the incoming bus has to be closed first and then the other disconnector can be opened.

55

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

DOUBLE MAIN WITH TRANSFER BUSBAR SCHEME

we have seen an arrangement that enables maintenance of circuit breaker without taking the feeder out of service. This was possible by addition of the transfer bus-bar and the transfer breaker.

56

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

DOUBLE MAIN WITH TRANSFER BUSBAR SCHEME

Advantages: In both the double bus with coupler and double main with transfer schemes, during instances of bus faults, the faulty bus can be identified and all feeders taken on the healthy bus-bar while maintenance on the faulty bus can be carried out . Dis-advantages: In case of bus-fault, all breakers connected to the faulty bus-bar trip and thus the corresponding feeders are out of service. Till the faulty bus-bar is isolated and the feeders connected back to the healthy bus-bar and the breakers switched on again.

57

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

ONE-AND-HALF BREAKER SCHEME

HERE TWO FEEDERS ARE CONTROLED BY THREE BREAKERS. SO THESE TWO FEEDERS CONTROLLED BY THREE CIRCUIT BREAKERS IT IS CALLED ONE & HALF BREAKER SYSTEM.

The bus-coupler and transfer bus are eliminated.

58

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

ONE-AND-HALF BREAKER SCHEME I Type

59

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

ONE-AND-HALF BREAKER SCHEME D Type

60

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Typical One-and-Half System

61

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

THANK YOU

62

E T PS-HVDC-COE- Karikalan.M

Siemens Ltd

Das könnte Ihnen auch gefallen