Objective
Deals with the overall aspects of sub-station Covering all the equipments installed in a sub-station.
SUBSTATION Sub-stations are basically points in the power network where power can be pooled from generating sources, voltage levels transformed and power delivered to the load points
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Voltage levels in AC Substations Ultra High Voltages 765KV,1200KV Extra High Voltages EHV - 132kV, 220kV, 400kV High Voltage HV -66KV
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
11) battery banks 12) emergency diesel generator set 13) power line carrier communication 14) protection relays 15) control systems
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
1. 2.
Incoming and outgoing circuits connected to bus-bar. Automatic switching during normal or abnormal conditions. Disconnection under no loan condition for safety, isolation and maintenance. To discharge the voltage on dead lines to earth To step down currents for measurement, control and protection.
3. 4. 5.
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
6.
Voltage Transformer To step down voltage for measurement, control and protection. Lighting Arrester (Surge Arrester) Shunt reactor To discharge lightning over voltage and switching over voltage to earth. To provide reactive power compensation during low loads.
7.
8.
9.
Series Reactors
10.
Neutral-Grounding Reactors.
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
11 12.
Line trap
13.
19.
To prevent high frequency signals from entering other zones. Power Transformer To step-up or step down the voltage and transfer power from one AC voltage to another AC voltage at the same frequency. Substation To provide an earth mat for connecting neutral Earthing points, equipment body, support structures to (Grounding) earth. For safety of personnel and for enabling System earth fault protection.. -Earth mat -Earthing spikes -Earthing risers Protection System To provide alarm or automatic tripping of faulty -Protection relay part from healthy part and also to minimize -Panels damage to faulty equipment and associated -Control cables system. -Circuit-breakers -CTs., VTs. etc.
E T PS-HVDC-COE- Karikalan.M Siemens Ltd
Circuit Breakers
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
To switch Transmission Lines, Transformers, Shunt Reactors, Capacitor Banks etc. To close/reclose an open circuit
And of course the most important to clear a fault to protect equipment, Power Grid and human life!
10
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Basic Schematic
Fault analysing equipment
Protection relays
Instrument Transformers
Station control
Power System
Circuit breaker
Communication Equipment
11
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
CB CONTACT ASSEMBLY
12
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Moving Contact
13
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Fixed Contact
14
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Current transformers
15
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
CURRENT TRANSFORMERS
CTs are used to provide isolation from the power system and reduction in magnitude to a level usable by relays and meters. TYPES OF CTS 1.LIVE TANK CT 2.DEAD TANK CT
16
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
LIVE TANK CT
17
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
DEAD TANK CT
18
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Paper insulation
Seconday cores
19
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Hair-Pin design
1. Dome 2. Nitrogen filling valve 3. Primary terminal 4. Collar 5. Porcelain insulator 6. Primary conductor with insulation 7. Adaptor cylinder 8. Secondary cores
9. Base
10. Oil drain plug
20
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Accuracy classes (Protection) Maximum current error in % of IP Accuracy limit primary current = fL.IN Burden :SN
Class e 5 P 10 P Ratio error at In 1 % 3 % Phase displacemen t at In 60 min. Composite error at fL.IN 5 % 10 %
21
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
1. Accuracy Limiting Factor What is Accuracy Limiting factor ? It is the factor of over current above the rated current which determines the capability of CT to maintain the error at such a condition. 2. Composite error It is the error of the CT when this over current is applied.
22
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Example
Accuracy Limiting Factor/composite error For e.g if the class designation is 5P20 20 is the Accuracy limiting factor which signifies that when 20 times the rated primary current is applied the composite error of 5P( +/- 5%) is maintained.
23
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
CVT
24
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
P1 C1
S1
C2
P2
25 E T PS-HVDC-COE- Karikalan.M
S2
Siemens Ltd
Inductive VT
26 E T PS-HVDC-COE- Karikalan.M Siemens Ltd
CVT Secondary Voltage v = k * V * C1/ (C1+C2) V Primary Voltage k Secondary Transformation ratio Note: Puncturing of C1 Secondary Voltage will increase Puncturing of C2 Secondary Voltage will decrease
27
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
VT
28
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Voltage Transformer :
Primary
U1
n1
K: Transformation ratio
U1 n1 K U2 n2
n2
U2
Secondary
29 E T PS-HVDC-COE- Karikalan.M Siemens Ltd
Transformer
30
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Transformer A transformer is a device that transfers electrical energy from one circuit to another through inductively coupled conductors (the transformer's coils) without change in frequency. A major application of transformers is to increase voltage before transmitting electrical energy over long distances through wires. By transforming electrical power to a high-voltage (and therefore low-current) form for transmission and back again afterward, transformers enable economical transmission of power over long distances.
31
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Power Transformer
32
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Convertor Transformer
33
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
34
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
ISOLATORS/DIS CONNECTORS
Isolators (also referred as disconnectors) are off-load type switches. TYPES OF ISOLATORS
35
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
ISOLATORS/DIS CONNECTORS
36
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Wave Trap
37
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
38
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Surge arrester
39
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Surge Arrestor An electrical appliance used to protect electronic equipment against lightning overvoltage transients. It is usually connected to wires (power phase line, signal line, zero line) and ground between being protective devices in parallel.
During the lightning over-voltage the arrestor immediately limits the over-voltage amplitude which leads to protection of the equipment and systems, enabling the system to work properly.
40
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Surge Arrestor
41
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Bus Bar
42
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
36
72.5 123 145
320
630 900 (1100*) 1100 (1300*)
320
630 900 (1100*) 1100 (1300*)
2800
3000 3500 (4000*) 4000
43
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
AC C&P Design
SUB-STATION BUSBAR ARRANGEMENT Bus-bars are the part of the sub-station where all the power is concentrated.
The power from the sources is collected on the bus-bars by connecting the incoming lines.
The power is distributed from the bus-bars by connecting the outgoing lines to them.
44
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Auxillary Power Engineering SINGLE BUSBAR SCHEME In this arrangement of bus-bars, all incoming and outgoing feeders are connected to the same bus. This type of bus-bar system is used mostly in small AC stations (low & medium voltage stations) This arrangement has the following advantages: Low initial cost since each feeder has only one bus-bar Relaying scheme is simple Due to single breaker for one circuit, operation is very simple Low Maintenance cost.
45
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Software Design
This arrangement has the following disadvantages: All generators and incoming lines connected to the same bus lead to a high fault level on the bus In case of any maintenance work on any part of the bus-bar, the whole station has to be shut down In case of any fault on the bus-bar, there is complete outage of the whole station
In case of maintenance work on any feeder circuit breaker, the feeder has to be disconnected till the work is completed
46
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
This scheme is an improvement over the single bus-bar scheme . The bus-bar has been split up into two parts with the feeders distributed over the two sections. This arrangement has the following advantages: Fault level of the bus due to incoming feeders can be reduced by operating the system with the bus-sectionaliser open
During fault on bus-bar, the whole station does not suffer complete outage Maintenance work can be carried out on one half of the bus-bars by taking it out of service instead of the whole station
47 E T PS-HVDC-COE- Karikalan.M Siemens Ltd
This scheme is very common in low and medium voltage substations, particularly for indoor switchboards. Grid sub-stations do not adopt this arrangement since it does not offer a completely reliable bus-bar system.
48
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
The single bus-bar scheme can be provided some flexibility by adding an additional bus-bar called the transfer bus-bar.
With this transfer bus, one feeder from the main bus can be connected to the transfer bus, thus freeing the circuit breaker of the feeder for maintenance. This scheme is mostly used in 132 KV or lower voltage sub-stations at the distribution level.
49
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
SINGLE MAIN AND TRANSFER BUSBAR SCHEME Advantages and Disadvantages This scheme combines the low cost and simplicity of single bus-bar scheme with a limited degree of flexibility. Whenever any feeder circuit breaker has to be taken for maintenance, the feeder is connected to the transfer bus through the transfer bus isolator and the transfer breaker. This arrangement does not offer any increased degree of reliability, it only provides the flexibility of maintenance of a circuit breaker without taking outage of line or bus-bar
50
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
In this system, there are two main bus-bars and each feeder has disconnectors that can connect the feeder to any bus-bar.
Thus some generators and feeders can be connected to any one bus-bar and the remaining generators and feeders to other bus-bar.
we can have two systems running in the same station and any generator or feeder can be switched to any one system
51
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
52
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
The double bus-bar systems are mostly used in generating stations and grid sub-stations at higher voltages (usually 220KV and 132KV in India) where reliability and availability are critical issues.
53
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Limitation of Double Bus Scheme: With this arrangement, any change-over from one bus to another has to be done under off-load conditions since the disconnectors are not made for switching loads and the two bus-bars are not connected together and hence there is no synchronism between the two bus-bars
54
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Now, any feeder can be changed over from one bus-bar to another without switching off, the only condition for doing so is that the bus-coupler should be closed with its disconnectors and the feeder disconnector connecting the incoming bus has to be closed first and then the other disconnector can be opened.
55
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
we have seen an arrangement that enables maintenance of circuit breaker without taking the feeder out of service. This was possible by addition of the transfer bus-bar and the transfer breaker.
56
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
Advantages: In both the double bus with coupler and double main with transfer schemes, during instances of bus faults, the faulty bus can be identified and all feeders taken on the healthy bus-bar while maintenance on the faulty bus can be carried out . Dis-advantages: In case of bus-fault, all breakers connected to the faulty bus-bar trip and thus the corresponding feeders are out of service. Till the faulty bus-bar is isolated and the feeders connected back to the healthy bus-bar and the breakers switched on again.
57
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
HERE TWO FEEDERS ARE CONTROLED BY THREE BREAKERS. SO THESE TWO FEEDERS CONTROLLED BY THREE CIRCUIT BREAKERS IT IS CALLED ONE & HALF BREAKER SYSTEM.
58
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
59
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
60
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
61
E T PS-HVDC-COE- Karikalan.M
Siemens Ltd
THANK YOU