Beruflich Dokumente
Kultur Dokumente
GE Multilin
Outline
Bus arrangements
Bus components Bus protection techniques CT Saturation Application Considerations: High impedance bus differential relaying Low impedance bus differential relaying Special topics
Distribution and lower transmission voltage levels No operating flexibility Fault on the bus trips all circuit breakers
Transmission and distribution voltage levels Breaker maintenance without circuit removal Fault on a bus disconnects only the circuits being connected to that bus
5 GE Consumer & Industrial Multilin 17-Feb-13
Increased operating flexibility A bus fault requires tripping all breakers Transfer bus for breaker maintenance
6 GE Consumer & Industrial Multilin 17-Feb-13
High operating flexibility Line protection covers bus section between two CTs Fault on a bus does not disturb the power to circuits
8 GE Consumer & Industrial Multilin 17-Feb-13
Breaker-and-a-half bus
Used on higher voltage levels More operating flexibility Requires more breakers Middle bus sections covered by line or other equipment protection
Ring bus
Higher voltage levels High operating flexibility with minimum breakers Separate bus protection not required at line positions
10 GE Consumer & Industrial Multilin 17-Feb-13
Bus components
breakers
Current Transformers
Gas (SF6) insulated current transformer Oil insulated current transformer (35kV up to 800kV)
Protection Requirements
High bus fault currents due to large number of circuits connected:
CT saturation often becomes a problem as CTs may not be sufficiently rated for worst fault condition case large dynamic forces associated with bus faults require fast clearing times in order to reduce equipment damage
With both dependability and security important, preference is always given to security
14 GE Consumer & Industrial Multilin 17-Feb-13
Interlocking Schemes
Blocking scheme typically used Short coordination time required Care must be taken with possible saturation of feeder CTs Blocking signal could be sent over communications ports (peer-to-peer) This technique is limited to simple one-incomer distribution buses
16 GE Consumer & Industrial Multilin 17-Feb-13
Linear Couplers
40 V
10 V
10 V
0V
20 V
0V
59
External Fault
If = 8000 A 2000 A 2000 A 0A 4000 A
18 GE Consumer & Industrial Multilin 17-Feb-13
Linear Couplers
Esec= Iprim*Xm - secondary voltage on relay terminals IR= Iprim*Xm /(ZR+ZC) minimum operating current
where, Iprim primary current in each circuit Xm liner coupler mutual reactance (5V per 1000Amps => 0.005 @ 60Hz ) ZR relay tap impedance ZC sum of all linear coupler self impedances
If = 8000 A Internal Bus
Fault
40 V 0V 10 V 10 V 0V 20 V
59
0A
2000 A
2000 A
0A
4000 A
Linear Couplers
Fast, secure and proven Require dedicated air gap CTs, which may not be used for any other protection Cannot be easily applied to reconfigurable buses The scheme uses a simple voltage detector it does not provide benefits of a microprocessor-based relay (e.g. oscillography, breaker failure protection, other functions)
Overvoltage element operates on voltage developed across resistor connected in secondary circuit
o
Percent Differential
Percent characteristic used to cope with CT saturation and other errors Restraining signal can be formed in a number of ways No dedicated CTs needed Used for protection of reconfigurable buses possible
Additional algorithms improve security of percent differential characteristic during CT saturation Dynamic bus replica allows application to reconfigurable buses
o Done digitally with logic to add/remove current inputs from differential
CT Saturation
CT Saturation Concepts
CT saturation depends on a number of factors o Physical CT characteristics (size, rating, winding resistance, saturation voltage) o Connected CT secondary burden (wires + relays) o Primary current magnitude, DC offset (system X/R) o Residual flux in CT core Actual CT secondary currents may not behave in the same manner as the ratio (scaled primary) current during faults End result is spurious differential current appearing in the summation of the secondary currents which may cause differential elements to operate if additional security is not applied
CT Saturation
No DC Offset
Waveform remains fairly symmetrical
With DC Offset
Waveform starts off being asymmetrical, then symmetrical in steady state
29 GE Consumer & Industrial Multilin 17-Feb-13
t1 t0
Ideal CTs have no saturation or mismatch errors thus produce no differential current
t1
t0
Actual CTs do introduce errors, producing some differential current (without CT saturation)
t1
t0
CT saturation causes increasing differential current that may enter the differential element operate region.
evolving faults
spurious differential current needed to incorrectly trip o Difficult to explicitly develop settings (Is 60% slope enough? Should it be 75%?)
asserting the differential element o Easy to implement and test o Stable even under severe CT saturation during external faults
33 GE Consumer & Industrial Multilin 17-Feb-13
RST = 2000 - stabilizing resistor to limit the current through the relay, and force it to the lower impedance CT windings. MOV Metal Oxide Varistor to limit the voltage to 1900 Volts 86 latching contact preventing the resistors from overheating after the fault is detected
Different CT Ratio Capability for Each Circuit Largest CT Primary is Base in Relay
CB 11
CB 12
scaled sum of
geometrical average
maximum of
50 GE Consumer & Industrial Multilin 17-Feb-13
Max Of Approach
Less restraint on external faults; more sensitive for internal faults Breakpoint settings for the percent differential characteristic easier to set Better handles situation where one CT may saturate completely (99% slope settings possible)
DIFL
DIR OR
SAT
DIFH
AND
53 GE Consumer & Industrial Multilin 17-Feb-13
CT Saturation
t2
t1
t0
SAT := 0 The differential current below the first slope for certain period of time saturation condition
EXTERNAL FAULT
SAT := 1
The differential characteristic entered
EXTERNAL FAULT & CT SATURATION
The differentialrestraining trajectory out of the differential characteristic for certain period of time
SAT := 1
~1 ms
current, A
0.07
0.08
0.09
0.1
0.11
0.12
time, sec
Despite heavy CT saturation the external fault current is seen in the opposite direction 60 GE Consumer & Industrial Multilin 17-Feb-13
Configuring CT Inputs
For each connected CT circuit enter Primary rating and select Secondary rating. Each 3-phase bank of CT inputs must be assigned to a Signal Source that is used to define the Bus Zone and Dynamic Bus Replica
Some relays define 1 p.u. as the maximum primary current of all of the CTs connected in the given Bus Zone
63 GE Consumer & Industrial Multilin 17-Feb-13
F1
F2 F3
3200 A
2400 A 1200 A
1A
5A 1A
1
1 1
F4
F5 F6
3200 A
1200 A 5000 A
1A
5A 5A
2
2 2
CT Primary and Secondary values Both 5 A and 1 A inputs are supported by the UR hardware Ratio compensation done automatically for CT ratio differences up to 32:1
2. Configure AC Signal Sources 3. Configure Bus Zone with Dynamic Bus Replica
66 GE Consumer & Industrial Multilin 17-Feb-13
Min Pickup
Low Breakpoint
All settings entered in per unit (maximum CT primary in the zone) Slope settings entered in percent Low Slope, High Slope and High Breakpoint settings are used by the CT Saturation Detector and define the Region 1 Area (2-out-of-2 operation with Directional)
Min Pickup
Low Breakpoint
Reconfigurable Buses
Reconfigurable Buses
Reconfigurable Buses
Reconfigurable Buses
Isolators
Reliable Isolator Closed signals are needed for the Dynamic Bus Replica In simple applications, a single normally closed contact may be sufficient For maximum safety:
o Both N.O. and N.C. contacts should be used o Isolator Alarm should be established and non-valid combinations
(open-open, closed-closed) should be sorted out o Switching operations should be inhibited until bus image is recognized with 100% accuracy o Optionally block 87B operation from Isolator Alarm
No
NOTE: Isolator monitoring function may be a built-in feature or userprogrammable in low impedance bus differential digital relays
CT Trouble operand is used to rise an alarm The 87B trip is inhibited after CT Trouble element operates The relay may misoperate if an external fault occurs after CT trouble but before the CT trouble condition is declared (double-contingency)
85 GE Consumer & Industrial Multilin 17-Feb-13
Trip
Trip
Trip
Breaker Fail Op command generated here and send to trip appropriate breakers
IEEE 37.234
Guide for Protective Relay Applications to Power System Buses is currently being revised by the K14 Working Group of the IEEE Power System Relaying Committee.