Sie sind auf Seite 1von 30

http://www.studygalaxy.

com/

POWER PLANT EMERGENECIES

26 February 2013

PMI Revision 00

Presentation outline
Boiler Emergencies

Turbine Emergencies
Generator Emergencies

Grid Failure

26 February 2013

PMI Revision 00

BOILER

26 February 2013

PMI Revision 00

HIGH FURNACE PRESSURE


One I.D. Fan tripped or Mal-operation of control vanes of I.D./F.D./P.A. Fans or closing of damper Unstable furnace flame conditions. Sudden starting of coal mill. Furnace water seal broken, E.P. or flue gas path manhole opened. Water wall tube rupture/leakage.

26 February 2013

PMI Revision 00

ID FAN LUB. OIL PRESSURE / BEARING TEMP TROUBLE


Lub. oil pressure may be inadequate. Lub. oil filters may be choked. Greasing long overdue in fan bearings. Corresponding alarm will indicate the problem area.

26 February 2013

PMI Revision 00

ID FAN TRIP
Motor over-loaded. Corresponding FD Fan has tripped. Spurious electrical fault. Lub. Oil pressure problem. Bearing temperature problem. Corresponding APH may have tripped.

26 February 2013

PMI Revision 00

FURNACE PRESSURE LOW


I.D. Fan auto control Failure. I.D. Fan vane control mechanism Failure causing vanes to open wide. Sudden decrease in air input or tripping of one F. D. fan. Sudden tripping of one or more mills or choking of mill/raw coal Feeder pipe.

26 February 2013

PMI Revision 00

FD FAN TRIPPED
Motor over-loaded Lub oil pressure trouble. Bearing temperature trouble. ID fan has tripped. FD lub. Oil pressure low.

26 February 2013

PMI Revision 00

PA FAN TRIPPED
tripping is due to high bearing temp. Boiler has tripped. Lub. Oil pressure may be very low. It will lead to tripping of some mills in service.

26 February 2013

PMI Revision 00

AIR PRE-HEATER
AIR PRE HEATER BEARING TEMPERATURE VERY HIGH. AIR PRE-HEATER ELECTRIC MOTOR TRIPPED. APH ELECTRIC DRIVE TRIPPED AND AIR MOTOR FAILS TO START. AIR PRE-HEATER ON FIRE.

26 February 2013

PMI Revision 00

10

DRUM LEVEL LOW


Mal-operation of Feed Auto Control or Feed Regulator or scoop auto. Tripping of one of working feed pump (standby pump does not start) Sudden increase of load. Sudden increase in firing rate, e.g. starting of mills having sufficient coal left before previous stopping. Tube repture/puncture of low point drain valves or Emergency drum drain Valve Inadvertant opening of low point drain valves or Emergency drum drain valve.

26 February 2013

PMI Revision 00

11

HIGH DRUM LEVEL


Mal-operation of feed water control. Sudden decrease in firing rate e.g. tripping of the running mills. B.F.P. Scoop tube position suddenly increased.

26 February 2013

PMI Revision 00

12

FLAME FAILURE AT AN ELEVATION


Closing of trip valves on H.O. , W.U. Oil/ Ignitor (Causing loss of ignition support energy) Where F.O. is being used as support fuel or when only oil is being used Sudden decrease of mill feeder speeds to minimum. Too low or too high windbox pressure causing unstable combustion. Water wall tube failure Malfunction of flame scanners due to supply failure or scanner air failure, slag or soot on scanner lenses etc. Burner tilt mechanism negative extreme due to air failure to power cylinders.

26 February 2013

PMI Revision 00

13

ONE FEEDER TRIPS


Support energy is removed within 3 minutes of feeder starting. No coal flow alarm comes & low current relay picks up simultaneously. (Feeder shear pin given way) Mill trips, Feeder motor supply fails

26 February 2013

PMI Revision 00

14

ONE MILL TRIPS


Mill discharge valves are closed Loss of elevation D.C. supply for more than 2 secs. Support ignition energy is removed Within 3 minutes of feeder starting. Motor protection operates. One P.A. Fan trips (mill in excess of 3 will trip starting from bottom).

26 February 2013

PMI Revision 00

15

WATER MILL TUBE LEAKAGE


Starved water walls due to very low drum level. Sustained flame impingement on water wall tubes. Blocked tube, scaling of tube, resulting in overheating of tube metal, pitting, corrosion of tubes. Soot blower steam impingement (wet steam impingement or direct impingement of steam). Circulation affected due to opening of low point drains.

26 February 2013

PMI Revision 00

16

REHEATER/SUPFRHEATER/ ECONOMISER TUBE FAILURE


Sustained high metal temperatures due to waterwall Slagging or forcing boiler at the time of hot restart. Erosion on tubes due to high excess air, high ash content in coal dislocated tubes, soot blowing. Blocked tubes causing overheating. Salt deposition due to high water level in drum, poor quality of water. Inadequate flow due to open superheater, reheater drain.

26 February 2013

PMI Revision 00

17

Continuous watch on ash build up Reduce load Stopping of unit

Problem in Bottom Ashing System

26 February 2013

PMI Revision 00

18

TURBINE

26 February 2013

PMI Revision 00

19

TURBINE EMERGENCIES
SUDDEN LOAD THROW OFF SUDDEN INCREASE OF LOAD FROM FULL LOAD VIBRATION HIGH TURBINE OVER SPEED MOT LEVEL LOW TURBINE BEARING OIL PRESS LOW BEARING OIL INLET TEMP. HIGH DIFFERENTIAL EXPANSION HI/LOW AXIAL SHIFT HIGH LOSS OF VACUUM LOSS OF BARRING GEAR OR BARRING GEAR FAILS TO START

26 February 2013

PMI Revision 00

20

HOTWELL LEVEL LOW


Excessive flow to D/A from Hotwell Some leakage in steam/water (feed) circuit (waterwall super heater, Economiser etc.). ACS Xmitter failure/fault. DM make-up may be inadequate. DM make up pump may have tripped.

26 February 2013

PMI Revision 00

21

HOTWELL LEVEL HIGH.


Malfunctioning of condensate PP valve Malfunctioning of DM make up valve. Condenser tube leakage Too much DM make-up to Hotwell. Hotwell set point too high. ACS transmitter fault. Condensate pumps may have tripped

26 February 2013

PMI Revision 00

22

LOSS OF VACUUM
Steam ejector not properly functioning. High level in condenser LOSS OF CIRCULATING WATER PUMP Air leak into system Condenser tube choking CW inlet water temp hi.

26 February 2013

PMI Revision 00

23

BOILER FEED PUMP


BFP RE-CIRCULATION VALVE FAILS CLOSED. BFP LOSS OF LUB. OIL PRESSURE BFP BEARING VIBRATION HIGH BFP HYDRAULIC COUPLING OUTLET OIL TEMPERATURE IS GOING HIGH. BFP SUCTION PRESSURE IS FALLING LOW. BOILER FEED PUMP MASTER SPEED CONTROLLER FAILS HIGH.

26 February 2013

PMI Revision 00

24

GENERATOR

26 February 2013

PMI Revision 00

25

Generator emergencies
Stator Water Flow Low Stator Water Conductivity High Hydrogen Pressure Low/Hydrogen leakage Hydrogen Purity Low Seal Oil Differential pr low Liquid in Generator Generator Stator Cooling Water Leakage Damper Tank Level Low Rotor Temperature High Stator Winding Temperature High Loss of Excitation Generator Transformer Cooling System Trouble Generator Rotor Earth Fault.

26 February 2013

PMI Revision 00

26

GRID FAILURE
1.DC lighting ON ( Torch light must be available at least in night shift). 2. Ensure starting of emergency DC drives: -Gen Seal Oil pump. -LOP of main TG -Scanner air fan. Then monitor battery voltage and current. 3. Ensure starting of air motors of APHs. 4. Open vacuum breaker manually. Close MOT oil centrifuge supply vv. Close SB isolation vv. Close gland steam supply vv.

26 February 2013

PMI Revision 00

27

GRID FAILURE
5.Ensure starting of DG set ,charging of EMCC and then changing over of emergency drives. 6.Open the incomer breakers of switch gears and transformers (motor breakers tripped on no voltage ). 7.After normalization of EMCC TVDC,BVDC AND BDDC power supply will restore. So care must be taken so that condenser/FT etc. will not

26 February 2013

PMI Revision 00

28

MISCELLANEOUS SYSTEMS
LOSS OF STATION AIR PRESSURE. LOSS OF INSTRUMENT AIR PRESSURE. BOILER WATER SILICA HIGH. ELECTRICAL TRIPPING OF SUPPLY TO THE BOARD.

26 February 2013

PMI Revision 00

29

THANK YOU

26 February 2013

PMI Revision 00

30

Das könnte Ihnen auch gefallen