CT under Flames
Types of CTs
5. Porcelain insulator
6. Primary conductor with insulation 7. Adaptor cylinder 8. Secondary cores
9. Base
10. Oil drain plug
5. Primary terminal
6. Porcelain insulator 7. Insulated primary 8. Cover plate for tank
9. Tank
10. Secondary cores
CT Design
Core Material The main aim is to give high accuracy with low saturation factor. Core Material is made of CRGO Silicon steel
For very low loss characteristics, material (Alloy of Ni-Fe) is used
Condition Monitoring
Checking of Bellow expansion - M
CT Insulation
CTs with Test Tap- Ungrounded Specimen Test mode (UST) CTs without Test Taps Grounded Specimen Test (GST) mode with jumpers disconnected Values to be monitored w.r.t. factory/ precommissioning values Sudden change in measured values indicate faster deterioration of insulation. Precautions: P1/P2 to be shorted. Porcelain surface to be thoroughly cleaned. Test Tap to be reconnected to Earth after the Test
Connection of Test Tap to be ensured otherwise it may lead to slow arcing in the soldering area and insulation may fail in due course of time. Measurement of Tan Delta of C2 (insulation between last foil on which test tap wire is soldered to the ground) to be carried out. Measurement in GSTg mode with P1/P2 terminal guarded.
Either Bellow or Nitrogen is provided for oil expansion CT with Nitrogen cushion need to be kept under positive pressure Can be tested where provision is available If found without pressure, Nitrogen to be filled
As CT is a sealed unit, DGA of oil indicates electrical/ thermal action inside the CT Quantity of oil to be sampled to be limited as less oil quantity is available. To be carried out as special test You may face opposition from manufacturers for taking oil samples