DC Power, Heat Dissipation & Cooling Requirements
January 2008
DC Power Requirements
DC Power Requirements
Use the following table to calculate worst-case power source requirements for the Base Station equipment:
Excluding the PIU, the total power that should be supplied by PSUs is 293W. Since each PSU can support a maximum of 200W, we need at least 2 PSUs. A third PSU will support a 2+1 redundancy.
[ 2176 ] + 481 = 2657W Average Power Consumption: Average power consumption of 24 ODUs, assuming DL-UL (Tx/Rx) ratio of 60-40: AU-ODUs: [89W * .60] * 4 = 214W (DL power consumption - directly from PIU) [15W * .40] * 4 = 24W (UL power consumption directly from PIU) [89W * .60] * 20 = 1068 (DL power consumed from ODU Power Feeders) [15W * .40] * 20 = 120W (UL power consumed from ODU Power Feeders) Power Feeders: 2W * 20 = 40W
Average Power Total: [214+24+1068+120+40]
10
Heat Dissipation
Use the following formula to calculate the heat dissipation for each Base Station:
[(Module 1 power consumption) + (Module 2 power consumption) + (Module N power consumption)] x 2.3884 = BTU
Example:
Base Station with 3 AU-IDUs and 1 NPU, the heat dissipation is as follows: PIU: 30W AVU: 24W PSU: 200W NPU: 65W AU-IDU: 41W * 3 = 123W Total: [30 + 24 + 200 + 65 + 123] x 2.3884 = 1056 BTU
11
Cooling Requirements
The BreezeMAX Chassis is intended for mounting in a cabinet or other rigid framework which is fixed to the building.
The BreezeMAX chassis is cooled by the flow of air between the elements mounted in the cabinet.
The fans and air baffles ensure that sufficient air flows between the elements. The cooling system, including the baffle and fan tray, is supplied with each chassis and is an integral part of the BreezeMAX chassis. It does not require separate installation.