Beruflich Dokumente
Kultur Dokumente
Presenter
Reference Data
(EEMUA) Engineering Equipment and Materials User Associations Publication No. 191:99 Alarm Systems - A Guide to
Design, Management and Procurement
ANSI/ISA-84.00.01-2004; Application of
Safety Instrumented Systems for the Process Industries
Sensors
Historian Logger
BPCS
HMI
Process
Interface
9 2
Identification
Design
8 6
Operation Monitoring
7
Shutdown/ Disposal
This simple model is a useful reference in the development of alarm principles and the alarm philosophy. The warnings and indications are not to suggest alarms are required, only that under some circumstances alarms may be warranted.
Trip Indication
Upset Indication
Pre-Upset Warning
Off-Target Indication
Describes the overwhelming majority of alarms and therefore serve as a useful model for the development of alarm system principles. .
Alarm Timeline
Normal (A) New Alarm (B) Ackd & response (C)
consequence threshold
Process Variable
sensor
deadband delay
alarm limit sensor & error delay Ack delay operator response delay alarm limit deadband process response delay
process deadtime
Time
Using the state transition diagram it is possible to map some states to a timeline, and clarify the definition of terms related to time. The diagram shows parallel lines representing true process conditions and the indicated process condition. The lines have two possible paths; one path if the operator takes corrective action and one path if no action is taken.
10
Reference: Trends in Process Safety, Asish Ghosh, ARC Advisory Group, July 2004
12
13
ENG
HMI
ENG
INTERFACED
DCS
Gateway
SIS
ENG
HMI
INTEGRATED
DCS
SIS
ENG
HMI
COMMON
DCS
SIS
14
Gateway
BPCS
HMI
SIS
BPCS
PS
ESD action
Trip Point
Pressure
SV
PCV
PT1
PT2
Process Control
Normal Pressure
Low level
15
Alarm requirements
Provide Operator Training Define Operator action Validated everything
DO DO DI AI AI
Simplex
DO DO DI AI AI
Dual
1oo1 LS
Triple
AI
1oo2 Valves
2oo3 PT
16
17
18
EEMUA studies have shown that to maximize operator effectiveness, no more than three different sets of alarm priorities should be configured in a system.
19
20
21
Conclusions
Proper alarm management CAN be used as a method of risk reduction by reducing the demand rate on the SIS providing:
1.The sensor is not used for control purposes where loss of control would lead to a demand on the SIF 2.The sensor is not used as part of the SIS 3.Limits taken into account with respect to risk reduction that can be claimed for the BPCS and common cause issues.
The alarm interfaces between the SIS and the operator need to be fully described (pre-shutdown alarms, shutdown alarms, bypass alarms, diagnostic alarms), graphics,
22
Thanks
Charles.Fialkowski@siemens.com
23