Beruflich Dokumente
Kultur Dokumente
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.
Page 4
Page 7 Page 14 Page 39 Page 44
Not Duplicated:
Circuit Breakers
Objective:
Page 4
Page 7 Page 14 Page 39 Page 44
A 21A
B 21B
Advantages Not affected by local station conditions Contributes to both relay and CB failure protection
Breaker Fail Protection Considerations - P 6
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Limited Discrimination
21
21
V I
V I
Fault Point
Fault Point
~ ~ ~
Breaker Fail Protection Considerations - P 8
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Disadvantages
Security
Dependability
Breaker Fail Protection Considerations - P 9
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Provision of duplicated main protection schemes Cannot duplicate the circuit breakers (usually) Can duplicate trip coils
Still common physical mechanism failures still possible Used to backtrip fault infeeds in case of local break failure Only initiated when tripping has occurred Sometimes called Stuck Breaker Protection or Backtripping Protection
Trip Circuit Supervision should be considered as part of the local backup facility
Breaker Fail Protection Considerations - P 10
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
AUX. DC SUPPLY
CT
MAIN 1 PROTECTION
MAIN 2 PROTECTION
TCS1
TCS2
TC 1
TRIP COILS
TC 2
CIRCUIT BREAKER
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
M2A
M2B
TC2A
M2B
TC2B
Circuit A
Circuit B
AUX. DC SUPPLY
CT
MAIN 1 PROTECTION
MAIN 2 PROTECTION
TCS1
TCS2
TC 1
TRIP COILS
TC 2
CIRCUIT BREAKER
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
D B Trip
MAIN PROTECTION
Fault Intertrip
Breaker Fail Protection Considerations - P 14
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Page 4
Page 7 Page 17 Page 39 Page 44
Typical Schemes
Simplest Scheme No Current Check
+
Main 1 Main 2
TC1 TC2
Prot Op.
Protection Reset Time (Max)
Backtrip
Error In Timer Safety Margin
Setting Of Timer
86
Disadvantages of this simple scheme Long total fault clearance times due to long timer setting Security of scheme Risk of initiation during testing causing widespread system disruption
Typical Schemes
Simple Scheme Use of CB Auxiliary Contact
+
Main 1 Main 2
TC1 TC2
Prot Op.
Backtrip
Error In Timer Safety Margin
52a
Setting Of Timer
Advantage of this scheme is that we dont need to consider the main protection reset time so fault clearance time is much reduced
86
Disadvantages of this simple scheme Security of scheme Risk of initiation during testing causing widespread system disruption
Typical Schemes
Simple Scheme Use of CB Auxiliary Contact
+
Main 1 Main 2
TC1 TC2
Prot Op.
Backtrip
Safety Margin
52a
Setting Of Timer
86
Additional improvement by including the CB auxiliary contact in the back tripping path Removes timer overshoot Increased security of tripping But, consider is it rational or proper to consider the breaker status in a CB failure protection scheme?
Typical Schemes
Simple Scheme Use of BF Current Detector
+
Main 1 Main 2
TC1 TC2
Prot Op.
50BF Reset Time
Backtrip
Safety Margin
50BF
Setting Of Timer Advantages of this scheme are: 50BF designed for fast reset so improved total fault clearance times Security enhanced by two elements being required to operate for timer initiation Disadvantages of this scheme 50BF must be set greater than maximum load current (if security is to be maintained)
86
Desirable Features
Desirable Features
Sensitivity
Minimum Plant Conditions Fault Position Operation Factor (or whats instantaneous!) Relay Drop Off / Pick Up Ratio Generator Circuits Large Inductive Circuits We NEED to achieve a setting of less than full load current
Breaker Fail Protection Considerations - P 21
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Desirable Features
Switching Large Inductive Loads CB Resistor Current
For Large Inductive Loads special circuit breakers are applied, utilising dual breakers: Main CB contacts opens first The resistor is used to reduce the switching overvoltages The auxiliary CB opens 1 or 2 cycles later BF current detector should NOT remain operated for the resistor current IR, but The minimum fault level MUST take priority (in which case the timer setting would need to allow for auxiliary CB operation)
IR
Desirable Features
Current Settings below Full Load Current
MAIN B.F.
+
B/F
If the Breaker Fail Current check is to be set below full load, it must only be switched into service when required: Inhibited during normal conditions For static type relays: Control application of auxiliary power to the 50BF relay
2 86
For numerical relays: Software control Exact operation depends upon relay
Applies to transmission levels (400/275kV) In general, 20% (minimum IF of 55%) Generator Circuits, 5% Inductive Loads, 80% (20% if IF<180%)
Theoretically, in order to set the BF timer we should consider: CB Trip Time Main contact seperation time (Arc Out) Or Resistor contact seperation time Current Detector Operation time, and Reset time Main Protection Reset time Discriminating (Safety) Margin Maximum permitted fault clearance times
Breaker Fail Protection Considerations - P 25
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Fault On
Fault Cleared
BF Init
BF Reset
86
Fault On
Arc Out
Fault Cleared
50BF
Timer Started
86
Main 1 SV Main 2
TC 1
TC 2
50BF
Advantages of 2-stage approach With lack of use, circuit breakers will become sticky Start verifier, re-strikes the trip coil and may overcome the initial reluctance of the CB to open First stage may be time-delayed (if preferred) but will extend overall fault clearance
Disadvantages Breaker fail timer setting must be set longer and overall fault clearance time is longer
50BF 52a
SV
Timer
SV Op. A (50)
Arc Out
Safety Margin D
(50) (10) C BF RESET (50)
Fault Cleared
(10)
(10)
86 OP.
Desirable Features
Security & Dependability
Security
Duplication with Series connections For example, duplicate current detectors & timers AND logic: 2 out of 2 Duplication with Parallel connections OR logic: 1 out of 2 Cater for single contingency failure
Dependability
Desirable Features
+
Main Prot
T1B T2B
T1A T2A
86
Unit DC Supply No 1
+
Unit DC Supply No 2
T1 A T1 B
T2 A T2 B
+
Breaker Fail Protection Considerations - P 31
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Desirable Features
Selectivity & Cabling
BF BF BF
Breaker fail scheme needs to: Intertrip remote infeed Backtrip all local feeds
Problems: Cabling cost Cabling complexity for all but the simplest schemes
Easy to make an error
It may be acceptable to integrate the backtripping into the local busbar protection
Desirable Features
Selectivity & Cabling Double Bus Systems
MI(A) MI(B)
TC B
50BF(A) MI(A) MI(B) MI(C) RI(A) MI(A) RI(A) RI(B) RI(C) etc. RI(A) RI(B) MI(C)
RI(C)
TC C
50BF
Cct A Cct B
50BF
50 BF Cct C
As can be seen, lots of auxiliary contacts will be required for a segregated backtrip system Is it more secure? Do we duplicate the breaker fail protection scheme to increase dependability & security?
50 BF(A)
50 BF(B)
50 BF(C)
BB TR (A)
BB TR (B)
BB TR (C)
INT (C)
50BFT (C)-2
MI RI MI A
MI RI MI RI B
MI
RI
C BF (B) 50BF (B) 50BFT (B) BF (C) 50BF (C) 50BFT (C) MTR RTR RI MI
MI
RI
BB TR(A)
INT (A)
MI
RI
BB TR(B)
INT (B) MT R RT R
50BFT (A)
50BFT(B )
50BFT (C)
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
TC1
TC2
CH T1B TR T2B
29L 52a
INT
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Page 4
Page 7 Page 17 Page 39 Page 44
50BF ABC
Fault On
Arc Out
C
Timer BFABC Init.
Timer Start
BFA Reset
BFBC Reset
86 OP
86
Trip Adjacent Circuits & Intertrip
Breaker Fail Timer setting: A+E+C+D-B = 145msecs Total Fault Clearance time (of CB Fail) 250msecs With Common BF initiation during single phase trpis, load current will prevent fast reset of the CB Fail current check device
Timer
Fault On
Arc Out
A (40) (50)
Timer Start
BFABC Init.
BFABC Op
86 OP
A B C
86
Trip Adjacent Circuits & Intertrip
Breaker Fail Timer setting: A+C+D-B = 135msecs Total Fault Clearance time (of CB Fail) 240msecs With Common BF initiation during single phase trpis, load current will prevent fast reset of the CB Fail current check device
Fault On
Main Prot Op
Fault Cleared
(40)
(5) B
(50)
(10)
(50)
(10)
(50)
Timer
86
Breaker Fail Timer setting: A+C+D-B = 105msecs Total Fault Clearance time (of CB Fail) 210msecs Phase segregated control of CB fail current check relay required to remove main protection reset time from setting consideration
BFA Init.
Timer Start
BFA Reset
86 OP
Page 4
Page 7 Page 17 Page 39 Page 44
Non-Conventional Techniques
Traditional CB Fail protection schemes utilise overcurrent technology Control inputs to energise the detection unit under appropriate conditions only i.e during a fault. This permits: Need to be designed correctly to ensure:
Low current thresholds good sensitivity & speed Allow for good thermal withstand
Fast energisation Fast resetting and very close to pick-up setting
Can suffer extended reset times during fast fault clearance due to a decaying DC current in the secondary circuit. Modern relays can achieve the same goals using different methods: Software control prevent operation except during fault situation, negating traditional issues associated with low current settings & thermal capacity Use of undercurrent type elements, or sampling relies on fast operation, not resetting Can account for or filter the DC currents preventing fast resetting on traditional overcurrent based technologies
Non-Conventional Techniques
Decaying DC Current after Fast Fault Clearance
At fault clearance, the flux within the core will still be at some value but this suggests that there is a magnetising current
E
Since the primary circuit is open, this magnetising current can only be present in the secondary circuit but it is not a sustainable state The CT will attempt to reach a stable state with no magnetising current The transition from the point on the flux curve to the point with no magnetising current (CT remenance) will cause a decaying DC component on the secondary circuit
Due to low current settings, this may be enough to prevent resetting of overcurrent elements (or operation of undercurrent elements)
Non-Conventional Techniques
Sampling Method of Current Check in CB Fail Schemes
The algorithm looks for successive positive going and negative going excursions above a positive and negative current threshold. If they are both above the current threshold and of oposite sign, current flow is still present i.e the CB has not opened.
Breaker Fail Protection Considerations - P 45
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Non-Conventional Techniques
Sampling Method of Current Check in CB Fail Schemes
In this case, the breaker fail timer is completed but the current check still indicates that the CB is closed. Therefore, a CB Fail condition is given.
Breaker Fail Protection Considerations - P 46
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Non-Conventional Techniques
Sampling Method of Current Check in CB Fail Schemes
In this case, the breaker fail timer is completed and the current check indicates that the CB is open, even in the presence of the decaying DC component due to the CB opening.
Breaker Fail Protection Considerations - P 47
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.