Reflect the strategic importance and scarcity value of water
Voluntary
3P approach Promote ownership of water conservation
Mandatory
Cut down on excessive flow and wastage of water
Pricing
Water Tariff Structure
W.e.f. 1 July 2000
Consumption block (m3 per mth) Tariff category
Tariff (/m3)
WCT (%)
Domestic
1 to 40 Above 40
30 45 30
Non-domestic
All units
WCT :
Mandatory
Installation of Water Saving Devices
Since 1983 Self-Closing Delayed-Action Taps
(non domestic premises including common amenities of condominiums)
Mandatory
Remarks
2 (toilets) 4 (others)
6
For self closing delayed action shower tap, timing shall remain at between 13 and 15 sec
9* 12 (hotels)
Other Areas
6
7
Website Portal
10
11
12
Excellent
Very Good Good
Washing Machine Basin/ Sink Tap
Shower Head Dual Flush Cistern
14
GOOD RATING
Shower Taps, Mixers & Showerheads (L/min) Basin Taps & Mixers (L/min) Sink/Bib Taps (L/min)
>7 to 9
6 8
>4 to 6 >6 to 8 >4.0 - 4.5 (full flush) > 2.5 -3.0 (low flush) > 1.0 to 1.5
>2 to 4 >4 to 6 >3.5 to 4.0 (full flush) > 2.5 3.0 (low flush) > 0.5 to 1.0
2 or less 4 or less 3.5 or less (1) (full flush) 2.5 or less (low flush) 0.5 or less (2) Or waterless urinals 9 or less
Flushing Cisterns Dual Flush Type (L/flush) Urinals & Urinal Flush Valve (L/flush) Washing Machine (L/Kg)
1.5
15
> 12 -15
> 9 -12
(1) (2)
To pass laboratory simulation test on waste transportation efficiency in pipe. To pass dilution test 15
WELS WEBSITE
www.sec.org.sg/wels.
16
17
18
19
20
21
22
(1) Submetering
Monitor water usage - Key element Sub-meters should be installed Installation of submeters/private meters on all major water systems, such as cooling tower, irrigation, hot water devices, etc.\ Know how water is used Identification of leak areas quickly Shall be accessible for meter readings and maintenance
23
Water Tank
Residential Units
m m
Sub meters
m
m
Public Toilets
m
24
Maintenance officers are encouraged to take water meter readings regularly (daily/weekly/fortnightly) Monitor the water consumption on a plotted graph Any sudden increase may indicate a leak in the system Investigate immediately Take prompt action to repair leaks, if any
25
main and sub-meters should be linked to a building management system (BMS) water usage trends can be recorded Alarm activated if there is a sudden increase in water consumption or a new trend in water consumption as this will indicate the possibility of a water leakage
26
27
Water Tank
Bulk Meter m
28
Encourage substitution with NEWater for non potable use eg. Air con cooling towers, process use, etc. Encourage recycling of process water or used water Cheaper
30
Legend
Water Efficient Irrigation Systems -Drip irrigation uses 30% to 50% less water than sprinkler irrigation - Drip irrigation applies water slowly and directly to the roots of plants. Hence, evaporation and runoff is minimized - Adopt flexible irrigation schedule to save water by adjusting to changing weather conditions - Recycled water should be used - Potable water is only permitted for system to be turned on manually and turned off automatically
33
Rainwater Collection
non-potable usage (irrigation, washing, toilet flushing, etc)
16 Mar 2004
34
Thank You
35
Urinals
recommended flush volume for standard size urinal (300mm width) is 0.5 litres per flush Waterless Urinals : Eliminate the use of water in flushing - save water Low installation cost as water connection and flush valve are not needed Proper maintenance is crucial to ensure the waterless urinal do not cause unpleasant smells.
36
Shower Taps & Low Flow Showerheads The flow rate should not exceed 7 litre/min Install Low Flow Showerheads with less than 5 litre/min
< 5 L/min
37
Washbasin Taps
Before insallation of thimble or CFR After insallation of thimble (3.8 L/min)
6 l/min (Turbulence)
2 l/min (Laminar)
For
sensor taps with 2 litre/min flow rate, cut off supply when hand is removed from basin or preset timing of not more than 60 secs is reached,whichever is earlier.
38
39
40
Consumption (m3)
Months (2005)
41