Introduction
CPVC pipes have replaced steel pipes for sprinklers across world successfully rendering trouble free service since 1986 Use in horizontal grid sprinkler piping in residential floors Product is recommended by NFPA & approved by International codes Bureau of Indian Standards has published code IS 16088
Standard for CPVC pipe in fire extinguishing systems
Fire reaches 760C (1,400F) After approximately 1 minute, sprinkler head activates Pipe is in direct contact with fire plume at 370C - 480C (700F 900F) for a total of 10 minutes
Fire Test
System inspected - no damage other than charring on the outside surface Inside Pipe Properties remain unchanged
System then tested at 1,207 kPa (175 psi) (12 Bar) for 5 minutes
Temperature from 900C to 1200C test was run for 30 min. without leakage
stagnant water pressure for 30 min. followed by hydrostatic pressure test of 4.2 bar for 5 min.
TATA HOUSING DEVELOPMENT COMPANY LTD.
Advantages
Limitations
Not suitable for basement Cannot be used in risers Upto 3 maximum diameter Not LISTED for outdoor applications
8
TATA HOUSING DEVELOPMENT COMPANY LTD.
Costing
Drawings to be forwarded for cost benefit analysis Material cost savings generate 5 % on material costs when compared with MS or GI
9
TATA HOUSING DEVELOPMENT COMPANY LTD.
Way Forward
Acceptance by various CFOs but cannot provide blanket approval Developer has to propose upon which it will be studied by CFO Ideal for projects where sprinklers are required in high rise Residential floors Brand name is Blazemaster marketed in India by M/s Astral
10
TATA HOUSING DEVELOPMENT COMPANY LTD.