Sie sind auf Seite 1von 37

PRELIMINARY

Introduction of TOSHIBA New Products

Mini-SMMS

Introduction
Line up: Outdoor : 4, 5, 6HP

Indoor : same as SMMS*

The new MiNi-SMMS: best performances for commercial and more private spaces. The great VRF traditional flexibility, reliability and energy savings can fit any room demanding application. Precise efficiency and control required by smaller offices, shops and quiet space applications are now available.

Design Keywords

Superior COP (4.61/ 4HP) & high reliability


achieved by TOSHIBAs unrivalled SMMS Technology Compact & Light weight outdoor unit Quiet operation can be further enhanced with PMV kit in indoor space Quiet sound design of outdoor unit Wide range of indoor unit line-up (81 variation) Various optional control gives great benefit and solution

Product Category
HP 2 3 4 5 6 8 10 48

Inverter Multi Mini-SMMS Super-MMS

2 to 4 indoor Max. 6 to 9 indoor

Residential

Light Commercial

Outdoor unit line-up


4HP
Model Name MCYCooling capacity (kW) Heating capacity (kW) Connectable indoor unit

Outdoor 5HP
MAP-0501HT
14.0 16.0 8

6HP
MAP-0601HT
15.5 18.0 9

MAP1401HT
12.1 12.5 6

Outdoor Diversity : 80% to 130%

Compact & Light Weight


The extreme compactness and lightweight allows easy transportation and installation on balcony or faades with a:
70% volume reduction*

60% footprint reduction

Height 1,340mm

Weight 117kg

Width 900mm

Depth 320mm

* over the standard SMMS condensing unit 5HP.

Outdoor unit : Foot print


Summary
0.359m2 0.288m 0.288m 0.314m
2

0.320m2

TOSHIBA

No.1

DAIKIN

No.1

Melco

No.3

SANYO

No.4

MITSUBISHI HVY

No.5

Reliability
DC Twin Rotary Compressor
New design DC Twin Rotary compressor delivers stable performances with minimum friction: ideal for noise-sensitive applications. The outdoor unit is almost imperceptible.
TWIN ROTARY COMPRESSOR

Low vibrations Super quiet operations High reliability

Toshiba Twin Rotary

Traditional Compressor

Wave generated by vector IPDU inverter

Latest Inverter technology with the Intelligent Power Drive Unit (IPDU): more and smaller steps for more accurate control.
It ensures optimised repetition of the sinusoidal supply current waves at the desired frequency.

Vector Inverter technology

COP comparison
TOSHIBA DAIKIN (VRV -S) DAIKIN (Super Multi PLUS) MITSUBISHI ELE. H.P. Cooling Heating Average Cooling Heating Average Cooling Heating Average Cooling Heating Average Cooling Heating Average Cooling Heating Average Cooling Heating Average 4 4.29 4.61 4.45 3.33 3.50 3.42 3.10 3.21 3.16 4.06 4.34 4.20 5 4.03 4.00 4.02 3.04 3.87 3.46 2.90 3.00 2.95 3.52 3.91 3.72 3.66 4.10 3.88 3.74 3.95 3.85 6 3.35 3.71 3.53 3.05 3.73 3.39 2.85 3.35 3.10 3.39 3.84 3.62 3.20 3.40 3.30

SANYO

MITSUBISHI HVY

Fujitsu General

4HP/5HP No.1 COP!!!!


5.00 4.50 4.00
COP

Average COP Average

COP

3.50 3.00 2.50 2.00


SH IB A V2 -S ) YO PL US ) Me lco Y HV IS HI u Fu jits Ge ne r SA N al

IK IN (V R

TO

ult i

MI TS UB

DA

IK IN (S up er M

4HP 5HP 6HP

DA

Company

Difference of With & Without PMV kit


Without PMV-Kit

SW setting
PMV-Kit

With PMV-Kit

Only for quiet space

Indoor unit line-up

Common with S-MMS indoor units

13 type x 10 capacity = 81 variations

New Compact 4way cassette (60X60) is connectable !

Indoor unit with PMV kit


PMV kit

PMV kit can be used for 6 type of indoor units.

Cassette Type

High Wall Type

Duct Type

PMV PMV

PMV

PMV
PMV

PMV

Floor Type

Line up of indoor unit


O Line-up, New model *Available for PMV_Kit (Quieter place)

1 2 3 4 5 6 7 8

(HP) (kW) 4Way-cassette(600*600) 4Way-cassette 2Way-cassette 1Way-cassette Concealed Duct standard Slim Duct Ducted Hi Static Celling

0.8 2.2 * * *

1.0 2.8 * * *

1.3 3.6 * * *

1.7 4.5 * * * * *

9 Hi Wall (1 series) 10 Hi Wall (2 series) 11 Floor Cabinet 12 Floor Concealed 13 Floor Standing

* * * * * * * * *

2.0 2.5 5.6 7.1 * * * * * * * *

3.0 8.0

3.2 9.0

4.0 5.0 11.2 14.0

PMV Kit
- Easy installation (Compact design)

- Quieter operation - Drain treatment free


Body size

161H X 226W X 58D

(Mitsubishi / Daikin)

Daikin

Mitsubi shi

Selection &Installation of PMV Kit


Indoor unit capacity type RBM-PMV0361E RBM-PMV0901E
007, 009, 012 type 015, 018 type

Pipe diameter
6.4mm 6.4mm

024 type
Length between PMV kit and indoor unit

9.5mm

2m to 10m

Connection cable : 10m (Accessory)

Branching joints and headers


Model Name Y-shape Branching joint 4-branching header RBM-BY53E RBM-BY103E RBM-HY1043E RBM-HY1083E Usage Below 6.4HP 6.4HP or more Below 7.8HP 7.8HP or more Appearance

8-branching header

Common with SMMS branch kit

Flexible joint combination


Y Branch after header branch
(Toshiba unique technology)

Header Branch after Y joint

Header after Header branch


(Toshiba unique technology)

:PMV unit

Allowable Piping Design


Without PMV kit
Furthest equivalent length (L1+L2+c)
L1 a L2 H1 H2 c b

125m
65m

Max. main pipe equivalent length (L1) Total extension (real length) (L1+L2+a+b+c) Upper outdoor unit

Top 180m
30m 20m 15m

Height difference (H1)


Lower outdoor unit Height difference (H2) Indoor - Indoor

Furthest length from 1st branching (L2+c) Max. length of indoor connecting pipe ( c )

35m
15m

Allowable Piping Design


With PMV kit
L1 a d L2 H1 H2 c f b e

Furthest equivalent length (L1+L2+c+f) Max. main pipe equivalent length (L1) Total extension (real length)
(L1+L2+a+b+c+d+e+f)

80m 50m 150m 30m 20m 15m 15m 15m 2 to 10m

Upper outdoor unit Height difference (H1) Lower outdoor unit Height difference (H2) Indoor (PMV) Indoor
(PMV)

Furthest length from 1st branching (L2+c) Max. length of indoor connecting pipe (c+f)
PMV Kit

Max. length between PMV kit and indoor (e/d/f)

Operating temperature range


Mini-SMMS
50 40 30 20 10 0 -10 -20
-5 C DB Heating 15.5C WB Cooling 43 C DB

-15 C WB

Outdoor : Sound level

H.P. TOSHIBA DAIKIN (VRV -S) DAIKIN (Super Multi PLUS) MITSUBISHI ELE. SANYO MITSUBISHI HVY Fujitsu General

4 49/50 51/52 51/53 51/52 -

5 50/52 52/53 52/54 50(47)/52 52/53 53 -

Cooling/Heating

6 51/53 53/54 54/56 53/54 56 (dB)

Technologies is nothing without control


All units connections are based on TCC Link control scheme. This protocol for interfacing with the full control range is a standard as like as the SMMS controllers: SMMS control solutions available Automatic network addressing TCC-Link connections with non-polarised wiring

Wired remote controller Simple remote controller

Wireless remote controller kit

Central remote controller

Weekly timer ON/OFF controller

Outdoor Option control : Sound reduction


4HP 5HP 6HP

Normal

(dB)

49/50
46/48

50/52
46/48

51/53
47/49

Sound reduction mode (dB)


For Quieter place
Night operation

55.5 X 60 mm

TCB-PCMO2E
Optional PCB for outdoor unit

Snow mode / Mode selection / External master ON/OFF control are also available by TCB-PCMO2E, (option P.C.Board)

Outdoor Option control : Error output


TCB-PCIN2E
Optional PCB for outdoor unit

79 X 73 mm - Error output - Operation signal output

Demand control
TCB-PCDM2E
Optional PCB for outdoor unit

- Standard (2 steps) - Expansion (4 steps) 71 X 85 mm

Central control with VRF (SMMS/SHRM)

Central controller TCB-SC642TLE2 Max 64 indoors

TCC-LINK main BUS

ON OFF controller TCB-CC163TLE2 Max 16 indoors

With Toshiba everything is easer.

Piping Design Program.


Put together a complete system by simply clicking on the icons. Pipe connection and sizing Specific details of selected units Export function (PDF; AutoCAD) Multiple system management Automatic regeneration Indoor unit fan speed indication

Diagnostic software.
For commissioning and service engineers. Diagram of refrigerant circuit Evualuation of indoor/outdoor units Operating parameters downloading Detailed informations for intant analysis.

Appendix

Control Option Line-up (1)


Local control Central control Add-On control

No.
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15

Name
Main wired remote controller
Simple wired remote controller Weekly timer Wireless remote controller kit Wireless remote controller kit Wireless remote controller kit Central remote controller ON/OFF controller Remote sensor Network adaptor 1:1 model connection interface Remote location ON/OFF control box External master ON/OFF control board Power peak-cut control board Error output control board

Model name
RBC-AMT31E
RBC-AS21E2 RBC-EXW21E2 TCB-AX21U(W)-E2 RBC-AX22CE2 TCB-AX21E2 TCB-SC642TLE2 TCB-CC163TLE2 TCB-TC21LE2 TCB-PCNT20E TCB-PCNT30TLE2 TCB-IFCB-4E2 TCB-PCMO2E TCB-PCDM2E RCB-PCIN2E

Remarks
Previous :AMT21E

For 4-way For ceiling, 1way-SH For others Max. 64 indoor unit Max. 16 indoor unit

Optional PCB for indoor unit For indoor unit Optional PCB for outdoor unit

Control Option Line-up (2)


Stand-alone network control Open network control

No. 1 2 3 4

Name Touch screen controller Touch screen controller Touch screen controller Touch screen controller

Model name BMS-TP0640ACE BMS-TP5120ACE BMS-TP640PWE BMS-TP5120PWE

Remarks
Max. 64 units Max. 512 units
Max. 64 units with energy monitoring Max. 512 units with energy monitoring

5
6

TCS-Net relay interface


Intelligent server

BMS-IFLSV1E
BMS-LSV2E

7
8 9 10 11

Intelligent server software


Energy monitoring relay interface Digital I/O relay interface
LON interface BACnet gateway

BMS-STCC01E
BMS-IFWH3E BMS-IFDD01E
TCB-IFLN640TLE BMS-****
Max. 64 units per I/F Max. 128 units

Panel Option Line-up


Indoor Unit Type Compact 4-way Cassette Type (600X600) 4-way Cassette Type Model Name RBC-UM11PG(W)E RBC-U21PG(W)-E2 RBC-UW136PG (AP0071- 0121)

2-Way Cassette Type

RBC-UW266PG (AP0151- 0301)


RBC-UW466PG (AP0361-0561) SH 1seires : RBC-US165PG (AP0151-0181)

1-Way Cassette Type

SH 1 series : RBC-US265PG (AP0241) YH 1 series : RBC-UY135PG (AP0071-0121) SH 2 series : RBC-US21PGE (AP0152-0242)

1-way cassette (MMU-AP0122SH/0182SH/0242SH) Optional parts Front air discharge unit (TCB-BU21HWE)

Indoor unit option Line-up (1)


4-Way Air Discharge Cassette (MMU-AP***1H)
Name
Super Long Life Filter
High Efficiency Filter 65 High Efficiency Filter 90 Fresh Air and Filter Chamber Fresh Air Inlet Box Auxiliary Fresh Air Flange Spacer for Height Adjustment

Model Name
TCB-LF1601UE
TCB-UFM1601UE TCB-UFH1601UE TCB-GFC1601UE2 TCB-GB1601UE2 TCB-FF101URE2 TCB-SP1601UE

Remarks
Be used with TCB-GFC1601UE

Be used with TCB-GFC1601UE Can be used to slim duct

Air Discharge Direction Kit

TCB-BC1601UE

Indoor unit option Line-up (2)


Compact 4-Way Cassette (MMU-AP***1MH)
Name Model Name Remarks

Spacer for Height Adjustment


Fresh Air Chamber Fresh Air Inlet Box Air Discharge Direction Kit

(TBD)
(TBD) (TBD) (TBD)

Under Ceiling (MMC-AP***1H)


Name Model Name Remarks
Necessary accessories when Using drain pump kit

Drain Pump Kit


Elbow Piping Kit

TCB-DP22CE
TCB-KP12CE (AP0151- 0181) TCB-KP22CE (AP0241- 0481)

Indoor unit option Line-up (3)


Concealed Duct Standard type (MMD-AP***1BH)
Name Model Name
TCB-UFM11BFCE (AP0071-0121/AP0241-0301) TCB-UFM21BFCE (AP0151-0181/AP0361-0561)

Remarks
AP0241-0301 use 2 pcs. AP0361-0561 use 2 pcs.

High Efficiency Filter 65

TCB-UFM11BE (AP0071-0121) TCB-UFM21BE (AP0151-0181)


For underside

TCB-UFM31BE (AP0241-0301)
TCB-UFM41BE (AP0361-0561) TCB-UFH51BFCE (AP0071-0121/AP0241-0301) TCB-UFH61BFCE (AP0151-0181/AP0361-0561)

suction

AP0241-0301 use 2 pcs. AP0361-0561 use 2 pcs. For underside suction

High Efficiency Filter 90

TCB-UFH51BE TCB-UFH61BE TCB-UFH71BE TCB-UFH81PE

(AP0071-0121) (AP0151-0181) (AP0241-0301) (AP0361-0561) (AP0071-0121) (AP0151-0181) (AP0241-0301)

RBC-UD281PE(W)

Ceiling Panel

RBC-UD501PE(W) RBC-UD801PE(W)

Half panel for underside suction

RBC-UD1401PE(W) (AP0361-0561)

Indoor unit option Line-up (4)


Concealed Duct Standard type (MMD-AP***1BH)
Name Suction Canvas Model Name TCB-CA281BE TCB-CA501BE (AP0071-0121) (AP0151-0181) For underside Remarks

TCB-CA801BE
TCB-FC281BE Filter Chamber TCB-FC501BE TCB-FC801BE TCB-FK281BE Filter Kit for Underside TCB-FK501BE

(AP0241-0301)
(AP0071-0121) (AP0151-0181) (AP0241-0301) (AP0071-0121) (AP0151-0181)

suction

TCB-CA1401BE (AP0361-0561) For rear suction

TCB-FC1401BE (AP0361-0561) For underside

TCB-FK801BE

(AP0241-0301)

suction

TCB-FK1401BE (AP0361-0561)

Indoor unit option Line-up (5)


High Static Duct (MMD-AP***1H)
Name High Efficiency Filter 65 High Efficiency Filter 90 Long Life Pre-Filter Filter Chamber Drain Pump Kit Model Name Remarks
AP0481 use 2 pcs.
Use 2 pcs. AP0481 use 2 pcs. Use 2 pcs. AP0481 use 2 pcs. Use 2 pcs.

TCB-UFM1D-1E (AP0181/0481)
TCB-UFM2D-1E (AP0241-0361) TCB-UFH5D-1E (AP0181/0481) TCB-UFH6D-1E (AP0241-0361) TCB-PF1D-1E (AP0181/0481) TCB-PF2D-1E (AP0241-0361) TCB-FCY21DE (AP0961) TCB-FCY31DE (AP0241-0361)

TCB-FCY51DE (AP0481)
TCB-DP31DE (AP0181-0481)

Das könnte Ihnen auch gefallen