Part - V
Miscellaneous points
Modification of Ah (6.4.2, IS:1893(Part 1)-2002) : For T0.1, Ah (Z/2), whatever be the value of (I/R)
(6.4.2 , IS:1893(Part 1)-Proposed Draft)
Load Combinations:
The analysis results are to be combined using the following load combinations for RC structures (6.3.1.2, IS:1893(Part 1)-2002, Table 18, IS:4562000) :
COMB-I = 1.5(DL+LL)# COMB-II = 1.2(DL+LLEL)# COMB-III = 1.5(DLEL) COMB-IV = 0.9DL1.5EL* Where EL represents ELx and Ely
#Live
load reduction for upper floors as per 3.2, IS:875(Part 2)1987 not to be included (Note 6, 8.1, IS:875(Part 5)-1987) *To be considered when stability against overturning or stress reversal is critical (foot note to Table 18, IS:456-2000)
Seismic Analysis of Multi-storied RC Building Presented by Rahul Leslie
with the earth quake loads Further reduction in imposed load as per 3.2, IS:875 (Part 2)-1987 need not be considered (7.3.3, IS:1893 (Part 1)-2002, similar to Note 6, 8.1, IS:875(Part 5)1987).
COMB-I = 1.5[DL+(0.25 LL3, 0.5 LL >3)] ?? COMB-II = 1.2[DL+(0.25 LL3, 0.5 LL >3)EL] COMB-III = 1.5(DLEL) COMB-IV = 0.9DL1.5EL
Presented by Rahul Leslie
with the earth quake loads Further reduction in imposed load as per 3.2, IS:875 (Part 2)-1987 can be considered (Comment to the draft code).
COMB-I = 1.5[DL+LL] COMB-II = 1.2[DL+LLEL] COMB-III = 1.5(DLEL) COMB-IV = 0.9DL1.5EL
Presented by Rahul Leslie
For checking uplift of supports: COMB10 = 0.9 DL + 1.5 ELx COMB11 = 0.9 DL 1.5 ELx COMB13 = 0.9 DL + 1.5 ELy COMB14 = 0.9 DL 1.5 ELy
Accidental eccentricity:
Minimum Design eccentricity edi to be considered during analysis (7.9.2, IS:1893(Part 1)-2002)
Accidental eccentricity:
Accidental eccentricity:
Minimum Design eccentricity edi to be considered during analysis (7.9.2, IS:1893(Part 1)-2002)
In case 3D dynamic analysis is carried, the 1.5 in the formula be replaced with 1.0 (6.3.5.2 & Table 1, IS:1893(Part 1)Proposed Draft)
Pile/Well
25% 50% 0%
Raft Isolated
When to include ductile detailing :Ductile detailing provisions shall be adopted in RCC buildings for
More than 5 stories high in zone III Industrial structure in zone III Importance factor > 1.0 in zone III In zone IV & V (1.1.1, IS:13920-1993)
When to include ductile detailing :Ductile detailing provisions shall be adopted in RCC buildings for
All buildingd in zone III, IV & V (1.1.1, IS:13920-1993, Edition 1.2) However: Moment resisting frame structures located in seismic zone III are permitted to comply with only section 10 of the code, (i.e., as Intermediate Moment Resisting Frame) Moment resisting frame structures located in seismic zones IV and V shall comply with sections 5 to 8 of the code, (i.e., as Special Moment Resisting Frames) (1.1.1, IS:13920-Proposed Draft)
Seismic Analysis of Multi-storied RC Building Presented by Rahul Leslie