Refrigeration Cycles

/



The vapor compression refrigeration
cycle is a common method for
transferring heat from a low
temperature to a high temperature.

2
3
The above figure shows the objectives of refrigerators
and heat pumps. The purpose of a refrigerator is the
removal of heat, called the cooling load, from a low-
temperature medium. The purpose of a heat pump is
the transfer of heat to a high-temperature medium,
called the heating load. When we are interested in the
heat energy removed from a low-temperature space,
the device is called a refrigerator. When we are
interested in the heat energy supplied to the high-
temperature space, the device is called a heat pump.
In general, the term heat pump is used to describe the
cycle as heat energy is removed from the low-
temperature space and rejected to the high-
temperature space.
4
The performance of refrigerators and heat pumps is
expressed in terms of coefficient of performance
(COP), defined as
COP
Q
W
COP
Q
W
R
L
net in
HP
H
net in
= = =
= = =
Desired output
Required input
Cooling effect
Work input
Desired output
Required input
Heating effect
Work input
,
,
Both COP
R
and COP
HP
can be larger than 1. Under the
same operating conditions, the COPs are related by
COP COP
HP R
= +1
5
Can you show this to be true?

Refrigerators, air conditioners, and heat pumps are rated
with a SEER number or seasonal adjusted energy
efficiency ratio. The SEER is defined as the Btu/hr of
heat transferred per watt of work energy input. The Btu
is the British thermal unit and is equivalent to 778 ft-lbf of
work (1 W = 3.4122 Btu/hr). An SEER of 10 yields a
COP of 2.9.
SEER = COP * 3.4122
Refrigeration systems are also rated in terms of tons of
refrigeration. One ton of refrigeration is equivalent to
12,000 Btu/hr or 211 kJ/min. How did the term ton of
cooling originate?
1 TR = 12000 Btu/hr = 3.517 kW
6
Reversed Carnot Refrigerator and Heat Pump

Shown below are the cyclic refrigeration device
operating between two constant temperature
reservoirs and the T-s diagram for the working
fluid when the reversed Carnot cycle is used.
Recall that in the Carnot cycle heat transfers
take place at constant temperature. If our
interest is the cooling load, the cycle is called
the Carnot refrigerator. If our interest is the
heat load, the cycle is called the Carnot heat
pump.
7
8
The standard of comparison for refrigeration
cycles is the reversed Carnot cycle. A
refrigerator or heat pump that operates on the
reversed Carnot cycle is called a Carnot
refrigerator or a Carnot heat pump, and their
COPs are
COP
T T
T
T T
COP
T T
T
T T
R Carnot
H L
L
H L
HP Carnot
L H
H
H L
,
,
/
/
=

1
1
1
1
9
Notice that a turbine is used for the expansion process
between the high and low-temperatures. While the
work interactions for the cycle are not indicated on the
figure, the work produced by the turbine helps supply
some of the work required by the compressor from
external sources.

Why not use the reversed Carnot refrigeration cycle?
Easier to compress vapor only and not liquid-vapor
mixture.
Cheaper to have irreversible expansion through an
expansion valve.

What problems result from using the turbine instead of
the expansion valve?
10
The Vapor-Compression Refrigeration Cycle

The vapor-compression refrigeration cycle has
four components: evaporator, compressor,
condenser, and expansion (or throttle) valve.
The most widely used refrigeration cycle is the
vapor-compression refrigeration cycle. In an
ideal vapor-compression refrigeration cycle, the
refrigerant enters the compressor as a
saturated vapor and is cooled to the saturated
liquid state in the condenser. It is then throttled
to the evaporator pressure and vaporizes as it
absorbs heat from the refrigerated space.

11
The Vapor-Compression Refrigeration Cycle


The ideal vapor-compression cycle consists of four
processes.

Ideal Vapor-Compression Refrigeration Cycle
Process Description
1-2 Isentropic compression
2-3 Constant pressure heat rejection in the
condenser
3-4 Throttling in an expansion valve
4-1 Constant pressure heat addition in the
evaporator
12
The following diagrams, show the flow and T-s
diagram illustrates the refrigeration cycle.
13
The P-h diagram is another convenient diagram
often used to illustrate the refrigeration cycle.
14
The ordinary household refrigerator is a good example
of the application of this cycle.
15
COP
Q
W
h h
h h
COP
Q
W
h h
h h
R
L
net in
HP
H
net in
= =

= =

,
,
1 4
2 1
2 3
2 1
Thermodynamic analysis of ideal vapor-compression
cycle SSVCC simple saturation vapor
compression refrigeration cycle
16
Relative efficiency
Refrigerator relative efficiency is defined as the
ratio between the actual refrigeration cycle
coefficient of performance and that for Carnot
cycle at same heat source and heat sink
temperatures.
q
R
=
17
Definitions
Refrigeration capacity: is the amount of heat transfer to the
evaporator in kW; for steady operations the refrigeration
capacity equal to the refrigeration load
Refrigeration effect: the amount of heat transfer to the
evaporator per one kg of refrigerant mass flow rate through it "
kJ/kg"
Condenser duty: is the amount of heat transfer from
condenser to surroundings in kW
Compressor indicated power: is power added to the
refrigerant during compression process ;kW
Compressor brake power: the power required to brake the
compressor kW; compressor brake power greater than the
compressor indicate power" defined the compressor
mechanical efficiency"
18
Example 1

Refrigerant-134a is the working fluid in an
ideal compression refrigeration cycle. The
refrigerant leaves the evaporator at -20
o
C
and has a condenser pressure of 0.9 MPa.
The mass flow rate is 3 kg/min. Find
COP
R
and COP
R, Carnot
for the same T
max

and T
min
, and the refrigeration capacity in
tons of refrigeration.
Using the Refrigerant-134a Tables, we
have
19
1
2
2 2
1
1
2
2 1
1
3
3
2
1
238.41
278.23
900
20
0.9456
43.79
0.9456
1.0
3
900
0
s
s
o
o
s
s
State
State
kJ
kJ h
Compressor exit
h
Compressor inlet
kg
kg
P P kPa
kJ
T C
s
T C
kJ
kg K s s
x
kg K
State
Condenser exit
P kPa
x


=

= =
` `
=

=
=


= =
=

)


)
=
=
3
4
4
4 1
3
4 3
4
101.61
0.358
0.4053
20
0.3738
.0
o
State
kJ
h
x
Throttle exit
kg
kJ
s
kJ T T C
s
kg K
kg K
h h

=
=


` `
=
= =

=

)
)
20
1 4 1 4
, 2 1 2 1
( )
( )
(238.41 101.61)
(278.23 238.41)
3.44
L
R
net in
Q m h h h h
COP
W m h h h h
kJ
kg
kJ
kg

= = =

=
The tons of refrigeration, often called the cooling load or refrigeration effect, are
1 4
( )
1
3 (238.41 101.61)
min
211
min
1.94
L
Q m h h
kg kJ Ton
kJ
kg
Ton
=
=
=
,
( 20 273)
(43.79 ( 20))
3.97
L
R Carnot
H L
T
COP
T T
K
K
=

+
=

=
21
Another measure of the effectiveness of the
refrigeration cycle is how much input power to
the compressor, in horsepower, is required for
each ton of cooling.
The unit conversion is 4.715 hp per ton of
cooling.
Find the system SEER?
,
4.715
4.715
3.44
1.37
net in
L R
W
Q COP
hp
Ton
hp
Ton
=
=
=
22
ACTUAL VAPOR-COMPRESSION REFRIGERATION CYCLE
An actual vapor-compression
refrigeration cycle differs from the ideal
one in several ways, owing mostly to the
irreversibilities that occur in various
components, mainly due to fluid friction
(causes pressure drops) and
heat transfer to or from the
surroundings.
The COP decreases as a result of
irreversibilities.
23
Schematic and T-s diagram for the actual
vapor-compression refrigeration cycle.
ACTUAL VAPOR-COMPRESSION REFRIGERATION CYCLE
24
DIFFERENCE:
The difference between actual and simple
refrigeration cycles are:
1- Non-isentropic compression
2- Superheated vapor at evaporator exit
3- Sub-cooled liquid at condenser exit
4- Pressure drops in condenser and evaporator
5- pressure drop in suction and discharge valves.
6- refrigerant heating during suction stroke.

ACTUAL VAPOR-COMPRESSION REFRIGERATION CYCLE
25
ACTUAL VAPOR-COMPRESSION REFRIGERATION CYCLE
Compressor isentropic efficiency
Polytrophic power
Pressure drop in suction and discharge valves
Refrigerant heating during suction process.
Actual volumetric efficiency


Reciprocating compressors
28
Single acting








Clearance volumetric efficiency=

Apparent clearance volumetric
efficiency
30
Clearance ratio C = clearance volume/
swept volume
Clearance volume = volume above the top
dead center = Vc
Swept volume = volume of the cylinder
between top and bottom dead centers =
volume above the bottom dead center -
volume above the top dead center

P
Pd


PS

VC V1 V2


31
Actual volume = volume above bottom dead
center volume of residual gages after
expansion from discharge to suction
pressure = V
2
V
1

Theoretical volume = swept volume =
volume above bottom dead center - volume
above top dead center = V
2
- V
c

Clearance ratio C = clearance volume /
swept volume = V
c
/ (V
2
V
1
)


32

Volumetric efficiency =


33


34
Compressor power
Compressors are classified into the following
categories from Th.D. point of view
1- isentropic compressors Adiabatic + reversible
Q =0 and no internal and external
irreversibleness
S = constant IW isent = m ref Ah isent
2- Adiabatic compressors, Q= 0 and AS 0
IW adiab = m ref Ah act.
Compressor efficiency = compressor isentropic
efficiency = IW isent / IW adiab = Ah isent / Ah act

Compressor power
3- poly-tropic compressors
During the compression process the
refrigerant follows the relation
Pv
n
= constant = C

Since the indicated work is given as


36
Compressor power


Since,
37
Heat transfer to poly-tropic
compressor
Find the rate of heat transfer to the poly-
tropic compressor?

38
39
Heat Pump Systems