Beruflich Dokumente
Kultur Dokumente
Airflow
System
Performance
Airflow measurement
An accurate airflow measurement must be performed before the system can be properly charged with refrigerant or before any attempt is made to measure performance.
Airflow measurement
BTUH (OUTPUT) CFM = TEMP DIFFERENCE X 1.08
Measurement Methods
power measurement - watt-hour meter electric resistance heat and heat pumps power measurement - volt-ampere electric resistance heat clocking a gas meter natural gas furnaces calculating input by orifice capicity propane gas furnaces total static pressure
WATT-HOUR METER
Power input measurements, by the watthour meter require power interruption to all appliances in the structure except the indoor fan motor and electric heaters.
Do not turn off power to: Life support devises Appliances subject to damage from power interruption
WATT-HOUR METER
Set the thermostat to heat or emergency heat and adjust the setpoint to 90 degrees. Locate the watt-hour meter serving the structure. Clock the black mark on the meter disc for 20 revolutions using a stop watch or the second hand on your wrist watch.
Seconds
518.4 = 7.97 kw
65
65
Airflow measurement
BTUH (OUTPUT)
CFM = TEMP DIFFERENCE X 1.08 EXAMPLE: 27,202 BTUH (output) 27 degrees delta T
Airflow measurement
Measurement Methods
set the thermostat to the heat or emergency heat mode, in the case of a heat pump, so that only the resistance heaters and the fan motor are activiated. measure the applied voltage to the resistance heaters while they are operating. measure the current draw for each circuit if more than one and add them together. measure the temperature difference entering and leaving the air handler.
multiply the applied volts times the total current draw (amperes)
Measurement Methods
60 SECONDS
120 CFH
Measurement Methods
determine the burners orifice size. count the number of orifices in the furnace. set the gas valves outlet manifold pressure to 11 inches of water column. set the thermostat to heat mode and 90 degrees. measure the temperature difference entering and leaving the furnace.
determine the btu per hour input for the selected orifice size using table f-2 in apendix f of the national fuel gas code. multiply the btu per hour input times the number of orifices counted in the furnace. multiply the btu per hour input times the furnace effeciency (minimum 80%).
table F-2
Measurement Methods
total
STATIC PRESSURE
Definition:
The pressure measured above or below atmospheric pressure created by the blower independant of air velocity. It is exerted in all direction to the inside walls of the ductwork and is measured at a 90 degree angle to the airflow.
Measure return static pressure close to air messure return static pressure as close to handler or furnace cabinet. air handler or furnace cabinet as possible
Measure supply static pressure downstream of all pressure drops. Average readings where turbulant airrflow is present
PRODUCT DATA
TWEO48C140B - BAY96X1415
PUB # 22-1298-03 PAGE # 8 EXAMPLE:
Measured external static pressure = .5 In. W.C. Blower set on high speed tap
Measured external static pressure = .5 In. W.C. Pressure drop accross heater = .13 In. W.C. Final static pressure = .63
TUD100C948H - TXC049C4HPB
EXAMPLE:
Measured external static pressure = .30 In. W.C. Blower set on black - high speed tap
Pressure drop accross coil = .30 In. W.C. Final total external static pressure = .60 In.
W.C.
EXAMPLE: