TOPICS COVERED
Intro

NED University Engineering & Technology Department of Civil Engineering

FLEXURAL MEMBERS OF SMRF


General
Clear span not less than 4 times effective depth Width/depth ratio not less than 0.3 Width not less than 10 in Width not more than width of supporting member plus distance on each side of supporting member equal to of the depth of flexural member

Cont.

NED University Engineering & Technology Department of Civil Engineering

FLEXURAL MEMBERS OF SMRF


Longitudinal Reinforcement
Reinforcement ratio not less than 200/fy Reinforcement ratio not more than 0.025 Two bars should be continuous in top and bottom +ve moment strength at joint face should not be less than of ve moment strength +ve or ve moment strength at any section should not be less than of strength at joint face Lap allowed only with hoop or spiral reinforcement Lap splices are not allowed within joints a distance of 2d from joint face

NED University Engineering & Technology Department of Civil Engineering

FLEXURAL MEMBERS OF SMRF


Longitudinal Reinforcement

NED University Engineering & Technology Department of Civil Engineering

FLEXURAL MEMBERS OF SMRF


Transverse Reinforcement
Maximum hoop spacing shall not exceed d/4 8 times dia of smallest longitudinal bar 24 times dia of hoop bar 12 in Examples of hoops are

Cont.

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF


General
Shortest cross-sectional dimension is 12 in. Ratio of shortest dimension to perpendicular dimension shall not be less than 0.4

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF


Reinforcement
Longitudinal reinforcement ratio not less than 0.01 and not more than 0.06 Concrete cover for transverse reinforcement shall not exceed 4 in. Spacing of rings (s) shall not exceed s= of minimum column dimension s=6 times dia of longitudinal bar s=4+[(14-hx)/3] 4< s <6 Length of column (L) for above ring spacing shall not be less than depth of column 1/6 of clear span 18 in.

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF


Reinforcement
Spacing (S1) for the rest of column length is smaller of 6 times longitudinal bar dia 6 in. Example of rings is

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF

NED University Engineering & Technology Department of Civil Engineering

COLUMNS FOR SMRF


Joints
Beam longitudinal reinforcement must be extended to the far face of column and anchored Column dimension parallel to the beam reinforcement not be less than 20 times bar dia Transverse reinforcement shall be provided in joint

NED University Engineering & Technology Department of Civil Engineering

INTERMEDIATE MOMENT RESISTING FRAME


Beams
+ve moment strength at joint face should not be less than 1/3 of ve moment strength +ve or ve moment strength at any section should not be less than 1/5 of strength at joint face First hoop provided at 2 in. from face of support Maximum hoop spacing shall not exceed d/4 8 times dia of smallest longitudinal bar 24 times dia of hoop bar 12 in

NED University Engineering & Technology Department of Civil Engineering

INTERMEDIATE MOMENT RESISTING FRAME


Columns
Hoops provided at spacing (s) over length (L) from both ends s should be smallest of 8 times dia of smallest longitudinal bar 24 times dia of hoop bar of smallest dimension of frame member 12 in L should be largest of 1/6 of clear span of column Minimum dimension of column 18 in

NED University Engineering & Technology Department of Civil Engineering

INTERMEDIATE MOMENT RESISTING FRAME


Columns
Hoops provided at spacing (s) over length (L) from both ends s should be smallest of 8 times dia of smallest longitudinal bar 24 times dia of hoop bar of smallest dimension of frame member 12 in L should be largest of 1/6 of clear span of column Minimum dimension of column 18 in