Beruflich Dokumente
Kultur Dokumente
Introduction.
Circuit Breakers (CBs) are the switching and current interrupting devices. The CBs are necessary at every switching point in the substation. A Circuit breaker differs from a disconnector switch mainly in three aspects: - Fault current interruption. - Arc extinction - Speed of operation
Basically a circuit breaker(CB) comprises of a set of fixed and movable contacts. Contacts can be operated by means of an operating mechanism. Separation of current carrying contacts produces the arc ,the arc is extinguished by suitable media such as dielectric oil,air,sf6 gas and vacuum. Arc is extinguished by lengthening, cooling, splitting or rotation. In some breakers arc is drawn in the direction of splitters by magnetic field.
Expected Functions
Must be capable of closing on to,and carrying full load currents for long periods of time Under prescribed conditions ,it must open automatically to disconnect the load or small overload Must successfully and rapidly interrupt heavy currents which flow when a short circuit has to be cleared from the system
Expected Functions(contd.)
Must be capable of closing on to a circuit in which a fault exists and of immediately reopening to clear the fault from the system Must be capable of carrying current of short circuit magnitude until,and for such time as,the fault is cleared by another breaker nearer to the time of fault
ELECTRICAL ENVIRONMENT
A circuit interrupting device operates in an electrical environment which imposes a unique set of criteria on the device. There are three major operating conditions: Closed, open and the transition from closed to open. In the closed position the device must conduct the continuous rated current without exceeding the temperature limits. While closed, the complete insulation system is stressed by system voltage and transient over voltage caused by lightning, switching and system changes. In open position, insulation across the open contacts is stressed in addition to the insulation to ground. If fault occurs, the CB is expected to interrupt the fault current within rated interrupting time to minimize any disturbances to the system. At some point during the opening operation the current is interrupted, resulting in an electrical separation of the system at the CB location. Immediately after current zero , the contacts are stressed by transient voltages produced by the system as it reacts to the new operating state. Additional requirements are- inductive and capacitive current switching by limiting over voltages within allowable limits. These wide variety of operating conditions impose conflicting constraints on the CB design.
o n b a s i s o f o p e r a t i n g m e c h a n i s m
o n b a s i s o f a r c q u e n c h i n g m e d i u m
o n b a s i s o f i n t e r r u p t o r l o c a t i o n
s p r i n g a s s i s t e d
p n e u m a t i c
h y d r a u l i c
a i r b r e a k c b
m i n i m u m o i lc b
a i r b l a s tc b
s f 6 c b
v a c u u m c b
l i v e t y p e
d e a d t y p e
SF6
High Di-electric strength. Chemical stability. High molecular weight. Absence of carbon. Gas can be compressed for high BDV requirements. Chemically inert. SF6 is a green house gas. Even though SF6 has a global warming potential some 25000 times greater than carbon dioxide, SF6 probably accounts for only about 0.1 percent of mankinds contribution to the greenhouse effect.
INTERRUPTOR
Interrupter houses the fixed, moving and arcing contacts and the linkage mechanism for operating moving contacts. There are different types of interruptors depending upon the type of nozzle design and arc extinction method :
Double blast Partial double blast Self blast Double motion type
OPENING OPERATION
CLOSING OPERATION
CLOSING-SECTION
OPENING-SECTION.
OPERATING MECHANISM
A. B. C. D.
Spring assisted motor mechanism Pneumatic operating mechanism Hydraulic mechanism Combination of above.
SF6 alarm and L/O Operating mechanism alarm / lock out Trip circuit supervision
CIRCUIT BREAKERS
Guaranteed SF6 leakage 1% per year. Separate SF6 monitoring for each poles for 145kV and above. Operating duty 0-0.3S CO 3 min. CO. S.C. rating 40KA (for 400kV & 220KV)
31.5 kA for 145KV - Line charging interruption Capability 600A for 420kV, 125A for 245kV(IEC), 50A for 145kV(IEC).
Op. Mechanism Pneumatic/Spring/Hydraulic. Aux. DC(220V) supply variation 70 -110% for trip of 85 110% for close. 2 Independent trip circuits, each having separate pressure switches.
CB OPERATION PHYLOSOPHY.
CB Shall be suitable for operation from Remote (control Room/Remote control centre) as well as from local MB depending on position of Local/Remote switch. The protection trip will be normally directly extended (bypassing local selection) Two trip coils and one close coils normally provided. No interlocks from other equipments like Isolator and Earthswitch for local trip. But CB local close normally allowed only if associated eartswitches are closed. For remote closing and required interlocks from other equipments like Isolator and Earthswitch are provided from CR panels. Autoreclose is done from CR panels only.
TYPE TESTS
LIST OF TYPE TESTS Insulation Tests : (a) Power Frequency withstand (IEC-62271-100, Clause-6.2) (b) Lightning Impulse withstand (IEC-62271-100, Clause-6.2) (c) Switching Impulse Withstand (IEC-62271-100, Clause-6.2) Short Time Current & peak current withstand: (IEC-62271-100, Clause-6.6) Temperature Rise Test (IEC-62271-100, Clause-6.5) Mechanical Operation Test (M1-2000 opns, M2- 10000 opns) (IEC-62271100, Clause-6.101.2. 1,2&3) Electrical Endurance (for 52 kV & below only) RIV/Corona extinction voltage tests (POWERGRID Spec. Section -GTR). Seismic withstand test (POWERGRID Spec. Section -GTR). Short Circuit tests/switching tests(IEC-62271-100, Clause-6.102 to 6.106) T-10, T-30,T-60,T-100a(IEC-TR62271-308),T100s,out of phase, critical current Short line fault tests - L-90, L-75(IEC-62271-100, Clause-6.109) Capacitive Current switching tests- C1/ C2.(capacitor/line charging/cable charging) (IEC-62271-100, Clause-6.111) Reactor switching test.(IEC 62271-110)
CONTROLLED SWITCHING
CONTROLLER IS AN ADD ON DEVICE TO IMPROVE CB PERFORMANCE. CONTROLLER IS USED TO OPEN (OR CLOSE) THE CB AT ITS MOST FAVOURABLE CONDITION CONTROLLER MONITORS THE SYSTEM PARAMETERS (LIKE VOLTAGE WAVEFORM) AND DECIDE OPTIMUM SWITCHING CONDITION AND HENCE KNOWN AS POINT ON THE WAVE SWITCHING.
CONTROLLED SWITCHING(CONTD)
USED FOR REACTOR/TRANSFORMER/ CAPACITOR/LINE SWITCHING TO CONTROL SWITCHING O/V OR INRUSH CURRENT WILL ALSO MONITOR CB OPERATION CHARACTERISTICS DURING PREVIOUS OPERATIONS AND ADAPT TO THE SPECIFIC OPERATING CONDITIONS(TEMPERATURE PRESSURE ETC.)
THANK YOU