Beruflich Dokumente
Kultur Dokumente
Purpose of Earthing
Protection of buildings and installations against lightning Safety of human and animal life by limiting touch and step voltages to safe values Fast clearing of faults Electromagnetic compatibility (EMC) i.e. Static electricity.
Grounding/Earthing
Earth grounding (System earthing)-Neutral grounding for safety of equipment Equipment grounding (Commonly called earthing/equipment earthing)-For safety of human.
GPR
The maximum electrical potential that a grounding grid may attain relative to a distant grounding point assumed to be at the potential of remote earth. This voltage, GPR, is equal to the maximum grid current times the grid resistance.
Remote Earth
A point on earth located at an effectively infinite distance from the location being analyzed. The remote earth potential is the reference voltage for ground potential rise and other voltages developed during fault conditions
Method of earthing
if b is small compared to a and c, and c>2a, the apparent soil resistivity value is:
Resistivity Vs Moisture
Effect of diameter
Diameter of the ground electrode Increasing the diameter of the ground electrode has very little effect in lowering the resistance. For example, you could double the diameter of a ground electrode and your resistance would only decrease by 10 %.
Multiple Electrodes
For additional electrodes to be effective, the spacing of additional rods need to be at least equal to the depth of the driven rod. Without proper spacing of the ground electrodes, their spheres of influence will intersect and the resistance will not be lowered.
Multiple Electrodes
Very often when two, three or four grounding electrodes are being used, they are driven in a straight line; when four or more are being used, a hollow square configuration is used and the grounding electrodes are still connected in parallel and are equally spaced In multiple electrode systems, the 62% method electrode spacing may no longer be applied directly. The distance of the auxiliary electrodes is now based on the maximum grid distance
2 3 4 8 12 16 20 24
62% Method
DEPTH DRIVEN
DISTNACE to P Probe
DISTANCE to C Probe
6 ft 8 ft 10 ft 12 ft 18 ft
45 ft 50 ft 55 ft 60 ft 71 ft
72 ft 80 ft 88 ft 96 ft 115 ft
20 ft 30 ft
74 ft 86 ft
120 ft 140 ft
For substations
Problem: Most critical location as step and touch potentials have to fall with in range.. Concentric shells are big so requires long lead for auxiliary electrodes for accurate measurement. Not possible through ordinary fall of technique.
References
Getting down to earth by Megger corporation. Understanding ground resistance testing by AEMC Instruments. Earthing technique by Lightning and surge technologies IS 3043 Earth ground resistance by Fluke corporation Earthing Myths and Facts by Jayanta Khan L&T Ltd. IR ACTM Paper-Ground testing in difficult installation by Mr. Jeffrey R. Jowett Grounding Consideration by Mr. Ruwan Weerasundara Member IEEE.
THE END