Beruflich Dokumente
Kultur Dokumente
Cool-Down Rates
Non-linear rate of cooling
Based on Thermal Model values
Accounts for extra convection
Hot motors cool more quickly at first
Cooling rate slows as it cools
True Time
Variable Cool Rate
Typical OL Relay
Cool Down Rate
ABB SSMt Training - 2007
SSM Setpoint Page 12
Benefits Dynamic Reset Capacity
Avoids Exhausting Starts/Hour Rating
Prevents having to wait longer for reset
Takes the guesswork away from the operator
Saves Operating Costs
Helps prevent motor damage
Decreases downtime
ABB SSMt Training - 2007
SSM Setpoint Page 13
Unit Factory Settings
Password for Setpoint Page 13 = 48562 (Not Documented).
Unit Maximum Current Use SF X FLA calculation to enable
correct settings in Setpoint Page 1.
Phase CT Primary Ratio Value of CTs located inside of red
box in SSM enclosure. Set from the factory.
Ground CT Primary Ratio Setting.
PT / VT Primary Ratio Setting.
ABB SSMt Training - 2007
SSM Setpoint Page 13 - Continued
Sync Bypass Close Sets triggering of bypass contactor - Firing
Angle and/or Current Drop Off.
Bypass Drop Out Delay Programmable delay for the opening of
bypass contactor after stopping.
Bypass Discrepancy Not used, Future Option.
Shunt Trip Not Used, Future Option.
Starter Settings Offset adjustment factors to correct current &
voltage limit output during starting. Not normally accessed.
Tachometer Input Offset Adjustment factors for compensation.
ABB SSMt Training - 2007
SSM Setpoint Page 13 - Continued
Analog Outputs 1 &2 Offset Programmable output control.
RTD Calibration Refer to procedure
Short Circuit Limit Adjustment and Delay.
Reset all relays No longer needed.
Factory Reset Refer to Factory Reset Procedure.
ABB SSMt Training - 2007
INTRODUCTION & OBJECTIVES OF SESSION A
SSM DESCRIPTION B
SSM FUNCTIONS - PROGRAMMING C
COMMISSIONING D
TROUBLESHOOTING & MAINTENANCE E
PROGRAMMING EXERCISE F
CONCLUSION G
ABB SSM Product Training
Startup, Operation & Service Session
ABB SSMt Training - 2007
SSM - Service Manual Documents
Tab 1 Theory of Operation How The SSM Works
Tab 2 SSM Manual Soft Starter Document
Tab 3 Electrical Drawings Soft Starter Kit Drawings
Tab 4 Application Information Common Issues Seen In The Field
Tab 5 Communications MODBUS RTU Using RS-485
Tab 6 Service Procedures Alignments And Adjustments
Tab 7 RTD Data Sheets Temp / Resistance Maps
ABB SSMt Training - 2007
SSM Commissioning
Final Inspection Before Start Up
Collect Data for Set Point Programming
Collect Nameplate Data from: Motor, Transformer, Load, Gearbox
Medium voltage cable Hi-Pot tests performed and successful
Check all control wiring
Verify all connections, fuses, current transformer circuit
Verify that all protective & timing relays have been set
With disconnect switch closed, verify MV door cannot be opened
Verify LV compartment plugs are connected
Verify that all insulating barriers are clean & dry
Inspect the equipment for loose parts, litter, tools
Review any key interlocking schemes
Verify that all barriers and doors are secured
ABB SSMt Training - 2007
MOTOR
LOAD
?
TRANSFORMER
Due to a lack of understanding, the SSM is the first thing to be blamed
when something doesnt seem to work right during commissioning
Many times, the end-user has to be educated in order to become
comfortable with the SSM. Primarily, the end-user needs to realize that the
SSM does not make power. It works similar to a fluid control valve, slowly
building up voltage and current to the motor
If the system power is weak and the voltage drops so low as to reduce the
Motor Torque below the Load Torque, the system will not come up to
rated speed
The Misunderstood SSM
ABB SSMt Training - 2007
Motor Torque produced is proportional to both
the Field and Rotor Voltages. This means that
Motor Torque is proportional to the square of the
Motor Terminal Voltage
The system will never make it to rated speed if not
enough torque is available from the motor to
overcome the Load Torque
The box beside can be manipulated, but the
Amount of Output must create sufficient Motor
Torque
SSM - 3 Dimensional Box Theory
TIME
AMPS
VOLTS
MOTOR
TORQUE
ABB SSMt Training - 2007
ABB SSM Product Training
Startup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSION A
SSM DESCRIPTION B
SSM FUNCTIONS - PROGRAMMING C
COMMISSIONING D
TROUBLESHOOTING & MAINTENANCE E
PROGRAMMING EXERCISE F
CONCLUSION G
ABB SSMt Training - 2007
Most troubleshooting is done primarily with the supplied SSM
Service Manual and the Soft Starter drawings
Hands-on troubleshooting with an actual SSM will be performed
tomorrow
SSM - Troubleshooting Outline
ABB SSMt Training - 2007
Test To Perform Ohm Meter Reading Test Result
From Position A to Position B Greater than 10K Ohm
Pass
Less than 10K Ohm
Fail
From Position B to Position C Greater than 10K Ohm
Pass
Less than 10K Ohm
Fail
Gate (G) to Cathode (K) for each SCR 8 to 100 Ohms Pass (Typical 8 to 20 Ohms)
Less than 8 or greater than 100 Ohms
Fail
Troubleshooting & Maintenance - SCR Test Procedure
When the condition of the SCRs is suspected, a resistance check can be
performed on the SCR heat sink assemblies in the right-hand cabinet to confirm if
they have been damaged. This test is to be performed on each individual
assembly per phase (there are 3 SCR heat sink assemblies per phase).
Note: Allow 15 minutes after shutdown for the stack assembly DV/DT
networks to discharge any stored DC voltages.
Refer to the image to the right for test connection references.
ABB SSMt Training - 2007
Fiber Optic Troubleshooting - Connectors
Be sure to check all connections and block
orientations as shown.
Ensure all fiber-optic connectors are fully
seated in their proper assemblies on the
circuit boards (SCR Stack Assembly).
Ensure indexing dot in the fiber-optic block
is placed over the white silk-screened mark
on the Main Board.
ABB SSMt Training - 2007
Minimum bend radius of the optical fiber
used in the Limitamp SSM is 2 [51mm].
If a bend radius is too small, the fiber core
will have tiny cracks on the outer portion of
radius.
Straightening a fiber after too tight of a bend
has been made will not fix it.
Fiber Optic Troubleshooting Bend Radius
ABB SSMt Training - 2007
The clear fiber optic core has a lower
melting point than the jacket
Heat damage can cause a minor distortion
or slight swelling that is barely visible on the
surface of the jacket
The damage can be felt with the fingers,
simply by pinching fiber lightly between
index finger & thumb, then drag fingers
North/South, East/West down length of fiber
Use caution when routing fibers through
starter and around circuit boards
Melted / Swelled Fiber Optic Cables
From Heat Shrinking Wire Markers
Near Fiber Optic Harness
Fiber Optic Troubleshooting Heat Damage
ABB SSMt Training - 2007
ABB SSM Product Training
Startup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSION A
SSM DESCRIPTION B
SSM FUNCTIONS - PROGRAMMING C
COMMISSIONING D
TROUBLESHOOTING & MAINTENANCE E
PROGRAMMING EXERCISE F
CONCLUSION G
ABB SSMt Training - 2007
SSM Setpoint Programming Exercise
Refer To Programming Exercise Presentation
ABB SSMt Training - 2007
ABB SSM Product Training
Startup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSION A
SSM DESCRIPTION B
SSM FUNCTIONS - PROGRAMMING C
COMMISSIONING D
TROUBLESHOOTING & MAINTENANCE E
PROGRAMMING EXERCISE F
CONCLUSION G
ABB SSMt Training - 2007
Mini-Quiz
1. What setpoint page requires you to input the motor data information?
2. If you needed to extend the time delay for the Acceleration Time Trip beyond
30 seconds, at what setpoint page would you make this change?
3. Name at two ways it is possible to damage a fiber-optic cable.
4. What are the 2 field-installable options for the SSM?
5. What are the three connection points of an SCR?
6. Does the SSM use a PLL circuit to control SCR firing?
7. What is the maximum amount of RTDs that can be programmed into the
Digital Control Unit (DCU)?
8. Name the 2 communication busses used for data transfer on the CPU Board
and Communications Board.
9. What are the 3 setpoints programmed into Setpoint Page 2 to start a motor
using Voltage Ramping with Current Limit?
10. What diameter are the firing LEDs on the Main Board?