Standard of Thermography Inspection

Differential
Temp
Max Temp
< 5
o
C 5
o
C 10
o
C 11
o
C 20
o
C 21
o
C 40
o
C >40
o
C
< 75
o
C Normal Low Medium High Critical
75
o
C 100
o
C
Information
of
overloading
Medium High Critical
Critical

>100
o
C
Information
of high
overloading
Critical Critical Critical Critical
Explanation:
All equipment including busbar, contactor, breaker, cable, capacitor, motor
and transformer exceeds 75
o
C temperature will deteriorate the equipment
insulation.
Equipment life time will be halved at exceed 10
o
C in the limit temperature of
75
o
C.
Four level severity in infrared inspection:
Low : Monitor and repair when possible
Medium : Repair with in 6 months
High : Schedule a shutdown to repair within 30 days
Critical : Repair as soon as possible
Critical case should inform related section immediately
Critical case also include the happen of melting in connection
Determaine the level of severity, in the background temperature about 28
o
C


Explanation:
Non-symmetrical load includes lighting, air conditioner, welding
panel and other utility equipment.
Equipment life time will be halved at exceeding 10
o
C in the limit
temperature of 75
o
C.
Four level severity in infrared inspection:
Low : Monitor and repair when possible
Medium : Repair with in 6 months
High : Schedule a shutdown to repair within 30 days
Critical : Repair as soon as possible
Critical case should inform related section immediately
Critical case also include the happen of melting in connection
Determaine the level of severity, in the background temperature
about 28
o
C
Compare the temperature of top and bottom connection of breaker
or fuse holder.