Sie sind auf Seite 1von 17

Generator protection :

1. Generator grounding
2. Excitation system
3. Generator stator thermal protection
Generator grounding
High resistance grounding
Distributive transformer
High resistance across the secondary
Excitation system
An electric generator or electric motor consists of a rotor spinning in a magnetic
field. The magnetic field may be produced by permanent magnets or by field coils.
In the case of a machine with field coils, a current must flow in the coils to
generate the field, otherwise no power is transferred to or from the rotor. The
process of generating a magnetic field by means of an electric current is
called excitation.
Generator stator thermal protection
In case of overload, thermal protection is
required for generator stator windings.
Temperature sensors
1. Resistance temperature detectors
2. thermocouples

Generator stator fault protection
Generator faults can cause sever damage to
insulatin,windings and the core.
The differential relay (87G) is commonly used as
primary protection for phase fault of generator stator
windings. This function is mostly completely selective
and can be used with very short tripping times.
Differential relays will detect three phase fault, phase
to phase fault and double phase to ground faults.
Differential relays will not detect turn to turn faults in
the same phase since there is no difference in the
current entering and leaving the phase winding.
Application and forms of differential
relays
one that operates when the vector difference
of two or more similar electrical quantities
exceeds a predetermined amount.
Differential relay
Under normal operating conditions



When a short circuit develops between the
two CTs:
Ground fault protection
Differential relays will not provide ground fault
protection on high impedance grounded
machines where primary fault current levels
are limited to 3-25 A.
Time delay overvoltage relay
Generator rotor field protection
Field circuit of a generator is ungrounded
system.
A portion of the field of the winding will be
short circuited, producing unbalanced air gap
fluxes
Rotor vibrations
A voltage relay is used to detect overvoltage in
the field winding produced by a ground fault.


Generator loss of field
When a synchronous generator loses excitation it will over
speed and operate as an induction generator.
It will continue to supply some power to the system and
will receive its excitation from the system in the form of
VAR.
During this condition, the stator currents will be increased
and, since the generator has lost synchronism, there can be
high levels of current induced in the rotor that can cause
dangerous overheating of the stator windings and the rotor
within a very short time.
The most widely applied methodfor loss of field protection
(40) is the use of distance relays to sense the variation of
impedance as viewed from the generator terminals.
Loss of synchronism
When a generator loses synchronism, the
resulting high peak currents and off-frequency
operation cause winding stresses, pulsating
torques, and mechanical resonances that are
potentially damaging to the generator and
turbine generator shaft (IEEE, 1995).
The conventional method for loss of synchronism
protection (78) is an impedance relay that
analyzes the variation in apparent impedance as
viewed at the terminals of the system element.
Over excitation
Motoring
Over voltage
Motoring or(reverse power)
Reverse power generally describes a condition where the
prime mover of a generator is not supplying sufficient
torque to keep the generator rotor spinning at the same
frequency as the grid to which the generator is connected.
In other words, the generator has actually become a motor
and is drawing current from the grid to which is connected
and is supplying torque to the prime mover which is
supposed to be supplying torque to the generator.
Reverse power protection (32) is a power relay set to look
into the machine and is, therefore, used on most units.
Although listed along with generator protection functions,
reverse power protection is actually designed for the
protection of the steam turbine.
Over voltage
Generator overvoltage may occur without
necessarily exceeding the V/Hz limits of the
machine.
Upon load rejection, the speed may increase and
cause a proportional rise in voltage. Under this
condition on a V/Hz basis, the overexcitation may
not be excessive but the sustained voltage
magnitude may be above permissible limits.
Overvoltage conditions can also occur due to
voltage regulator failure. Protection for generator
overvoltage is provided with an overvoltage relay
Abnormal frequencies

Generator breaker failure protection
system

Das könnte Ihnen auch gefallen