ground) 2. Type of conductors. 3. Switching Schemes. 4. Switchyard / substation Layouts.
1. Transmission Line Transmission lines and associated substations and their equipment / material are major assets of an power utility
Optimum utilisation of assets and providing reliable and quality power is the objective of an utility Contd.. Conventional Type
Lattice Type (Commonly used in India) Guye type Pole type
Gas Insulated Transmission Line(GITL) Gas used (SF6+N2) Could be under ground / over the ground
Lattice type towers Single Circuit (Tension Towers, suspension Towers) Double Circuit (Tension Towers, suspension Towers) Multi Circuit(Tension Towers, suspension Towers) Multi Circuit & Multi Voltage (Tension Towers, suspension Towers) Dead end type (Tension Towers)
Continued Tower classification based on angle of Deviation
Type A 0 to 2 degree (suspension tower) Type B 2 to 15 degree (Tension tower) Type C 15 to 30 degree (Tension tower) Type D 30 to 60 degree / Dead end tower - (Tension tower)
Continued Percentage of different types of tower
Plain Area
Type A 72% Type B 12% Type C 12% Type D 4%
Suspension type About 70% Tension type About 30% Continued Percentage of different types of tower
Plain Area
Type A -- Type B 35% Type C 35% Type D 30%
Suspension type Almost Nil Different Types of Towers Suspension Towers (HVAC, HVDC) No. of Disc Insulators No. of Disc Insulators 800kV 40/4x35 420kV 23/2x23 245kV 14/15 145kV 9/10 72.5kV 5/6 Tower Design Wind Force. Conductor Tension. Span. Type of conductor (Bundle / single) Ice loading
Contd Right of Way Requirement and power transmission capability
800kV 85/64m(S/C) / 67m(D/C) 2500-3000 MW 420kV 52m(S/C) / 46m(D/C) 600-700 MW 245kV 35 m 150-160 MW 145kV 27 m 50-60 MW 72.5kV 22 m 10-15 MW 36kV 18 m 115kV 15 m +/- 500kV HVDC 52m 2000-2500MW +/- 800kV HVDC 70m 6000-6400MW 1200kV 100m 6000-8000MW
Clearances and Shielding angle in respect of Transmission lin Ground Mid span Sag Shield Clearance (m) Clearance(m) (m) Angle (Deg.) 800kV 12.4 12.4 10 420kV 8.84 9.00 13 20 245kV 7.00 8.50 9 30 145kV 6.10 6.10 7 30 72.5kV 5.50 3.00 5 30
Current Carrying Capacity Heat Generated (Conductor loss) = Hc + Hr Hs Where Conductor loss = I x I x Rt I = Current rating Rt = Resistance at temperature t = R20 (1+ alpha x delta t) Hc = Heat Loss by Convection Hr = Heat Loss by radiation Hs = Heat generated by solar radiation Hc depends on wind velocity (Typical value 0.5 to 0.6 m/sec) Hr depends on emissivity of conductor ( Typical value 0.6) Hs depends on
solar absorption coefficient (depends on outward condition of conductor- Typically 0.6 for new bright & shiny conductor & 0.9 for old conductor)
and intensity of solar radiation (Typical value 1500W/sq. m)
Current Carrying Capacity ACSR Conductor (Ambient 50 deg. C and Max. 85 deg. C) Dog(14.15mm) 270A Panter(21mm) 415A Zebra(28.62mm) 620A Moose(31.77mm, 520 Sq. mm, 54/3.53mm Al 700A (Amb. 50) 7/3.53mm St) 850A (Amb. 40) Snowbird (30.6mm , 523.67 Sq. mm, 54/3.895mm Al ) 700A 7/2.215mm St) Bersimis(35.1mm) 820A Lapwing(38.2mm) 880A AAA Conductor (Ambient 50 deg. C and Max. 85 deg. C) AAAC (29.79mm, 525 Sq. mm, 61/3.31mm Al) 700A Permissible Line Loading Line loading Depends on Voltage Regulation Stability Current carrying capacity (Thermal loading)
Surge Impedance Loading (SIL) - Limits loading of long line For short line loading can go beyond SIL limit Permissible loading limit to be restricted to Thermal Loading limit Surge Impedance The surge impedance loading or SIL of a transmission line is the MW loading of a transmission line at which a natural reactive power balance occurs. MVAR produced = MVAR used V*V/Xc = I*I*Xl Surge Impedance = SQRT(L/C) Approx. 250 ohms for >= 420kV and 350 Ohms < 420kV
Permissible Line Loading Voltage Size of conductor SIL (MW) level
Thermal lading depends on Ambient Temperature Maximum permissible conductor temperature(ACSR: 75 0 C, AAAC: 85 0 C) Wind Velocity
Conductor Current Thermal loading
800 kV ACSR Bersimis 820A 900 MW 400 kV ACSR Moose 700A 400 MW Manual on Transmission Planning Criteria Fault Clearance System Fault Clearance System Protection System CT VT TE Protection Equipment Trip Coil Circuit Breaker Breaker Circuit Mecha- nism Figure 1 The fault clearance system. DC-System
Neutral point earthing
Effectively earthed (EFF up to 1.4) (earth fault current may be 60 to 120%) Non-effectively earthed (EFF 1.7) Isolated
Control in general
Whether disconnectors are operated manually / by motor Presence of earthing switches Whether control is via alocal control board or a local computer terminal Degree of substation automation, sequence control Remote control from grid control centre Regulations Whether station is manned or unmanned
Contd.
Protection in general Substations to be constructed so that all possible faults can be eliminated: Selectively Fault current rating of lines and equipment is not exceeded No danger to personnel Stability of system is maintained Load and production held in balance
Contd. Protection according to protected items
Line protection (Distance protection, over voltage,)
Compensating equipment protection Contd. According to type of protection
Short Circuit protection Earth Fault protection Harmonic protection Overload protection Over voltage protection Over fluxing protection
Automatic switching schemes (Load shedding, auto reclosing, network sectionalisation and splitting of the network)
Transmission Line Protection
Sl. No. Protection 765 kV 400 kV 220 kV 132 kV or 66 kV (a) Main I- Distance protection
Y Y Y Y (b) Main II- Distance protection or directional comparison protection or phase segregated line differential protection
Y Y Y/N N (c) Directional instantaneous definite minimum time (IDMT) type earth fault relay Y
Y
Y if both Main-I & Main-II are distance protection s otherwise N N (d) Directional IDMT over current and earth fault back up protection
N N Y if Main-II is not provided otherwise N Y (e) Two stage over voltage protection
Y Y N N (f) Auto reclosing Y (Singl e phase and three phase) Y (Single phase and three phase) Y (Single phase and three phase)
Y (Three phase)
Note: (1) Y- Required; N- Not required; Y/N- Optional.
(2) Transmission lines with distance protection shall, in general, have carrier aided inter-tripping or blocking feature. Separate cores of current transformer and voltage transformer shall be used for Main-I and Main-II.
Transformer Protection
Sl. No. Protection 765 kV 400 kV 220 kV or 132 kV 66 kV (a) Differential protection
Y Y Y Y (b) Over fluxing protection
Y Y Y N (c) Restricted earth fault (REF) protection
Y Y Y Y (d) Backup directional over current and earth fault protection (HV and LV side) or impedance protection
Y Y Y Y (e) Buchholz, WTI and OTI (for 1 MVA and above), MOG with low oil level alarm, OSR for OLTC, PRD, SA on both primary and secondary sides of transformers located outdoors and connected to over head lines
Y Y Y Y (f) Tertiary winding protection Y Y Y (above 100MVA rating) N (g) Over load alarm
Y Y Y N
Note: (1) Y- Required; N- Not required.
(2) WTI- winding temperature indicator; OTI- oil temperature indicator; OLTC- on load tap changer; PRD- pressure relieve device; OSR- oil surge relay; MOG- magnetic oil gauge; SA- surge arrester.
Reactor Protection
Sl. No. Protection
765 kV 400 kV (a) Differential protection
Y Y (b) REF protection
Y Y
Mechanical Forces Weight (Normal weight of apparatus, conductors, structures etc.; temporary loads due to frost & ice, maintenance staff) Wind Load Ice load
Short Circuit Loads
Earth Quake load wherever necessary
Maintenance and / or erection load
Additional mechnical loads (due to low ambient tempt., CB operation) CIRCULATING CURRENT DIFFERENTIAL PROTECTION EXTERNAL FAULT CONDITION x x x x Fault 1500A W
W
W
Diff Relay W
250A 450A 300A 1000A/1 A B C D 500A 0.25A 0.45A 0.30A 1.0A 1000A CIRCULATING CURRENT DIFFERENTIAL PROTECTION INTERNAL FAULT CONDITION
x x x x W
W
W
W
Fault 87 1.5A Diff. relay 250A 450A 300A 500A 1000/1A 0.25A 0.45A 0.30A 0.50A A B C