New Rectifier TP48200B


Settings

Ahmed Osama Salah

18-12-2012

Integration Team
Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

www.huawei.com

Contents
I.

DC connection.

II.

Alarms Connection.

III. Web User Interface.


IV. Change System time.
V.

Change the LVD Settings.

VI. Change Battery Rated Capacity


VII. Load Low Voltage Alarms Disconnected Settings.
VIII. Non Float Status Alarm Setting.
IX. Import Default Configuration

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page1

I. DC Connection.

BLVD
Circuit
breakers

LLVD
Circuit
breakers

There are two kinds of circuit breakers


LLVD CBs : which are connected ( 2DCDU of BTS3900L and DCDU of 3G RRUs).
BLVD CBs: which are connected ( all MW links ).

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

II.Alarms Connection.

UIM: reports 8 dry contact alarms connected to EMUA board.


ALM0: AC Power Failure.
ALM1:DC under voltage alarm OR over voltage alarm.
ALM2: Rectifier Fault Alarm.
ALM3: SPD Failure Alarm.
ALM4:Battery Temperature Alarm.
ALM5:Fuse Burn-out Alarm.
ALM6:Battery Temperature Alarm.
ALM7:User Defined.
ALM8:User Defined.

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

III. Web User Interface

Connect your Ethernet cable to Port 1 in SMU ( Site Monitoring Unit ).


Change your laptop local IP and subnet mask.
Enter the IP address of SMU ( Default :10..168.0.10 Subnet mask:255.255.255.0).
Set user name to (admin) and password to (001)

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

IV. Change System Time

Choose Site Configure > System Date Time


Set the Date , Time and System Time Zone .

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

V. Change the LVD Settings.

Choose System Configure > LVD Setting


Set the BLVD Disconnected Voltage to 43.2 and LLVD Disconnected Voltage to 47.
All above values are according to VDF requirements in Emerson Power Cabinet .

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

VI. Change Battery Rated Capacity

Choose System Configure > VRLA Battery Basic Parameters


Set the Rated Capacity according to the number of battery strings in the site
Every battery string equivalent to 100 AH.

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

VII. Load Low Voltage Alarms Disconnected Settings.

Choose Alarm Configuration > battery Summary


Set the Shown alarms to Enable and to Relay number 7 .

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

VIII. Non Float Status Alarm Setting.

Choose Alarm Configuration > battery Summary


Set the battery discharge alarms to Enable and to Relay number 8.

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2

IX. Import Default Configuration

Choose Site Configuration> Configuration Operation


You can import a default configuration file saved from previous site has the same
configuration.

Copyright 2010 Huawei Technologies Co., Ltd. All rights reserved.

Page2