Substation
Automation Products
Training

2006-03-30
1

Substation Automation Products Training

Control IED
REC 670
Interlocking

ABB Power Technologies AB, 2005

Contents

2006-03-30
2

Substation Automation Products Training

Purpose and features

Basic principles

Interaction between bays

Reservation method

Function blocks

Different switchyard arrangements

SCILO

POS_EVAL

Implementation example

Exercise

Interlocking
The purpose of the interlocking function is:

To avoid dangerous or damaging switchgear operations and


to assure personnel safety

ABB Power Technologies AB, 2005

The features are:

2006-03-30
3

Distributed functionality, not depending on a central function

Standardized and well-proven software modules for easy


and safe implementation

Information exchange over the station bus, which means


minimizing of cabling between IEDs

Interlocking conditions depend on the circuit configuration


and apparatus position status at any given time

Substation Automation Products Training

Interlocking
The interlocking modules are
based on these basic principles:

ABB Power Technologies AB, 2005

2006-03-30
4

Disconnectors shall not be


opened or closed on-load
Earthing switches shall not be
closed onto voltage
CB:s shall not be closed when
surrounding disconnectors are in
intermediate positions
CB opening is only interlocked at
a bus-coupler bay, if a busbar
transfer is in progress

Substation Automation Products Training

Basic principles

Interlocking
Data exchange example between bays
Station bus
Bay 1

Bay n
Disc QB1 and QB2 closed

Disc QB1 and QB2 closed

WA1 not earthed


WA2 not earthed
WA1 and WA2 interconn

Bus coupler

.....

WA1 not earthed


WA2 not earthed
WA1 and WA2 interconn

WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
WA1 and WA2 interconn
in other bay

WA1

ABB Power Technologies AB, 2005

WA2
QB1

2006-03-30
5

QB2

QB1

QA1

QA1

QB9

QB9

Substation Automation Products Training

QB2

QB2 QB1
QA1

QC1

QC2

Interlocking

Interaction between modules

Interlocking module on bay level

Interlocking
modules in
other bays

Apparatus control
modules
SCILO

SCSWI

SXSWI

Apparatus control
modules

Interlocking
module

SCILO

SCSWI

SXCBR

Apparatus control
modules

ABB Power Technologies AB, 2005

SCILO

2006-03-30
6

Substation Automation Products Training

SCSWI

SXSWI

Interlocking

Reservation method

Station HSI

Control center

GW
Station bus

ABB Power Technologies AB, 2005

Close
Disconnector

2006-03-30
7

Substation Automation Products Training

Open
Breaker

Interlocking modules
WA1 (A)

Function block ABC_LINE

WA2 (B)
WA7 (C)
QB1

QB2

QB7
QC1

QA1

Line bay in arrangements


with single, double, and
bypass busbars

QC2
QB9
QC9

WA1 (A)
WA2 (B)
WA7 (C)
QB1

QB2

QB20

QB7

QC1

ABB Power Technologies AB, 2005

QA1

QC2

2006-03-30
8

Substation Automation Products Training

Function block ABC_BC

Bus coupler in arrangements


with single, double, and
bypass busbars

Interlocking modules
WA1 (A)
WA2 (B)
QB1

Function block AB_TRAFO

QB2
QC1

QA1
AB_TRAFO

Transformer bay in
arrangements with single and
double busbar

QC2

T
QC3
QA2
QC4
QB3

Function block BB_ES

QB4
QC

ABB Power Technologies AB, 2005

QA2 and QC4 are not


used in this interlocking

2006-03-30
9

Substation Automation Products Training

Busbar earthing switch on


any busbar part

Interlocking modules
WA1 (A1)

WA2 (A2)

Function block A1A2_BS


QB1

QB2

QA1

QC3

QC4

QB
WA1 (A1)
ABB Power Technologies AB, 2005

WA2 (A2)

Function block A1A2_DC

2006-03-30
10

Substation Automation Products Training

Bus section coupler between bus


sections A1 and A2

Bus section disconnector between


bus sections A1 and A2

Interlocking modules
WA1 (A)
WA2 (B)
QB1

QB2
QC1

QA1

QC4
QA2
DB_BUS_B

DB_BUS_A
QC2

QB61

QC5

Function blocks

QB62

DB_BUS_A, DB_BUS_B

QC3

QB9
DB_LINE

Bus links of a double


breaker bay

QC9

DB_LINE

ABB Power Technologies AB, 2005

2006-03-30
11

Substation Automation Products Training

Line connection of a
double breaker bay

Interlocking modules
WA1 (A)
WA2 (B)
QB1

QB2
QC1

QC1

QA1
QC2

BH_LINE_A, BH_LINE_B

QC2

QB6

QB6
QC3

BH_LINE_A

Function blocks

QA1

QC3

QB61

QA1

BH_LINE_B

Line connections of a
breaker and a half
diameter

QB62

BH_CONN
QB9

QB9
QC1
QC9

ABB Power Technologies AB, 2005

QC9

BH_CONN

2006-03-30
12

Substation Automation Products Training

QC2

Connection between two


lines of a breaker and a
half diameter

Interlocking

Open/close position of
switch device

ABB Power Technologies AB, 2005

Open/close operation from


interlocking logic is enabled

2006-03-30
13

Substation Automation Products Training

SCILO

CI01SCILO
POSOPEN
POSCLOSE
OPEN_EN
CLOSE_EN

EN_OPEN
EN_CLOSE

Open/close operation at
closed/open or
intermediate or bad
position is enabled

Interlocking

POSOPEN
POSCLOSE

SCILO logic

SCILO
=1

EN_OPEN

&

>1
&

OPEN_EN
CLOSE_EN

EN_CLOSE

&

>1
&

ABB Power Technologies AB, 2005

en04000525.vsd

2006-03-30
14

Substation Automation Products Training

Interlocking

Interaction with apparatus control function

CS01SCSWI

CI01SCILO

ABB Power Technologies AB, 2005

From
interlocking
module

POSOPEN
POSCLOSE
OPEN_EN
CLOSE_EN

2006-03-30
15

Substation Automation Products Training

EN_OPEN
EN_CLOSE

BLOCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_GRT
RES_EXT
SY_INPRO
SYNC_OK
EN_OPEN
EN_CLOSE
XPOS1
XPOS2
XPOS3

EXE_OP
EXE_CL
SELECTED
RES_RQ
START_SY
POSITION
OPENPOS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUSE
XOUT

XC01-/XS01SXCBR/SXSWI
BLOCK
LR_SWI
OPEN

XPOS
EXE_OP
EXE_CL

CLOSE

SUBSTED

BL_OPEN
BL_CLOSE

OP_BLKD
CL_BLKD

BL_UPD

UPD_BLKD

POSOPEN

OPENPOS

POSCLOSE
TR_OPEN

CLOSEPOS

TR_CLOSE

CNT_VAL
L_CAUSE

RS_CNT
XIN

TR_POS

PE01POS_EVAL
POSITION OPENPOS
CLOSEPOS

To
interlocking
module

Interlocking

Position including quality

POS_EVAL
PE01POS_EVAL
POSITION OPENPOS
CLOSEPOS

Open/close position of
switch device

Truth table:

ABB Power Technologies AB, 2005

POSITION
0
0
1
1
2
2
3
3
2006-03-30
16

Substation Automation Products Training

Quality
0
1
0
1
0
1
0
1

OPENPOS CLOSEPOS
0
0
0
0
0
1
0
0
1
0
0
0
0
0
0
0

Interlocking

Implementation example for an AB-arrangement


ABC_LINE

Position indications
from own bay via
function block
POS_EVAL or BI

1
0

Earthing switch
for busbar 1 (A)
Earthing switch
for busbar 2 (B)

BB_ES
BBESOPTR
BBESCLTR

BB_ES

1
0

BBESOPTR
BBESCLTR

From bus-coupler bay


ABC_BC
BC12CLTR

No line voltage
1
and no fuse failure 0

VPBC12TR

No transmission error from


bus earthing switches

ABB Power Technologies AB, 2005

No transmission error
from bus-coupler bay

User-specific
conditions
Not used = 1

2006-03-30
17

Substation Automation Products Training

QA1_OP
QA1_CL
QB9_OP
QB9_CL
QB1_OP
QB1_CL
QB2_OP
QB2_CL
QB7_OP
QB7_CL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QC9_OP
QC9_CL
QC11_OP
QC11_CL
QC21_OP
QC21_CL
QC71_OP
QC71_CL
BB7_D_OP
BC_12_CL
BC_17_OP
BC_17_CL
BC_27_OP
BC_27_CL
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_ES
EXDU_BPB
EXDU_BC
QB9_EX1
QB9_EX2
QB1_EX1
QB1_EX2
QB1_EX3
QB2_EX1
QB2_EX2
QB2_EX3
QB7_EX1
QB7_EX2
QB7_EX3
QB7_EX4

QA1CLREL
QA1CLITL
QB9REL
QB9ITL
QB1REL
QB1ITL
QB2REL
QB2ITL
QB7REL
QB7ITL
QC1REL
QC1ITL
QC2REL
QC2ITL
QC9REL
QC9ITL
QB1OPTR
QB1CLTR
QB2OPTR
QB2CLTR
QB7OPTR
QB7CLTR
QB12OPTR
QB12CLTR
VPQB1TR
VPQB2TR
VPQB7TR
VPQB12TR

To apparatus control module


SCSWI via SCILO for own bay
To earthing switch
for busbar 1 (A)
BB_ES
BB_DC_OP
VP_BB_DC

To earthing switch
for busbar 2 (B)
BB_ES
BB_DC_OP
VP_BB_DC

To bus-coupler bay
ABC_BC
BBTR_OP
VP_BBTR

VPX = 1 if status of X is valid


EXDU_X = 1 if no transmission error
from bay Y

Interlocking engineering

Exercise

time

ABB Power Technologies AB, 2005

Exercise

2006-03-30
18

Substation Automation Products Training