Craig Chidester
909 288 7990

AFDs and Their Effect on


Power Quality

What Kind of Power Quality Effects?


Power factor?
PF = kW / kVA
High motor content means lagging PF
100HP motor, 460V, 93% eff, 119A

(100HP x 0.746kW/HP) / 0.93 = 80.2kW


119A x 460V x 1.73 / 1000 = 94.8kVA
PF = 80.2kW / 94.8kVA = 84.6% @ FL
But at actual load, more like 70% or less

PF is improved with AFDs to 90 95%


AFDs seen as resistive load

What Kind of Power Quality Effects?


Incoming Sine Wave Notching?

Arises from SCR front ends on AFDs


Forced commutation causes line notches
But modern AFDs use diode front ends
Self commutating no notching

What Kind of Power Quality Effects?


Voltage sag?

Standard motor starters allow 650% inrush


Weak power systems are affected
500HP motor on 1000kVA, 5.75%Z Xfmr
650% X (500 / 1000) X 0.0575 = 19% sag
AFD limits inrush to 110% (or 150%)
110% X (500 / 1000) X 0.0575 = 3% sag

What kind of Power Quality Effects?


Harmonic Distortion
AFDs, DC Drives, UPSs, DC power supplies (computers,
duplicators, faxs) will cause current (and voltage) harmonics
Single phase 3rd, 6th, etc (triplens) can cause transformer
neutral conductor overheating
Three phase 5th, 7th, 11th, 13th, etc can cause equipment
malfunctions
Big questions How much? and How much is too much?

What are Harmonics?

Definition:
Harmonics are integral multiples of some fundamental
frequency that, when added together, result in a
distorted waveform.

What are Harmonics?

+
sin(5x)
f(x) = sin(x)
f(x) =
5
The resulting wave shows a strong departure from the smooth
waves comprising it:

f(x) = sin(x) + sin(5x)


5

What are Harmonics?


In fact, any function may be constructed from a
sine wave and some number of its harmonics:

Where do they come from?


The power company typically supplies a reasonably
smooth sinusoidal waveform:

Where do they come from?


...but nonlinear devices will draw distorted waveforms,
which are comprised of harmonics of the source:

Common sources of Harmonics


Lighting ballasts

UPS systems

AC and DC drives

AC drives and Harmonics

Converter

DC bus
&
smoothing

Determine the line-side


harmonics

Inverter

Determines load-side
harmonics

AC drives and Harmonics


EFFECTS OF LOAD-SIDE
HARMONICS:
Have implications for the motor
insulation and windings.
Essentially have zero effect on
other equipment on the power
system.

Inverter

Determines load-side
harmonics

AC drives and Harmonics


LINE-SIDE HARMONICS CAN HAVE
FAR-REACHING EFFECTS ON THE
POWER SYSTEM:
Distribution transformers
Converter

DC bus
&
smoothing

Standby generators
Communications equipment
Switchgear and relays

Determine the line-side


harmonics

Computers, computer systems


Diagnostic equipment

AC drives and Harmonics


Typical 6-step converter waveform:
Harmonic Content
I5 = 22.5%
I7 = 9.38%
I11 = 6.10%
I13 = 4.06%
I17 = 2.26%
I19 = 1.77%
I23 = 1.12%
I25 = 0.86%

Harmonics and transformers


Transformer overheating and potential
insulation failure result from several
conditions caused by harmonics:
Increased skin and proximity effects
Harmonics circulating in the primary
winding
AFC

AFC

Increased hysteresis losses


Increased eddy current losses
DC in the primary windings

Harmonics and transformers


Many transformers are rated by
K factor which simply describes
their ability to withstand harmonics.
Transformers may also be derated
to compensate for the additional
heating caused by harmonics.

AFC

AFC

Improved transformer designs have


also been developed, with oversized
neutral busses, special cores, and
specially designed coils.

Harmonics and power-correction capacitors

Power correction capacitors can cause


series and parallel resonance effects on
a power system.
If a harmonic is generated which excites
a system resonance, amplification of that
harmonic may occur.

Calculation of the harmonic resonance frequency for the


system can give an indication of potential resonance
problems.

Harmonics and power-correction capacitors


EXAMPLE:
Assume a 1500 kVA supply xfmr,
with a 5.75% impedance.

1500 kVA
5.75%

Also assume 600 kVA of power


correction capacitors on the system

600 kVAC

The harmonic resonance frequency is defined by:

hr =

kVAsc
kVAC

1500 / 0.0575 = 6.6


600

Recommended limits - IEEE 519


The Institute of Electrical and Electronics Engineers (IEEE)
has set recommended limits on both current and voltage
distortion in IEEE 519-1992.
Voltage distortion limits (@ low-voltage bus):
Application class

THD (voltage)

Special system

3%

General system

5%

Dedicated system

10 %

Recommended limits - IEEE 519


MAXIMUM HARMONIC CURRENT DISTORTION
in percent of IL
Isc/IL
<20
20-50
50-100
100-1000
>1000

<11
4.0
7.0
10.0
12.0
15.0
Isc:
IL:

Individual harmonic number (odd harmonics)


11<h<17
17<h<23
23<h<35
2.0
1.5
0.6
3.5
2.5
1.0
4.5
4.0
1.5
5.5
5.0
2.0
7.0
6.0
2.5

Maximum short-circuit current at the Point of Common


Coupling (PCC).
Maximum demand load current (fundamental) at
the PCC.

TDD
5.0
8.0
12.0
15.0
20.0

Attenuation of Harmonics
Inductive Reactance
Method:

Add a line reactor or isolation transformer


to attenuate harmonics.

Benefits:

Low cost.
Technically simple.

Concerns:

Tends to offer reductions in only higher


order harmonics. Has little effect on the 5th
and 7th harmonics.
Because of the associated voltage drop,
there are limits to the amount of reactance
that may be added.

Attenuation of Harmonics
Passive Filters
Method:

Provide a low-impedance path to ground


for the harmonic frequencies.

Benefits:

May be tuned to a
frequency between two prevalent harmonics
so as to help attenuate both.

Concerns:

Tuning the filters may be a labor-intensive


process.
Filters are difficult to size, because they offer
a path for harmonics from any source.
Quite sensitive to any future system changes.

Attenuation of Harmonics
Active Filters
Method:

Inject equal and opposite harmonics onto the


power system to cancel those generated by
other equipment.

Benefits:

Have proven very effective in reducing


harmonics well below required levels.

Concerns:

The high performance inverter required for the


harmonic injection is costly.
Power transistors are exposed to conditions
of the line, so reliability may be a problem.

Attenuation of Harmonics
12-pulse Rectifiers
Method:

Two separate rectifier bridges supply a single


DC bus. The two bridges are fed from phaseshifted supplies.

Benefits:

Very effective in the elimination of 5th and 7th


harmonics.
Stops harmonics at the source.
Insensitive to future system changes.

Concerns:

May not meet the IEEE standards in every


case.
Does little to attenuate the 11th and 13th
harmonics.

Attenuation of Harmonics
18-pulse Rectifier
Method:

An integral phase-shift transformer and rectifier


Input which draws an almost purely sinusoidal
waveform from the source.

Benefits:

Meets the IEEE standards in every case!


Attenuates all harmonics up to the 35th.
Stops harmonics at the source.
Insensitive to future system changes.

Concerns:

Can be expensive at smaller HPs

Comparison of waveforms
6-pulse converter
note the level of distortion
and steep current rise.

12-pulse converter
the waveform appears more
sinusoidal, but still not very
smooth.

18-pulse converter
virtually indistinguishable
from the source current
waveform.