AUTOMATIC WATER LEVEL

CONTROLLER

THE AUTOMATIC WATER LEVEL CONTROLLER IS THE AIR


CONTROLLED TYPE WITH THE SINGLE ELEMENT WHICH
INDICATES THE WATER LEVEL DETECTING ON THE
DIFFERENTIAL PRESSURE BETWEEN THE CONDENSER
PROVIDED AT THE STEAM SIDE OF THE UPPER PORTION OF
THE BOILER AND THE ACTUAL WATER LEVEL DETECTED BY
THE DIFFERENTIAL PRESSURE TRANSMITTER .

THIS VALVE IS USED FOR THE COMBARISON WITH PRESET


VALUE IN THE CONTROLLER AND AN OPERATNG SIGNAL IS
DETERMINED TO ADJUST THE OPENIG OF THE FEED
CONTROL VALVE , THERE BY THE WATER LEVEL IS
CONTROLED ADJUSTING THE FEED WATER TO BOILER .

LEVEL CONDENSER
THE WATER LEVEL IN THE CONDENSER IS
PROVIDED ABOVE THE MAXIMUM ALLOWABLE WATER LEVEL,
IN WHICH DRAIN PRODUCED WHICH COOLED STEAM MAKES
CONTACT WITH THE EXTERNAL ATMOSPHERE CAN BE
COLLECTED SO THAT THE WATER LEVEL CAN BE KEPT
CONSTANT . THE DIFFERENTIAL WATER HEAD (h) BETWEEN
THIS CONSTANT WATER LEVEL AND WATER LEVEL IN THE
BOILER IS DECTED BY DIFFERENTIAL PRESSUR
TRANSMITTER.

DIFFERENTIAL PRESSURE CELL


THE DIFFERENTIAL PRESSURE CELL CONSISTING
OF BELLOW AND NOZZLE FLAPPER CONVERTS THE
DIFFERENTIAL WATER HEAD INTO AN AIR PRESSURE SIGNAL
OVER THE RANGE OF 0.2 TO 1.0 kgf/sqcm . THE OUT PUT
SIGNAL IS ALSO USED AS A SIGNAL FOR INDICATIONS AND
DELIVERING AN ALAM TO A REMOTE LOCATION

CONTROLLER
AIR PRESSUR SIGNAL FROM THE DIFFERENTIAL
PRESSUR CELL ARE INDICATED AS PROCESS SIGNAL , WHILE
SIMULTANEOUSLY BEING USED FOR COMPARISON WITH
PRESET VALUE IN THE DEVIATION MECHANISM TO THE
EXTENT OF DEVIATION FOR CONTROL PURPOSES.

FEED REGULATING VALVE


THE FEED REGULATION VALVE CONSIST VALVE
DISK , DIAPHRAM AND VALVE POSITIONER . THE VALVE
POSITIONER OUTPUT THE AIR PRESSUR TO BE EXERTED ON
THE DIAPHRAM BY COMPARING THE OPENING OF THE
CONTROL VALVE WITH AN OPERATING SIGNAL SENT FROM
THE REGULATOR . THE AIR PRESSUR IS USED TO VERY THE
OPENING OF THE CONTROL VALVE FOR CONTROLLING
DELIVERY FROM THE WATER PUMP , AND THE WATER LEVEL
IN THE BOILER .