Beruflich Dokumente
Kultur Dokumente
K.KRISHNAMOORTHY
AEE/TECHNICAL SERVICES
MTPS
IS / ISO 9001:2008
CERTIFIED POWER PLANT
Unit 1: 227days
Unit 2: 205days
Unit3: 272days
Unit4: 311days
Station: 71days
IS / ISO 9001:2008
Quality Policy:
-Uninterrupted quality power to TNEB grid
-Minimizing forced & planned outages
-Quality excellence in all our activities
Quality Objective:
-Annual generation:>6500mu
-Plant load factor :>88%
-Aux. power consumption:>8.5%
-Specific oil consumption :<1.25ml
THERMAL GENERATION
Fuel is fired in
Boiler and
Super heated
steam
Is produced
Energy in SH
Steam from
Boiler is used
for achieving
Rotational energy
In the Turbine.
Generator
connected with
Turbine rotates
and produces
Electricity.
Auxiliary
Utility
(6.6KV & 415V)
Voltage is stepped up
Connected to Grid
(110, 230, 400 & 785KV)
3/9/15
What is Turbine?
Turbine is the prime mover for the
Generator
It is a rotating machine.
Thermal energy is converted into
rotational energy by means of blades
of Impulse and Reaction.
This rotational energy is used in
Generator to generate power
LMW- Leningrade machine works,
Russian deign,supplied by BHEL
CONDENSER VACUUM
Steam from
FSH 130 ksc
1 ksc
CRH 26 ksc
Re heater
IPT
HPT
Generator
LPT
HRH 24 ksc
Condenser
Vacuum- 670mm Hg
TURBINE
HP TURBINE
IP TURBINE
LP TURBINES
HP ROTOR &
CASING
INTERMEDIATE PRESSURE
TURBINE
Reaction Turbine
No of stages :11
Shaft out put:105MW
Inlet/outlet Steam flow :540/461 t/hr
Inlet/outlet Steam temp : 535/190
deg
Inlet/outlet Steam pr. : 24/1.32 ksc
No of stages :8(4+4)
Shaft out put:40MW
Inlet/outlet Steam flow :461/446 t/hr
Inlet/outlet Steam temp : 190/45 deg
Inlet/outlet Steam pr. : 1.32/0.06 ksc
1. Main Turbine.
2. Oil system.
3. Condenser
4. Cooling water system.
5. Hot well & Condensate system
6. HP Heaters & LP Heaters
7. Feed Water system
OIL SYSTEM
Supplies oil for lubricating all
bearings in TG set(1ksc)
Supplies oil for governing
system(20ksc)
Generator seal oil system(10ksc)
HP LP B/P SYSTEM(30%)
During startup of the unit, to raise
the steam parameters and to match
it with Turbine parameters.
Bypass system is required to bypass
the steam w/o entering the HPT from
MSL to CRH and IPT from HRH to
Condenser.
CONDENSATE SYSYEM
The steam from the exhaust of the
LPT, condenses into water and hence
it is called as condensate
Condensate water collected in the
hotwell, at the bottom of the
condenser
CEP, Main Ejector, GSC1, LPH1,
GSC2, LPH2,3,4 and Deaerator.
DEAERATOR
Removes dissolved oxygen, from
condensate water.
To prevent internal corrosion of boiler
tubes.
HEAT TRANSFER
1. CONDUCTION
2. RADIATION
3. CONVECTION
CONDUCTION
CONDUCTION IS THE TRANSFER
OF HEAT FROM ONE PART OF THE
MATERIAL TO ANOTHER OR ONE
MATERIAL TO ANOTHER WHICH
ARE IN CONTACT.
RADIATION
THE TRANSFER OF HEAT FROM
THE HOT BODY TO THE COLD ONE
BY MEANS OF ELECTROMAGNETIC
HEAT WAVES OR RAYS WITHOUT
HEATING THE MEDIUM THROUGH
WHICH IT PASSES BETWEEN THE
TWO BODIES INVOLVED.
CONVECTION
HEAT TRAVELS FROM ONE
PARTICLE OF THE BODY TO
ANOTHER PARTICLE BY ACTUAL
MOTION OF HEATED PARTICLES
DUE TO DIFFERENCE IN DENSITY.
TURBINE PROTECTIONS
1. CONDENSER VACUUM VERY
LOW
2. LUBE OIL PRESSURE VERY
LOW
3. AXIAL SHIFT HIGH
4. GENERATOR TO TURBINE THRO
86T
5. BOILER TO TURBINE THRO
MFT
GENERATOR
Voltage: 15.75 KV
Capacity: 210MW
Coolant:
ROTOR- Hydrogen gas
STATOR-DM WATER
TURBO GENERATOR
H
ROTOR
210
ACTIVE POWER
211
POLE
Capacity
MVA)
Stator Voltage
Stator Current
Rotor Voltage
: 210 MW (247
: 15.75 KV
: 9050 Amps.
:310 Volts.
coil(copper losses)
2. Iron losses in core ( Hysteresis /
Eddy current losses)
3. Load on Rotor by the way of
excitation power (DC V & I due to
VAR loading on Generators)
4.Other frictional loss in bearings
(which are negligible)
50
Reactive Power
Inductors oppose the change in current by
dropping voltage directly proportional to rate of
change of current
Inductive Load in the power system will produce
the energy which transfers power to source
Energy, which returns to the source in each
cycle, is known as reactive power.
The loss of power in a system arising from the
production of electric and magnetic fields. This
the portion of power flow due to stored
51
Reactive power(cont)
KW is the real power that actually does the
work,
KVAR is the reactive power.
KVA is the apparent power
KVA is the vector sum of both the reactive(KVAR)
and the active power ( K.W.).
Mathematically, power factor is the ratio between
KW and KVA (PF = KW / KVA).
In an inductive load, such as a motor, active
power performs the work, and reactive power
creates the electromagnetic field
Power factor measures how efficiently the current
is being converted into useful real workwith a
low power factor, more electrical current will be
required to provide the same amount of
real power.
52
Hydrogen cooling
system of
Turbogenerator
57
Characteristics of Hydrogen
Molecular weight
2.0156
Relative density
0.06952
Boiling point
-252 C
:
:
:
Purity of Hydrogen
At pressure 0.035 atm. of hydrogen heat
carrying capacity is 1.
But at 2.0atm. of hydrogen heat carrying
capacity is 1.95 and there is serious
possibility of hydrogen explosion with in
the machine
To ensure the safety of operation purity
of hydrogen on the generator Casing
must be maintained as high as possible.
The purity of hydrogen should be 98%
above but should not be less than 98% .
60
The components of H
system
H cylinder bank
CO cylinder bank
Gas driers with reactivation
cabinet.
Gas panel. (not in service at
present ).
H circulation fans in the rotor @
both ends of exciter and turbine
ends
H coolers in the casing and its
cooling water pumps
61
SW system (Diagram)
62
Synchronous generator
operation &
synchronizing
procedures
What is meant by
synchronization?
In a Power Station, it is the term
used
for
the
process
of
connecting the Generator to the
Grid.
GENERATOR
230 KV
POWER
TRANSFORMER
230 KV TUNNEL
DAM PH
SALEM 400 KV-I
SALEM 400 KV-II
METTUR AUTO SS
SINGARAPET
Circuit breakers
A circuit breaker is a switching and
current interrupting device. It
serves two basic purposes
Switching during normal
operating conditions for the
purpose of ,operation and
maintenance
Switching during abnormal
conditions such as short circuits
and interrupting fault currents.
There are several types of faults
and abnormal conditions. The fault
current can damage the
equipments if allowed to flow for
a longer duration.
Since the breaker is an fast acting
Circuit breakers
Types:
OCB
OMCB
ABCB
SF6
Isolators
Isolators are Off load devices
Isolators are used for disconnecting
the circuit under no load conditions
since it is operated under no load
condition it does not have any
making or breaking capacity
To prevent mal operation of
isolators it is interlocked with
circuit breakers and earth switches.
Isolators used in switchyards are
normally three pole isolators
Whereas in our 400KV yard the
isolators are of individual pole
POWER GRID
A grid is a larger
interconnected network of
transmission lines linking
different generating stations
and load centers
OBJECTIVE OF GRID
Continuity of service
Economy of power
production
GRID TYPES
National Grid
Regional Grid
State Grid
Q&A
Thank You