Operation And Troubleshooting Air Cooled,

Water Cooled And Chilled Water System


8th -11th of December 2013
By: Muhd Nasir Bin Mhd Yusuf

www.acson.com.my

Mollier
Evaporatio
n
Compressi
on
Condensati
on
Expansion

www.acson.com.my

Mollier

www.acson.com.my

Mollier

www.acson.com.my

Compression
Adiabatic Insulate compressor
Isentropic Parallel with Entropy
Isothermal Compressor Same
temperature

www.acson.com.my

Subcooling
Subcooling
Range -15C ~ -9.4C (5F ~ 15F)
>-9.4C over-charged or mismatched
component installed
<-15C undercharged or mismatched
component installed
<-15C will reduce efficiency metering device
Solution;
Check evaluate system components, locate
& repair leaks.
Charge in refrigerant to correct subcooling.

www.acson.com.my

Superheating
Superheating
Range -6.7C ~ -1.1C (20F ~ 30F)
<-6.7C liquid enter into compressor
> -1.1C compressor too hot (burn)
Charging Refrigerant Correct
Subcooling & Superheat

www.acson.com.my

Superheat Capillary
tube

www.acson.com.my

Superheat TXV

www.acson.com.my

Superheat

www.acson.com.my

Cooling Coils
Off Coil- 4 ~10C
Air Velocity- 500 ~ 550 ft/min
Design 350 ~ 450 CFM / TR

www.acson.com.my

Troubleshooting Using PH
Chart

www.acson.com.my

Mollier
P2
Cooling Capacity = x RE
Power Input = x HC
COP = RE =
HC

www.acson.com.my

Mollier
P2
Cooling Capacity = x RE
Power Input = x HC
COP = RE =
HC

www.acson.com.my

Mollier
P1
Cooling Capacity = x RE
Power Input = x HC = (little
bit)
COP = RE =
HC

www.acson.com.my

Mollier
P1
Cooling Capacity = x RE
Power Input = x HC =
COP = RE =
HC

www.acson.com.my

Troubleshooting by Temperature
Checking
Return Air Temperature Indicave of
Room Temperature
Causes for high temperature
Supply Air Temperature Indicative
of coil performance
Supply Air Temperature and room
humidity

www.acson.com.my

Troubleshooting of Air Cooled


System
How ambient air temperature affects
system performance
Effects of high entering air
temperature
Non-performance due to high
condensing pressure
Servicing of condenser coil
Effects of fouling on the cooling coils
Servicing of the cooling coils
www.acson.com.my

Troubleshooting of Air Cooled


System

www.acson.com.my

Case Study
Case P2
No. (psig
)
1
310
134
F
2

270
123
F
220
108
F

P1
Possible Problems
(psig
)
73
Check condenser
43F Air temperature @
condenser
Condition on condenser coil
53
Indoor Site
285F Evaporator problem
20
-5F

Refrigerant leak

www.acson.com.my

Operation & Troubleshooting of Cooling


Tower

Types of Cooling Towers


Working principles of Cooling Towers
Performance of Cooling Tower:
Range, Approach
Troubleshooting of cooling towers

www.acson.com.my

Cooling Tower

www.acson.com.my

Cooling Tower

www.acson.com.my

Water Pump

www.acson.com.my

Case Study
Case
No.

Ambien T1 T2 P1
t
F F psi
Twb
g
F

P2
psi
g

1
2
3
4

www.acson.com.my

Possible
Problem

www.acson.com.my