Term Project
Hazem Hamam
962864
Outline
Design of AC TL.
Design of DC TL.
Design of a 500kV, 2GW AC TL.
Design of a 400kV, 2GW DC TL.
Economic Comparison.
Conclusion.
Power Transmission
Importance of power
transmission.
Means to transmit and sell
power.
Distant energy sources.
Trading energy.
Generation away from cities.
AC Transmission
Dominated transmission for a long
time.
Needs synchronization.
Simple & cheap terminals.
Expensive towers.
Works well for short distances.
Use of models to represent lines.
AC Transmission Design
PLL at 5% VD, 30-45o AD.
Double or single circuit lines.
Margin to minimize overloading.
Number of lines=total P/PLL.
AC Transmission Design
Entering current.
Appropriate conductors CCC.
Transformer (TRF) rating.
Conductors between TRF and TL.
Bundling.
AC Transmission Design
Insulation design criteria.
Withstand of standard unit = 15kv.
Adjacent centers at 0.146m.
Minimum clearance.
Sag and tension.
Tower dimensions.
AC Transmission Design
TRF protection.
Over-load margin.
CT ratio.
Mismatch.
Percentage operation line.
Pickup value.
AC Line Diagrams
TRF
1
TRF
5
TRF
2
TRF
6
TRF
3
TRF
7
TRF
4
TRF
8
AC Tower Dimensions
12m
12m
32m
5.678m
20m
25 30 m
DC Transmission Design
Converting Station is expensive.
Converting TRF.
Converting Valve. (quad valves).
AC & DC filtering.
DC Transmission Line.
Pole Configuration
Smaller, Cheaper DC Towers.
Line Commutation.
DC Transmission Design
6-pulse configurations.
Converting
TRF
Thyristor Module
+
DC
-
DC Transmission Design
12-Pulse Configuration
Thyristor Module
AC
Side
Mid-point
DC bus
arrestor
DC
Side
Thyristor Quad-valve
Delta
winding
AC
Filters
TRF
protection
Converter TRF:
V=380kV/400kV
S=1200MVA
3p 3 windings
Y winding
3p ACSR 874500,54,7 2
bundles
CCC=950A/bund
V=380kV
S=1200MVA
I=1824A
TRF
protection
TRF
protection
866
A
3000
A
Mid-point
DC bus
arrestor
400kV
DC
Side
+
D
C
-
V = 400kV DC
P = 1100MW
I = 2750
DC
Filters
Transmission Line
ACSR 874500, 54, 7
3 bundles per pole
CCC per pole = 950A
Total I per pole =
2750A
R = 17.18 ohms
Span = 200 m
DC Filters
To the DC
side of the
converting
Valve
V = 352.75kV DC
P = 970.08MW
I = 2750
TRF 2
Converting
Valve
Converting
Valve
Diagram of the
Line
Converting
Valve
TRF 1
Converting
Valve
TRF 2
12m
22m
15-20m
DC Tower
Dimensions
Economic Comparison
Break-Even Distance.
AC Cost Estimation Legend:
1 Station = 10,000,000$.
DC Towers 200m span = 45,000$.
1m of conductor for AC = 160$.
Economic Comparison
Table of Equipment:
Equipment
TRF 380/500kV
700MVA
Number
8
105,000$
3,500
80,000$
AC Conductors
12/m
80$
Converter Station 2
10,000,000$
DC Tower 200m
Span
3,500
50,000$
DC Conductors
4/m
160$
AC & DC Costs
1. 98,644,000 $ for AC TL.
2. 91,040,000 $ for DC TL.
Conclusion
AC TL higher Tower and conductor
costs and lower terminal costs.
DC TL lower Tower and conductor
costs and higher terminal costs.
Economics determines the design
to be used.
Line length determines which one
is more economic.