Sampling Point

for
Boiler System

(1.) Demi Water Pump Discharge


Test Parameter:
Specific Conductivity
Silica (
Total Iron
pH

(2.) Deaerator Inlet

Test Parameter:
Silica (
Total Iron

(3.) Deaerator Outlet


No online Analyzer
Only Grab Sample
Parameter
Not yet identify or establish

(4.) Drum Outlet


Test Parameter:

Cationic Conductivity
Sodium
Dissolve Oxygen
pH

(6.) Drum Water


Test Parameter:
(5.) Economizer Inlet
Test Parameter:
Specific Conductivity
Dissolved Oxygen
pH

pH

(7.) Main Steam


Test Parameter:

Cationic Conductivity
Silica (
Sodium
Total Iron

(8.) Condenser Hotwell


Test Parameter:
Cationic Conductivity

(9.) Condensate Pump Discharge


Test Parameter:

Cationic Conductivity
pH
Dissolved Oxygen
Silica (

Chemical Dosing
for
Boiler System

(1.) Deaerator Outlet


Chemical Feed:
Oxygen Scavenger
Ammonia

(2.) Boiler Drum


Chemical Feed:
Phosphate

(3.) Condensate Pump Discharge


Chemical Feed:
Oxygen Scavenger
Ammonia

Mass Balance
Heat Balance Diagram (100% MCR)

Test Parameter

pH

Cationic Conductivity

Specific Conductivity

Dissolved Oxygen

Silica

Sodium

Total Iron

Total Hardness

Free Chlorine Concentration

Chemical Feed

Phosphate

Oxygen Scavenger (Hydrazine)

Ammonia

Chemical Reaction

System Description
for
Main Cycle Chemical Dosing System

Oxygen Scavenger Dosing Unit


Oxygen Scavenger dosing unit shall be provided to ensure
chemical conditioning of the feed water by removing the
oxygen.
Oxygen Scavenger is to be injected to the condensate pump
discharge line, the boiler feed pump suction line, and CCW unit
line for reducing oxygen content in the feed water.

Oxygen Scavenger Dosing Unit consists of:


Equipment

Quantity
(set/unit)

Capacity/Speed

KKS

1. Oxygen Scavenger Dosing Tank

1QCA10BB110

2. Oxygen Scavenger Dosing Tank


Agitator

1QCA10AM110

3. Oxygen Scavenger Dosing Pump

2
(one is
standby)

1QCA11/12AP110

4. Oxygen Scavenger Metering Cylinder

1QCA10CF010

5. Oxygen Scavenger Dispensing Pump

1QCA20AP110

Ammonia Dosing Unit consists of:


Equipment

Quantity
(set/unit)

Capacity/Speed

KKS

1. Ammonia Dosing Tank

1QCD10BB110

2. Ammonia Dosing Tank Agitator

1QCD10AM110

3. Ammonia Dosing Pump

2
(one is
standby)

1QCD11/12AP110

4. Ammonia Metering Cylinder

1QCD10CF010

5. Ammonia Dispensing Pump

1QCD20AP110

Phosphate Dosing Unit consists of:


Equipment

Quantity
(set/unit)

Capacity/Speed

KKS

1. Phosphate Dosing Tank

1QCC10BB110

2. Phosphate Dosing Tank Agitator

1QCC10AM110

3. Phosphate Dosing Pump

2
(one is
standby)

1QCC11/12AP110

Chemical Injection Procedure


Chemical
1. Oxygen
Scavenger
Solution

2. Ammonia

Injection Point

Dosage Control

Operation mode of
Power Plant

COP discharge

Manual
(Manual Valve Open)

Intermittent

Deaerator Outlet

Auto
(Control by signal of condensate
pump discharge Dissolved Oxygen)

Continuous

COP discharge
Deaerator
Deaerator Outlet
Outlet

3. Phosphate

Boiler Drum

Intermittent
Auto
Auto
(Control
(Control by
by signal
signal of
of Economizer
Economizer
pH)
pH)

Continuous
Continuous

Continuous

Chemical Design Data


Chemical

Chemical
Formula

Concentration
Remark
(Delivery)

(Diluted)

1. Oxygen Scavenger
(Hydrazine)

80%

0.5%

Liquid Mixing

2. Ammonia

25%

5%

Liquid Mixing

3. Phosphate

98%

3%

Powder Mixing

System Description
for
Feed Water System