Beruflich Dokumente
Kultur Dokumente
1.
2.
3.
4.
Daily maintenance
1.
2.
3.
4.
5.
Leak detection
Refrigerating plants must be gastight to prevent refrigerant leakage
and air entering the low-pressure
side when under a vacuum. Systems
which have been opened to the
atmosphere during repairs, must be
pressure tested for mechanical
strength and leaks before charging
with refrigerant.
Pressure tests
Pressure tests should be done with
nitrogen. Water or other fluids must
not be used as a test medium. The
plants compressors must not be
used to pressurise the plant. The
pressure is gradually increased by
pressurising with nitrogen gas the
pressure is equal to 1.5 times the
maximum working pressure of the
system. This pressure should be
maintained for about 10 minutes.
Leak detection
equipment
Electronic leak detectors
Electronic leak detectors are the
most sensitive and accurate method
of leak detection. The detector
contains an internal pump that draws
air into a probe, or tube. If refrigerant
gas is present in the sample, the
electrodes in the sensing element
generate a current, and an output
signal is obtained.
Halide lamps
Halide lamp is used to locate leaks of
HCFC refrigerants. This method is
based on the colour of a flame that
surrounds a glowing copper element.
The flame turns blue-green if the air
being consumed contains the
refrigerant.
These lamps should only be used in
well ventilated spaces.
Routine inspections
The high pressure side of the system may
easily be tested for leaks with the plant
running, but it may be necessary to stop
the compressor, and allow the pressure in
the low pressure side to rise sufficiently for
leak test in the low pressure side. The
amount of refrigerant in the system should
also be strictly monitored as a drop in level
may indicate the presence of a leak. In the
event of a major leak, the initial leak test
should be made using the soap bubble
method, specially in areas where there are
signs of an oil leak.
Drying by evacuation
1.
2.
3.
4.
Charging procedures
Refrigerating plants should not be
overcharged with refrigerant, as this may
overload or damage the compressor.
To ensure that the correct amount is
added, the refrigerant should be weighed
during charging.
The liquid refrigerant is decanted from the
refrigerant bottle into the system via a
charging valve just after, the liquid
receiver.
Charging Procedure
1. Weigh refrigerant bottle
2. Connect refrigerant bottle to charging valve with flexible
charging line.
3. Crack bottle liquid valve before tightening line to blow out air.
4. Close main liquid line valve and pump down system.
5. Open charging valve and carefully open liquid valve on
refrigerant bottle.
6. Liquid refrigerant will flow into the system.
7. Start compressor.
8. Continue charging until required amount of refrigerant has
been charged.
9. Check weighing scale reading and observe liquid level in
receiver.
10.Close charging valve and open main liquid valve and observe
liquid flow through sight glass. Bubbles indicate the need for
further charging.
11.If charge is complete, close bottle valve, and disconnect
charging line.
12.Store empty refrigerant bottle for reuse.
Condensers
Once a year, the tubes should be cleaned
with a tube brush in order to remove
deposits which would cause a high
condensing pressure. The gaskets must be
glued to the condenser end plate with
good contact. If the partition wall gasket is
not properly installed, there is a risk that it
will blow, leading to an excessively high
water velocity and to damage to the tube
plate.
If a tube has become defective, it does not
have to be replaced immediately. Up to
10% in each pass (flow direction) can be
plugged.
Defrosting
Another task which maybe regarded
as maintenance is to keep frost
deposits on provision and cargo
refrigerating plants under control.
Frequent defrosting assures that the
plant will cause few problems.
Investigating trouble
1.
2.
3.
4.
5.
6.
7.
8.
TROUBLE SHOOTING
When problems are incurred in a
refrigerating plant, these can be attributed
in most cases to a shortage of refrigerant.
Bearing this in mind, always commence
trouble-shooting by checking the
refrigerant charge.
For example, in the case of HCFC plants,
too little refrigerant prevents the oil, which
always circulates in the system, from
being returned as the gas velocity is low,
and this leads to various functional
troubles.
CONTAMINANTS
If the moisture present in a
refrigerating system exceeds the
amount that the refrigerant can hold
in solution it will exist as free water.
At temperatures of 0C or lower, the
free water will freeze into ice in the
expansion valve or evaporator,
restricting the flow of refrigerant. To
avoid freeze-ups, the moisture
content in low temperature HCFC
refrigerant systems must be
Oil
In refrigerating systems some oil is always carried
over from the compressor into the condenser by
the refrigerant gas, from where it is carried by the
liquid into the evaporator. The presence of oil in
the circulating refrigerant reduces the heat
transfer capacity of the various heat exchangers,
the problem being greatest in the evaporator,
since oil becomes more viscous and tends to
congeal at low temperature. To prevent oil related
problems, the operation of the oil separator
should be checked regularly to ensure oil is being
returned to the compressor lubrication system.
The amount of oil added to the lubrication system
should also be strictly monitored; an excessive
amount indicates that oil is being trapped in the
evaporator or suction line.
down.
1. Shut off compressor and close suction line valves.
2. The thermometer in the sea water outlet of the
condenser will indicate the actual condensing
temperature, when there is no further drop in
temperature.
3. Record the condensing pressure.
4. On a refrigerant pressure gauge, look up the
saturation temperature that corresponds to the
condensing pressure.
5. If the condensing temperature is less than the
corresponding saturation temperature of the
condensing pressure, it is necessary to purge.
Purging Non-condensable
Gases
1. Pump down the refrigerant by shutting
the liquid valve at the outlet of liquid
receiver.
2. Continue cooling the condenser for 10 to
15 minutes.
3. Open purge valve on top of condenser,
and slowly release gases.
4. Since it is difficult to tell if excessive
refrigerant is being purged with the noncondensables, purge slowly.
Compressor Short-Cycles
Possible Cause
Action
Low refrigerant
charge.
Reduced
evaporator
capacity.
Compressor Runs
Continuously
Possible Cause
Low refrigerant
charge.
Compressor valves
leaking.
Action
Check for proper charge. If
low, repair any leaks and
recharge.
Pump down, remove cylinder
heads, and check.
Legionella bacteria