Beruflich Dokumente
Kultur Dokumente
Protection
Protective Device
Coordination
Definition
Overcurrent Coordination
Objective
Criteria
Economics
Operating Practices
Previous Experience
Design
Analysis
When:
Reliability
Speed
Performance
Economics
Simplicity
Protection
Spectrum Of Currents
Load Current
Overcurrent
Up to 100% of full-load
115-125% (mild overload)
Abnormal loading condition (Locked-Rotor)
Fault Current
Fault condition
Ten times the full-load current and higher
Coordination
Coordination
C
t
D B
A
A
C
Equipment
Motor
Transformer
Generator
Cable
Busway
I2 t
I2t
I 2t
2
Motor
Gen
Xfmr
Cable
Transformer Category
ANSI/IEEE C-57.109
Frequent-Fault
Incidence Zone*
Transformer
FLA
200
t
(sec)
Thermal
I2t = 1250
Infrequent Fault
(D-R LG) 0.58
Frequent Fault
Mechanical
K=(1/Z)2t
Inrush
2.5
Isc
25
I (pu)
Transformer Protection
MAXIMUM RATING OR SETTING FOR OVERCURRENT DEVICE
PRIMARY
SECONDARY
Over 600 Volts
Over 600 Volts
600 Volts or Below
Transformer
Rated
Impedance
Circuit
Breaker
Setting
Fuse
Rating
Circuit
Breaker
Setting
Fuse
Rating
Circuit Breaker
Setting or Fuse
Rating
600 %
300 %
300 %
250%
125%
(250% supervised)
More than 6%
and not more
than 10%
400 %
300 %
250%
225%
125%
(250% supervised)
Table 450-3(a)
source: NEC
Protective Devices
Fuse
Thermal Magnetic
Electro-Mechanical
MCP
Overload Heater
Fuse
Voltage Levels
Characteristic Curves
Min. Melting
Total Clearing
Application
Total Clearing
Time Curve
Minimum Melting
Time Curve
Let-Through Chart
15% PF (X/R = 6.6)
230,000
300 A
100 A
12,500
60 A
5,200
100,000
Fuse
Generally:
Selectivity Criteria
Typically:
Non-CLF:
CLF:
Molder Case CB
Thermal-Magnetic
Magnetic Only
Integrally Fused
Current Limiting
High Interrupting
Capacity
Types
Frame Size
Trip Rating
Interrupting Capability
Voltage
Thermal Maximum
Thermal Minimum
Magnetic
(instantaneous)
LVPCB
Interrupting Rating
LT PU
CB 2
CB 1
CB 2
LT Band
480
ST PU
CB 1
IT
If =30 kA
ST Band
kV
Motor Protection
Thermal Protection
Fault Protection
125% of FLA
125% of FLA
115% of FLA
LRA sym
LRA asym (1.5-1.6 x LRA sym) + 10% margin
Fault Protection
(NEC Art 430-52)
175% of FLA
300% of FLA
800% of FLA*
250% of FLA
(49)
I2 T
tLR
O/L
MCP
(51)
ts
Starting Curve
MCP (50)
LRAs
LRAasym
200 HP
Overcurrent Relay
Time-Overcurrent Unit
IR
51
IL
Instantaneous Unit
Instantaneous Calculation
IR
50
IL
Relay Coordination
41
Fixed Points
Points or curves which do not change
regardless of protective device settings:
Situation
4.16 kV
CT 800:5
50/51
Relay: IFC 53
CB
Cable
CU - EPR
Isc = 30,000 A
DS
5 MVA
6%
Solution
Transformer:
5,000kVA
694 A
3 4.16kV
5
IR IL
4.338 A
800
IL
(6/4.338 1.38)
5
52.1A 55 A
800
IL
IR
R
CT
Question
Answer
For delta-wye connection, with single line-toground faults on the secondary side, the curve
values must be reduced to 58% (shift to the left
by a factor of 0.58)
Question
Answer
Question
What T/C Coordination interval should be
maintained between relays?
Answer
B
t
CB Opening Time
+
Induction Disc Overtravel (0.1 sec)
+
Safety margin (0.2 sec w/o Inst. & 0.1 sec w/ Inst.)
Question
What is Class 10 and Class 20
Thermal OLR curves?
Answer
Answer