Beruflich Dokumente
Kultur Dokumente
2 Siemens
Abstract: The paper presents a new automated method for assessing the security of protection systems concerning selectivity
and speed to reduce the risk of unnecessary disturbances and blackouts. The invented algorithms are capable to handle complex
structures. Hence, the system behavior of a protection system and network is analyzed and assessed as a whole and it has not to be
reduced to its single components or devices. The simulation tool is used as an engine to provide the possibility of a holistic si
mulation of networks together with the protection.
The system-method can be divided into two main approaches: Fault pattern analysis (FPA) and economic impact assessment
(EIA). The FPA calculates running faults through the whole grid for diverse scenarios of load flows. Economic aspects of non
selective protection systems are also be introduced and presented by the EIA method. It benefits from the fact that protection
devices violating dependability or security will lead to additional outage. This outage is calculated and evaluated by the differ
ences of simulated outage and unavoidable outage. The large amount of resulting data is stored in a central database. Intelligent
filtering and data preparation allow a holistic assessment and visualization of complete networks of different architecture.
Routinely checks of contingency sequences with the presented methods will reveal bottlenecks of the protection behavior itself
and of the coordination of network and protection.
Keywords: Protection security assessment, selectivity, speed, blackout prevention, protection coordination, holistic si
mulation, routinely contingency check, fingerprint analysis
Introduction
Method of investigation
www.apap2011.org
SIMULATION TOOL
ARJO BUILD
C. Evaluation Tool
A general evaluation method of protection system behavior is
given by the terms of Fig. 2. Following definitions are stated
[1]:
SC FAULT
SIMULATIO
N
DATA
EVALUATION TOOL
STORAGE
FAULT PATrERN
ANALYSIS (FPA)
Cl
:;::
Cl
ECONOMIC IMPACT
ASSESSMENT (EIA)
<
iii
c
;::
:
-lr
Z
-l
is
C/>
C/>
-<
-l
;::
:
Dependability
Figure 1
Security
power grid model will be copied to the database. All other sys
tems read required information from and write their calculated
results to the database. By the use of an entity-relationship-model,
the data storage system enables associations and filtering by keys
between all scenarios, simulated :faults, results and the selection
of
data under consideration of various conditions.
B. Simulation tool
The simulation tool starts with the initialization of the
power
grid model to be assessed. ill the first step, all installed
protection
devices are analyzed, categorized and linked to their
associated
electric equipment. From these results protection zones
and selec
tivity-requirements may be defined. After initialization
and sto
rage of the results, the scenario builder generates a broad
diversi
fication of grid states with different load flows. For each
defined
scenario and for each protection zone the SC :fault
simulation
program calculates different kind of short circuits and
different
amounts of :fault resistances. As the simulation
engine
PSSSINCAL is used. [8] The location of the SC-faults
is mov
ing from calculation to calculation through the whole
network in
steps of i.e. 1 - 5% of the line length. The setngs for step
size,
resistances, scenarios, etc. either may be on standard
values or
may be limited or specialized by user's selection over 1858
graphical
user interfuces. The use of an automatic control of the
Figure 2
uct (GNP) estimation is proposed. The outage costs per kWh can
be calculated as follows:
outage cost ($/kWh)
GNP ($)
TotalEnergConsumption(kWh)
A. Grid model
The case studies were carried out on an existing 20-kV- dis
(1)
X'
0.12 nIkm
to DG4
operator
o
6,5
2,1
4.2
-1.4
Figure 3
B.
Relay
Sectinjn
g pomt
3+Por--..(MW]
I
Qou-(MVAr(
Protection system
E.
(DG5)
Visualization tool
1859
additional load drop through all of the simulated mults and scena
rios.
LMddrop
non-directional.
The considered protection fimctions of the DG tmits at the PCC
are:
J 4 5 6 7 8 9 10 II 12 IJ 14 15 16171819
Zone
(e.g. the cable from the PCC to the generator transformer). For all
DG tmits it is possible to discriminate faults in the distribution
ent allocation of the highest values. Here, zone no. 4 and no.7
delayed. [2]
etary advantages.
Costs
[]
20000
and
it can also be configured smaller or wider by the user. The com
one with
maximum
DG infeed
DGs
on).
The
bination
of the asimulation
definition
leads to (all
41,800
single
simu
considered
lations that are transferredand executed by the SC simulation tool.
Parallel to the simulation tool and after all simulations, \\-hich are
Figure 5
because it
maloperations.
shows
and
rates
the
importance
J 4 5 6 7 8 9 10 11 12 IJ 14 1516171819
Zone
of
1860
~ --cc--1------- ---
vice no. 4 is displayed. On the right side the statistic shows all
devices that trip for faults in protection zone no. 4. It can be easily
seen that the device itself reacts selective without any overfunc
-+----=~~-----
-----l ~
1
n(s)
1.0
tions. But the right side of the diagram shows several devices that
are tripping on faults in zone no. 4.
20
25
30
35
fa111tplx~in1.0
0C
Fault zonn ",ilb n:aclK)fl
orprotccl1oon device
no.4
A
A6
in wnc
00.4
1
2
0.8
0.'
II
I
IS
J
0.'
O
8
7
1
9
IS
. ..
16
17
16
17
I
z......of r
1
3)
IS
OJ
u
s
10
20
faultplacei.n1l
)l'IC
IS
"
1,
0,0
Zoneofp1occcuondc\ttt
11
Figure 7
FPA for defined scenarios with no active and active DG infeed, fault
resistance 0
Figure 6
?O
II
0.'
IS
"
..
0.'
0.'
10
18
IO
Conclusion
[I]
Jager, J., Krebs, R.: ' Automated protection security assessment of today's and
future power grids', IEEE Power and Energy Society General Meeting, 2010
on the right side there is the one with all DGs active. The x-axis
[2 ]
[ 3]
Keil, T., Jager J., SOllner N., BoppT., Krebs R.:'Software Assisted Develop
ment of Protection Coordination Concepts in Nationwide Power Systems', 9.
protection zone. The clearing times and the selectivity are 400 ms
(light). With focus on zone no. 14, the first zone is very short.
[ 4]
Therefore, the average speed of this device is slow for its faults.
6,
ill that
Report B5-202
[5]
.
function, but overfunctions that are caused by sympathetic trip
the case of full DG infeed the selectivity shows still no under
Yamashita K., Joo S.-K., Li J., Zhang P., Liu Ch.-Ch.: Analysis, Control, and
Economic Impact Assessment of Major Blackout Events. ETPEP Euro. Trans.
on Electr. Power, 18:854-871,2008
[6]
ping (cp. also fig. 6). The malfunctions occur for faults behind the
Bums S.,
GrossG: Value
end of the first zones where the undirectional starter facilities trip.
hnprovement can be accomplished in two ways: First by accele
rating the average tripping time by increasing the first zone of
[7]
PSSSINCAL 'Efficient planin ng software for electricity and pipe networks', SIEMENS AG, PTD
SE PTI, www.siemens.com
lpower-technologieslsoftware