Excitation System
&
AVR
August 21, 2015
EXCITATION PRINCIPLE
Stator induced Voltage
E = K. L. d/ dt
K = constant
L = length exposed to flux
d/ dt = rate of change of flux
270
0
90
360
180
TYPES OF EXCITATION
EXCITATION SYSTEM
ROTATING
SYSTEM
Conventional
Rotating
machines
STATIC
SYSTEM
High frequency
excitation
Brushless
Excitation System
EXCITATION SYSTEM
REQUIREMENT
Reliability
Sensitivity and fast response
Stability
Ability to meet abnormal conditions
Monitoring and annunciation of parameters
User friendliness
COMPONENTS OF TYPICAL
EXCITATION SYSTEM
Input and output interface , Aux. power supply, FB
AVR: At least two independent channels
Follow up control and changeover
Excitation build up and Field Discharging system
Cooling / heat dissipation components
Limiters
Protective relays
Testing , Monitoring and alarm / trip initiation
Specific requirements :
Field Flashing, Stroboscope, PSS,
August 21, 2015
575 v
AVR
AUTO
15.75 kV
MAN
FB
FF
FDR
415 v AC
August 21, 2015
10
Excitation power from generator via excitation transformer. Protective relays for
excitation transformer
Two channels : Auto & manual, provision for change over from Auto to Manual
Limiters : Stator current limiter, Rotor current limiter, Load angle limiter etc.
Alternate supply for testing
11
Field Breaker
EXC TRFR
18KV/700V
1500KVA
THYRISOR
BRIDGE
FIELD
voltage regulator
GENERATOR
Crow
Bar
From TGMCC- C
Non linear
resistor
Field
discharge
Resistor
Pre Excitation
415/40V,10KVA
August 21, 2015
12
Field flashing
For start up DC excitation is fed to the field from external source like
station battery or rectified AC from station Ac supply .
Filed flashing is used to build up voltage up to 30 %.
From 30 to 70 % both flashing and regulation remains in circuit.
70 % above flashing gets cut-off
13
BRUSH
GEAR
14
15
Brushless excitation
FIELD BREAKER
R
Y
ARMATURE
ROTATING
DIODES
FIELD
(PM)
PILOT
EXCITER
August 21, 2015
MAIN
EXCITE
R
GENERATOR
16
17
AVR
21 KV
18
19
22
Unit
capacity
MW
Excitation
Current at
Full Load
Excitation
Voltage at
full load
Ceiling
Volts
200/ 210
2600
310
610
500
6300
600
1000
23
PMG
24
Description
Brushless Excitation
Type of system.
Requirement of additional
bearing and increase of
turbo generator shaft length.
Maintenance.
Static Excitation
25
MAIN EXCITER
26
EXCITER ROTOR
27
EXCITER COOLING
VAPOUR EXHAUST
COOLER
28
GENERATOR
I
XG
EF =
EF
I . XG + VT
VT
29
GENERATOR
Phasor diagram of the Generator
Ef
IL.Xd
VT
IL
30
GCB
GENERATOR
GT
G
Xd
Ef
XT
VT
Vbus
31
GENERATOR
Vector Diagram of Generator and GT
connected to an infinite bus
EF
IL.Xd
VT
Vbus
IL.XT
IL
32
GENERATOR
In the equivalent Circuit and Phasor diagram, the notations used have the
following description:
Vbus
VT
EF
Xd
XT
Transformer reactance
IL
Load Current
Phase angle
August21, 2015
33
GENERATOR
POWER ANGLE EQUATION
Referring to the phasor diagram on slide no.14;
Sin / IL.{Xd+XT}
Sin (90+ ) / EF
VIL Cos / EF
VIL Cos
Pmax
EF . V / X
Note that the Electrical Power Output varies as the Sin of Load angle
34
35
Physical
significance
of load angle
Stator
mag.
axis
red
N
ROTOR
Rotor
mag.
axis
yellow
STATOR
blue
August 21, 2015
36
P2
Excitation constant;
EF2
P1
Power output P1 to P2
EF1
2
1
2
I2
Vbus
Locus of
Constant
Excitation
I1
ACTIVE POWER CHANGE
August 21, 2015
37
Locus of P = const.
Steam Flow constant;
Excitation increased
Power output Constant
EF2
EF1
2
1
2
I2
Vbus
Locus of
Constant
Excitation
I1
I Cos = Constant
August 21, 2015
38
EXCITATION CHANGE
Excitation Control
39
AVR
40
41
42
43
44
45
AVR
There are two independent control systems
1. Auto control
2. Manual control
The control is effected on the 3 phase output of the pilot
exciter and provides a variable d.c. input to the main exciter
46
AVR
The main components of the voltage Regulator are two closed
loop control systems each followed by separate gate control unit
and thyristor set and de excitation equipment
Control system 1 for automatic generator voltage control
(AUTO) comprises the following
47
AVR
Generator voltage control
The output quantity of this control is the set point for a following.
48
AVR
This equipment acts on to the output of the generator voltage,
control, limiting the set point for the above excitation current
regulator. The stationary value of this limitation determines the
maximum possible excitation current set-point (field forcing
limitation);
Limiter for the under-excited range (under excitation limiter),
Delayed limiter for the overexcited range (over excitation limiter)
49
AVR
In the under excitation range, the under
excitation ensures that the minimum excitation
required for stable parallel operation of the
generator with the system is available and that
the under -excited reactive power is limited
accordingly
50
AVR
The set-point adjuster of the excitation current
regulator for manual is tracked automatically (followup control) so that, in the event of faults, change over
to the manual control system is possible without delay
Automatic change over is initiated by some special
fault condition. Correct operation of the follow-up
control circuit is monitored and can be observed on a
matching instrument in the control room. This
instrument can also be used for manual matching.
August 21, 2015
51
AVR
FAULT INDICATIONS
The following alarms are issued from the voltage
regulator to the control room.
AVR fault
AVR automatic change over to MANUAL
AVR loss of voltage alarm
August 21, 2015
52
AVR
The current feedback is utilized for active and
reactive power compensation and for limiters
53
Excitation Interlocks
Preconditions for Excitation
ON
Excitation ON command
N>90%
Protection
Of
FCB Of feedback
5s delay
Excitation
ON
External trip
GCB is OFF
54
Delay 1sec
Exc OFF
GCB OFF
External trip
55
Capability Curve
Capability Curve relates to the limits in which a generator can
Operate safely.
Boundaries of the Curve within with the machine will operate
safely
Lagging Power Factor/Overexcited region
Top Section Relates to Field Heating in Rotor Winding
Right Section Relates to Stator current Limit
Straight line relates to Prime Mover Output
Leading Power Factor/ Underexicted region
Lower Side relates to Stator end ring Limit
Further down relates to Pole slipping
August 21, 2015
56
57
LIMITERS
58
60
61
62
V/F limiter
Also known as over fluxing limiter
It is the protection function for the GT
V/F ratio , eddy current , the local eddy current causes
thermal over loading of GT
In DVR mode V/F ratio is continuously monitors the limit
violation
In case V/F ratio crosses the limit characteristic, the upper limit
as the effective AVR set point is reduced as a function of V/F
ratio
This limiter is used when it is required to keep the unit operating
even in case of substantial frequency drops , for instance in
order to prevent complete breakdown of the system, a V/F
limiter is used to lower the voltage proportional with frequency
August 21, 2015
63
drop
2 nd priority
3 rd priority
Voltage regulator
UN-2010
64
65
66