What is Excitation system?


Creating and strengthening the magnetic field
of the generator by passing DC through the
filed winding.

August 21, 2015

Why Excitation system?


With large alternators in the power system,
excitation plays a vital role in the management
of voltage profile and reactive power in the
grid thus ensuring Stability

August 21, 2015

EXCITATION PRINCIPLE
Stator induced Voltage
E = K. L. d/ dt
K = constant
L = length exposed to flux
d/ dt = rate of change of flux

Frequency of induced Voltage


F = NP / 120
Magnitude of flux decides generated voltage and speed of
rotation decides frequency of generated voltage

August 21, 2015

270
0

August 21, 2015

90

360

180

Flux in the generator rotor


is produced by feeding
DC supply in the field
coils, thus forming a 2
pole magnet of rotor

The Equipment for supply, control and monitoring of this


DC supply is called the Excitation system

August 21, 2015

TYPES OF EXCITATION
EXCITATION SYSTEM

ROTATING
SYSTEM

Conventional
Rotating
machines

August 21, 2015

STATIC
SYSTEM

High frequency
excitation

Brushless
Excitation System

EXCITATION SYSTEM
REQUIREMENT
Reliability
Sensitivity and fast response
Stability
Ability to meet abnormal conditions
Monitoring and annunciation of parameters
User friendliness

August 21, 2015

COMPONENTS OF TYPICAL
EXCITATION SYSTEM
Input and output interface , Aux. power supply, FB
AVR: At least two independent channels
Follow up control and changeover
Excitation build up and Field Discharging system
Cooling / heat dissipation components
Limiters
Protective relays
Testing , Monitoring and alarm / trip initiation
Specific requirements :
Field Flashing, Stroboscope, PSS,
August 21, 2015

STATIC EXCITATION SYSTEM ( 200 MW)

575 v

AVR
AUTO

15.75 kV

MAN

FB
FF
FDR

415 v AC
August 21, 2015

10

Static excitation system

Excitation power from generator via excitation transformer. Protective relays for
excitation transformer

Field forcing provided through 415 v aux supply

Converter divided in to no of parallel (typically4 ) paths. Each one having separate


pulse output stage and air flow monitoring.

Two channels : Auto & manual, provision for change over from Auto to Manual
Limiters : Stator current limiter, Rotor current limiter, Load angle limiter etc.
Alternate supply for testing

August 21, 2015

11

Static excitation system


GT

Field Breaker

EXC TRFR
18KV/700V
1500KVA

THYRISOR
BRIDGE

FIELD

voltage regulator

GENERATOR

Crow
Bar

From TGMCC- C

Non linear
resistor

Field
discharge
Resistor

Pre Excitation

415/40V,10KVA
August 21, 2015

12

Field flashing

For start up DC excitation is fed to the field from external source like
station battery or rectified AC from station Ac supply .
Filed flashing is used to build up voltage up to 30 %.
From 30 to 70 % both flashing and regulation remains in circuit.
70 % above flashing gets cut-off

August 21, 2015

13

BRUSH
GEAR

August 21, 2015

14

August 21, 2015

15

Brushless excitation
FIELD BREAKER

R
Y

ARMATURE

ROTATING
DIODES

FIELD
(PM)
PILOT
EXCITER
August 21, 2015

MAIN
EXCITE
R

GENERATOR

16

Components of Brush less Excitation


System
Three Phase Main Exciter.
Three Phase Pilot Exciter.
Regulation cubicle
Rectifier Wheels
Exciter Coolers
Metering and supervisory equipment.

August 21, 2015

17

BRUSHLESS EXCITATION SYSTEM (500 MW)

AVR

August 21, 2015

21 KV

18

Brushless Excitation System


Eliminates Slip Rings, Brushgear and all problems associated with
transfer of current via sliding contacts
Simple, Reliable and increasingly popular system the world over,
Ideally suited for large sets
Minimum operating and maintenance cost
Self generating excitation unaffected by system fault/disturbances
because of shaft mounted pilot exciter
Multi contact electrical connections between exciter and
generator field
Stroboscope for fuse failure detection
Rotor Earth fault monitoring system
August 21, 2015

19

Brushless Excitation system


Rotor E/F monitoring system
alarm 80 K, Trip 5 K
Stroboscope for thyristor fuse monitoring
(one fuse for each pair of diodes, )
Auto channel thyristor current monitor
For monitoring of thyristor bridge current , and initiating
change over to manual.
Auto to Manual changeover in case of Auto channel power
supply, thyristor set problem, or generator volts actual value
problem

August 21, 2015

22

Excitation Power Requirement

Unit
capacity
MW

Excitation
Current at
Full Load

Excitation
Voltage at
full load

Ceiling
Volts

200/ 210

2600

310

610

500

6300

600

1000

August 21, 2015

23

PMG

August 21, 2015

24

DIFFERENCES BETWEEN BRUSHLESS AND STATIC


EXCITATION SYSTEMS
S.NO

Description

Brushless Excitation

Type of system.

Brushless system gets activated


with pilot exciter, main exciter
and rotating diodes.

Static excitation system uses


thyristors & taking supply
from output of the generator

Dependency on external supply.

No external source requirement


since pilot exciter has
permanent magnet field.

Field flashing supply required for


excitation build up.

Response of the excitation


system.

Slower than static type since control


is indirect (on the field of main
exciter) and magnetic
components involved.

Very fast response in the order of


40 ms. due to the direct
control and solid state
devices employed.

Requirement of additional
bearing and increase of
turbo generator shaft length.

One additional bearing and an


increase in the shaft length are
required.

No additional bearing and increase


in shaft length are required.

Maintenance.

Less since slip rings and brushes


are avoided.

More since slip rings and brushes


are required. Also over hang
vibrations are very high
resulting in faster wear and
tear.

August 21, 2015

Static Excitation

25

MAIN EXCITER

August 21, 2015

26

EXCITER ROTOR

August 21, 2015

27

EXCITER COOLING
VAPOUR EXHAUST

COOLER

August 21, 2015

28

GENERATOR
I

XG
EF =

EF

I . XG + VT

VT

Equivalent circuit of Generator


August 21, 2015

29

GENERATOR
Phasor diagram of the Generator
Ef

IL.Xd

VT

IL

August 21, 2015

30

GCB

GENERATOR

GT

G
Xd

Ef

XT

VT

Vbus

Generator + Generator Transformer Eq. Ckt.


August 21, 2015

31

GENERATOR
Vector Diagram of Generator and GT
connected to an infinite bus

EF
IL.Xd

VT
Vbus

IL.XT

IL

August 21, 2015

32

GENERATOR
In the equivalent Circuit and Phasor diagram, the notations used have the
following description:
Vbus

Infinite bus voltage

VT

Generator Terminal Voltage

EF

Induced Voltage (behind synchronous


Impedance) of Generator, proportional
to excitation.

Xd

Direct axis sync. Reactance assumed


same as quadrature axis sync.
Reactance

XT

Transformer reactance

IL

Load Current

Phase angle

August21, 2015

Torque Angle (rotor/load angle)

33

GENERATOR
POWER ANGLE EQUATION
Referring to the phasor diagram on slide no.14;
Sin / IL.{Xd+XT}

Sin (90+ ) / EF

Putting Xd+XT =X, and multiplying both sides by VIL,


V Sin /X

VIL Cos / EF

{Sin (90+ ) = Cos }


or,
(EF . V / X) Sin

VIL Cos

Pmax

EF . V / X

Note that the Electrical Power Output varies as the Sin of Load angle

August 21, 2015

34

August 21, 2015

35

Physical
significance
of load angle

Stator
mag.
axis

red
N
ROTOR

Rotor
mag.
axis
yellow

STATOR

blue
August 21, 2015

36

P2

Excitation constant;
EF2

Steam flow increased

P1

Power output P1 to P2
EF1

2
1

2
I2

Vbus

Locus of
Constant
Excitation

I1
ACTIVE POWER CHANGE
August 21, 2015

37

Locus of P = const.
Steam Flow constant;
Excitation increased
Power output Constant

EF2

EF1

2
1

2
I2

Vbus

Locus of
Constant
Excitation

I1
I Cos = Constant
August 21, 2015

38

EXCITATION CHANGE

Excitation Control

August 21, 2015

39

AVR

August 21, 2015

40

TYPES OF AVR SYSTEMS


Single channel AVR system
Dual channel AVR system
Twin channel AVR system

August 21, 2015

41

Single channel AVR system


Here we have two controllers one is automatic and the other is
manual and both the controllers are fed from the same supply
The AVR senses the circuit parameters through current
transformers and voltage transformers and initiates the control
action by initiating control pulses , which are amplified and sent
to the circuit components
The gate controller is used to vary the firing angle in order
to control the field current for excitation
In case of any fault in the automatic voltage regulator the control
can be switched on to the manual controller.
August 21, 2015

42

Dual channel AVR system


Here also we have two controllers in the same manner as the
previous case i.e. one automatic voltage controller and one manual
controller
But here in contrary to the previous case we have different power
supply, gate control and pulse amplifier units for each of the
controllers
Reliability is more in this case than previous one since a fault in
either gate control unit or pulse amplifier or power supply in single
channel AVR will cause failure of whole unit, but in dual channel
AVR this can be avoided by switching to another channel.
August 21, 2015

43

Twin channel AVR system


This system almost resembles the dual channel AVR but the only
difference is that here we have two automatic voltage regulators
instead of one automatic voltage regulator and one manual Voltage
regulator
This system has an edge over the previous one in the fact that in case
of failure in the AVR of the Dual voltage regulator the manual system
is switched on and it should be adjusted manually for the required
change in the system and if the fault in AVR is not rectified in
reasonable time it will be tedious to adjust the manual voltage
regulator

August 21, 2015

44

Twin channel AVR system


In Twin channel AVR both the AVRs sense the circuit parameters
separately and switching to other regulator incase of fault is much
easier and hence the system is more flexible than the other types.
Generally switching to manual regulator is only exceptional cases
like faulty operation of AVR or commissioning and maintenance
work and hence we can easily manage with one AVR and one
manual regulator than two AVRs. So Twin channel AVR is only
used in very few cases and generally Dual channel AVR is
preferred.
August 21, 2015

45

AVR
There are two independent control systems
1. Auto control
2. Manual control
The control is effected on the 3 phase output of the pilot
exciter and provides a variable d.c. input to the main exciter

The feedback of voltage and current output of the generator


is fed to avr where it is compared with the set point
generator volts se from the control room
August 21, 2015

46

AVR
The main components of the voltage Regulator are two closed
loop control systems each followed by separate gate control unit
and thyristor set and de excitation equipment
Control system 1 for automatic generator voltage control
(AUTO) comprises the following

August 21, 2015

47

AVR
Generator voltage control
The output quantity of this control is the set point for a following.

Excitation current regulator, controlling the field current of


the main exciter

Circuits for automatic excitation build-up during start up


and field suppression during shut-down
August 21, 2015

48

AVR
This equipment acts on to the output of the generator voltage,
control, limiting the set point for the above excitation current
regulator. The stationary value of this limitation determines the
maximum possible excitation current set-point (field forcing
limitation);
Limiter for the under-excited range (under excitation limiter),
Delayed limiter for the overexcited range (over excitation limiter)

August 21, 2015

49

AVR
In the under excitation range, the under
excitation ensures that the minimum excitation
required for stable parallel operation of the
generator with the system is available and that
the under -excited reactive power is limited
accordingly

August 21, 2015

50

AVR
The set-point adjuster of the excitation current
regulator for manual is tracked automatically (followup control) so that, in the event of faults, change over
to the manual control system is possible without delay
Automatic change over is initiated by some special
fault condition. Correct operation of the follow-up
control circuit is monitored and can be observed on a
matching instrument in the control room. This
instrument can also be used for manual matching.
August 21, 2015

51

AVR
FAULT INDICATIONS
The following alarms are issued from the voltage
regulator to the control room.
AVR fault
AVR automatic change over to MANUAL
AVR loss of voltage alarm
August 21, 2015

52

AVR
The current feedback is utilized for active and
reactive power compensation and for limiters

There are 3 limiters


1.Under excitation limiter
2.Over excitation limiter
3. V/F limiter
August 21, 2015

53

Excitation Interlocks
Preconditions for Excitation
ON
Excitation ON command
N>90%
Protection
Of
FCB Of feedback

5s delay

Excitation
ON

External trip
GCB is OFF

August 21, 2015

54

Excitation OFF Interlocks


Exc. OFF from Field
flashing

Exc OFF command


GCB OFF
N>90%

Delay 1sec

Exc OFF

GCB OFF
External trip

August 21, 2015

55

Capability Curve
Capability Curve relates to the limits in which a generator can
Operate safely.
Boundaries of the Curve within with the machine will operate
safely
Lagging Power Factor/Overexcited region
Top Section Relates to Field Heating in Rotor Winding
Right Section Relates to Stator current Limit
Straight line relates to Prime Mover Output
Leading Power Factor/ Underexicted region
Lower Side relates to Stator end ring Limit
Further down relates to Pole slipping
August 21, 2015

56

August 21, 2015

57

LIMITERS

Over excitation limiter


Under excitation limiter
Rotor angle limiter
Stator current limiter
V/F limiter

August 21, 2015

58

Over excitation limiter


Line voltage drops due to more reactive power requirement ,
switching operations or faults
AVR increases
generator excitation to hold the voltage
constant
Line voltage drops , thermal over loading of generator can
result
OEL is automatic limitation of generator excitation by lowering
the generator voltage (otherwise the set point of generator
voltage is reduced in time or the transformation ratio of the GT
is to be adjusted )
OEL permits excitation values above the normal excitation and
extended to max excitation (for field forcing) for a limited time,
so as to permit the generator to perform the grid stabilization in
response to short drops in line voltage
When IF >110% of Ifn , the OEL and Field forcing limiter are
active
August 21, 2015
59

Under Excitation limiter


Function is to correct the reactive power when the excitation
current falls below minimum excitation current value required
for stable operation of generator
Activation of UEL takes over the control from the closed loop
voltage control, acting via a max selection
The limit characteristic is adjustable (shifted parallel)
I reactive ref is compared with the measured I reactive , the
error is fed to P- amplifier. When the value drops below the
characteristic the amplified diff signal causes the field current to
increase
For commissioning purpose provision is made to mirror the
characteristic in the inductive range, this allowing both the
direction in which the control signal acts and the blocking of the
set point generators is to be changed
August 21, 2015

60

Rotor Angle Limiter


Stable operation rotor angle <900, for higher degree of stability
a further margin of 10-12% is normally provided
RAL gives the o/p as
permissible I reactive =F ( I active)
Characteristic is shifted linearly as a function of generator
voltage
Permissible I reactive is compared with the measured value and is
fed to the limit controller when the I reactive achieved value drops
below the permissible value then the limiter comes in action
and I reactive
August 21, 2015

61

Stator current limiter


During operation at high active power P and / low voltage the
stator current of the generator tends to rise beyond its rated
value and can cause the thermal overloading of stator, in spite
of the action of the UEL
An additional stator current limiting controller acting on the
generator excitation is provided as a safe guard against such
states of operation
SCL always monitors the stator current measured value for
crossing the rated stator current
SCL permits small time over load but comes in action thereafter
and influences the effective generator voltage set point- to
reduce the Q till the stator current is brought down below the
rated value
Change in generator voltage set point is not blocked when SCL
active
SCL does not operate near the unity PF because near this value
any limiter would cause oscillations
August 21, 2015

62

V/F limiter
Also known as over fluxing limiter
It is the protection function for the GT
V/F ratio , eddy current , the local eddy current causes
thermal over loading of GT
In DVR mode V/F ratio is continuously monitors the limit
violation
In case V/F ratio crosses the limit characteristic, the upper limit
as the effective AVR set point is reduced as a function of V/F
ratio
This limiter is used when it is required to keep the unit operating
even in case of substantial frequency drops , for instance in
order to prevent complete breakdown of the system, a V/F
limiter is used to lower the voltage proportional with frequency
August 21, 2015
63
drop

PRIORITY STRUCTURE OF AVR


1st priority

Rotor current limiter


UN1024

Stator current li miter


inductive
UN0027

2 nd priority

Load angle limiter


UN1043

Stator current limiter


Capacitive
UN0027

3 rd priority

Voltage regulator
UN-2010

August 21, 2015

64

Field failure protection


Loss of generator field excitation under normal
running conditions may arise due to any of the
following condition.
1. Failure of brush gear.
2.unintentional opening of the field circuit breaker.
3. Failure of AVR.
When generator on load loses its excitation , it starts to
operate as an induction generator, running above
synchronous speed.cylindrical rotor generators are
not suited to such operation , because they don't have
damper windings able to carry the induced currents,
consequently this type of rotor will overheat rather
quickly.