Beruflich Dokumente
Kultur Dokumente
High Impedance
Low Impedance
Restricted E/F
Biased
Pilot Wire
Types of Protection
D - Distance
• For Transmission and Sub-transmission Lines
and Distribution Feeders,
• Also used as back-up protection for
transformers and generators without
signaling with signaling to provide unit
protection e.g.:
– Time-stepped distance protection
– Phase comparison for transmission lines
– Directional comparison for transmission lines
Types of Protection
E - Miscellaneous:
• Under and over voltage
• Under and over frequency
• A special relay for generators, transformers, motors
etc.
• Control relays: auto-reclose, tap change control, etc.
• Tripping and auxiliary relays
Design Criteria/Characteristics
Economy
Simplicity
Speed
Reliability
Sensitivity
Selectivity
Design Criteria/Characteristics
• Reliability
– Operate dependably and in healthy operating
condition when fault conditions occur, even after
remaining idle for months or years.
• Selectivity
– Clearly discriminate between normal and
abnormal system condition to avoid unnecessary,
false trips.
• Sensitivity
– Ability to distinguish the fault condition, although
the different between fault and normal condition
is small.
Design Criteria/Characteristics
• Speed
– Fault at any point in the system must be
detected and isolated rapidly to minimize fault
duration and equipment damage. Any intentional
time delays should be precise.
• Economy
– Provide maximum protection at minimum cost
• Simplicity
– Minimize protection equipment and circuitry
Economic Factor
• Total cost should take account of :
– Relays, schemes and associated panels and panel wiring
– Setting studies
– Commissioning
– CTs and VTs
– Maintenance and repairs to relays
– Damage repair if protection fails to operate
– Lost revenue if protection operates unnecessarily
Economic Factor
• The cost of protection is equivalent to an insurance policy
against damage to plant, and loss of supply and customer
goodwill.
• Acceptable cost is based on a balance of economics and
technical factors. Cost of protection should be balanced
against the cost of potential hazards.
• There is an economic limit on what can be spent.
• MINIMUM COST :Must ensure that all faulty equipment is
isolated by protection.
Relationship between reliability of supply, its
value and cost to the consumer
System Protection Components
• Transducer / Instrument Transformer
• Relay
• Circuit Breaker
System Protection Components
Function:
• Transducers/Instrument Transformers
– Provide low current and voltage, standardized levels suitable for
the relays operation.
• Relays
– Discriminate between normal operating and fault conditions.
– When current exceed a specified value relay will be operated and
cause the trip coil of CB to be energized/open their contact.
• Circuit Breakers
– Open the line
System Protection Components
System Protection Components
System Protection Flow
voltage or current rise from normal condition
circuit isolation
A P1 2 C P2
B
4
1 3
D
A P1 2 C P2
Fault at P1 = A, B, C
Fault at P2 = A, B, C,D, E
Example
a) If three circuits breakers are added at the tap
point 2, how would the zones of protection be
modified? Which circuit breakers will operate for
fault at P1 and P2 under these conditions?
1 3
A P1 2 C P2
B
4
1 3
2
D
A P1 F G C P2
Fault at P1 = A, F
Fault at P2 = C,D,E,G
Zone Discrimination
Voltage/Potential
Transformer
(VT/PT)
Voltage Transformers
Voltage Transformers
Voltage Transformers
HV and EHV
• Capacitor-coupled VT (CVT)
– C1 & C2 are adjusted, so that a few kVs of
voltage is obtains across C2
– Then, stepped down by T
• VTs must be fused or protected by MCB.
Voltage Transformers
Voltage Transformers
• VT ratios:
– ratio of the high voltage/secondary
voltage
1:1 2:1 2.5:1 4:1
5:1 20:1 40:1 60:1
80:1 100:1 200:1 300:1
400:1 600:1 800:1 1000:1
2000:1 3000:1 4500:1
Current Transformers
• CT is an instrument transformer that is used
to supply a reduced value of current to
meters, protective relays, and other
instruments.
• The primary winding consist of a single turn
which is the power conductor itself.
• CT secondary is connected to a current-
sensing device with zero impedance.
Current Transformers
• CTs ratio(secondary current rating is 5A)
50:5 100:5 150:5 200:5
250:5 300:5 400:5 450:5
500:5 600:5 800:5 900:5
1000:5 1200:5
• CTs also available with the secondary rating
of 1A
Current Transformers
Current Transformers
Reclosers and Fuses
• Automatic reclosers are commonly used for
distribution circuit protection.
• Recloser: self-controlled device for automatically
interrupting and reclosing an AC circuit with preset
sequence of openings and reclosures
• Have built-in control to clear temporary faults and
restores service with momentary outages.
• Disadvantages:
– increase hazard when circuit is physically contacted by
people.
– Recloser should be locked out during live-line maintenance.
Reclosers and Fuses
1. An upstream fuse/relay
has detected a fault
2. Downstream system
isolated by fuse or
breaker
3. Automatic re-closing
after delay successful if
fault not permanent
Relays
• Discriminate between normal operating
and fault conditions.
• Type of Relays
– Magnitude Relay
– Directional Relay
– Distance/Ratio Relay
– Differential Relay
– Pilot Relay
Magnitude Relays
• Also called as Overcurrent Relay
• Response to the magnitude of input quantities ie.
current.
• Energize CB trip coil when the fault current magnitude
exceeds a predetermined value or trips when a current
rises above a set point (pick-up current).
• If it is less than the set point value, the relay remains
open, blocking the trip coil.
• Time-delay Overcurrent Relay also have the same
operating method but with an intentional time-delay.
Directional Relays
• Responds to fault only in one direction, either to the
left or to the right of its location
• Operation depends upon the direction (lead or lag) of
the fault current with respect to a reference voltage.
• The directional element of these relays checks the
phase angle between the current and voltage of one
phase, and allows the overcurrent unit to operate if
this phase angle indicates current in the reverse
direction.
Ratio Relays
• Operate for certain relations between the
magnitudes of voltage, current and the phase angle
between them.
• Measures the distance between the relay location
and the point of fault, in term of impedance,
reactance and admittance.
• Respond to the ratio of two phasor quantities as
example Voltage and Current (Z = V/R)
• Also called impedance or distance relay
Differential Relays
• Respond to the vector difference between two currents within
the zone protection determined by the location of CTs.
• Not suitable for transmission-line protection because the
terminals of a line are separated by too great a distance to
interconnect the CT secondaries.
• For the protection of generators, transformers, buses,
• Most differential-relay applications are of the ‘current-
differential’ type.
Differential Relays
Relay
• Fault occur at X
• Suppose that current flows through the primary circuit either to
a load or to a short circuit located at X.
• If the two current transformers have the same ratio, and are
properly connected, their secondary currents will merely
circulate between the two CTs as shown by the arrows, and no
current will flow through the differential relay.
Differential Relays
Relay
A B C
ZA
ZB
A B C