POWER SYSTEM

FAULTS

Introduction

Any abnormal conditions which causes flow of huge


current in the conductors or cable through inappropriate
paths in the circuit can be defined as a fault. In normal
operating conditions all the circuit elements of an
electrical system carry currents whose magnitude
depends upon the value of the generator voltage and
the effective impedances of all the power transmission
and distribution system elements including the
impedances of the loads usually relatively larger than
other impedances.

Introduction

Modern electric systems may be of great complexity


and spread over large geographical area. An electric
power system consists of generators, transformers,
transmission lines and consumer equipment.. The
system must be protected against flow of heavy short
circuit currents, which can cause permanent damage to
major equipments, by disconnecting the faulty section
of system by means of circuit breaker and protective
relaying

Such conditions are caused in the system accidentally


through insulation failure of equipment or flashover of lines
initiated by a lightning stroke or through accidental faulty
operation.
The safe disconnection can only be guaranteed if the
current does not exceed the capability of the circuit
breaker. Therefore, the short circuit currents in the network
must be computed and compared with the ratings of the
circuit breakers at regular intervals as part of the normal
operation planning.

Introduction

The short circuit currents in an AC system are


determined mainly by the reactance of the alternators,
transformers and lines upto the point of the fault in the
case of phase to phase faults. When the fault is
between phase and earth, the resistance of the earth
path play an important role in limiting the currents.

Introduction

Balanced three phase faults may be analyzed using an


equivalent single phase circuit. With asymmetrical three
phase faults, the use of symmetrical components help
to reduce the complexity of the calculations as
transmission lines and components are by and large
symmetrical, although the fault may be asymmetrical.
Fault analysis is usually carried out in per-unit
quantities as they give solutions which are somewhat
consistent over different voltage and power ratings, and
operate on values of the order of unity.

Introduction

Depending on the location, the type, the duration, and


the system grounding, short circuits may lead to
electromagnetic interference with conductors in the
vicinity (disturbance of communication lines),
stability problems,
mechanical and thermal stress (i.e. damage of
equipment, and or personnel

Fault Types
The fault can be classified due to the NATURE of the fault
as
1- Permanent
2- Transient
Or due to PARTICIPATED PHASES as
1- Phase-Earth
2- Phase-Phase
3- Phase-Phase-Earth
4- Three-Phase or Three-Phase-Earth

Fault Types
Fault may be categorized broadly into 2 types:
Symmetrical or balanced faults
Asymmetrical or unbalanced faults

Symmetrical or balanced faults

Symmetrical or balanced faults


In normal operating conditions, a three-phase power
system can be treated as a single-phase system when
the loads, voltages, and currents are balanced.

Symmetrical or balanced faults

A three phase fault is a condition where either (a) all


three phases of the system are short circuited to each
other, or (b) all three phase of the system are earthed.

Symmetrical or balanced faults

This is in general a balanced condition, and we need to


only know the positive-sequence network to analyze
faults. Further, the single line diagram can be used, as all
three phases carry equal currents displaced by 120.
The positive sequence system is that system in which the
phase or line currents or voltages attain a maximum in the
same cyclic order as those in a normal supply e.g.
assuming conventional counter clockwise rotation, then
the positive phase sequence phasors are as shown below
in the figure

Symmetrical or balanced faults

The negative sequence system is that system in which


phasors still rotate anti-clockwise but attain maximum
value in the reverse order as shown in the figure. This
sequence only arises in the case of occurrence of an
unsymmetrical fault.

Symmetrical or balanced faults


Typically, only 5% of the initial faults in a power system,
are three phase faults with or without earth. Of the
unbalanced faults, 80% are line-earth and 15% are
double line faults with or without earth and which can
often deteriorate to 3 phase fault. Broken conductor
faults account for the rest.
CAUSES : System Energisation with Maintenance Earthing
Clamps still connected.
1 Faults developing into 3 Faults

Unsymmetrical or Unbalanced
faults
Unbalanced Faults
Unbalanced Faults may be classified into
SHUNT FAULTS and SERIES FAULTS.
SHUNT FAULTS:
Line to Ground
Line to Line
Line to Line to Ground

Unbalanced faults

Unbalanced faults

Causes :
1) Insulation Breakdown
2) Lightning Discharges and other Overvoltages
3) Mechanical Damage
During unbalanced faults, symmetry of system Is lost
therefore single phase representation is no longer Valid

Unbalanced faults
SERIES FAULTS OR OPEN CIRCUIT:
Single Phase Open Circuit
Double Phase Open Circuit
Causes :
1) Broken Conductor
2) Operation of Fuses
3) Maloperation of Single Phase Circuit Breakers

A fault is characterized by: of Faults


Characteristics

Magnitude of the fault current


Power factor or phase angle of the fault current

The magnitude of the fault current depends upon:


The capacity and magnitude of the generating sources
feeding into the fault
The system impedance up to the point of fault or source
impedance behind the fault
Type of fault
System grounding, number and size of overhead ground wires

Characteristics of Faults

Fault resistance or resistance of the earth in the case


of ground faults and arc resistance in the case of both
phase and ground faults

The phase angle of the fault current is dependent upon:


For phase faults: - the nature of the source and
connected circuits up to the fault location and
For ground faults: - the type of system grounding in
addition to above.

Necessity for fault calculations


Fault calculations are done primarily for the following:
To determine the maximum fault current at the point of
installation of a circuit breaker and to choose a
standard rating for the circuit breaker (rupturing)
To select the type of circuit breaker depending upon
the nature and type of fault.

Necessity for fault calculations

To determine the type of protection scheme to be


deployed.
To select the appropriate relay settings of the
protection scheme.
To co-ordinate the relay settings in the overall
protection scheme of the system

Procedures and Methods

To determine the fault current at any point in the


system, first draw a one-line diagram showing all of the
sources of short-circuit current feeding into the fault, as
well as the impedances of the circuit components.
To begin the study, the system components, including
those of the utility system, are represented as
impedances in the diagram.

Procedures and Methods

It must be understood that short circuit calculations are


performed without current limiting devices in the
system. Calculations are done as though these devices
are replaced with copper bars, to determine the
maximum available short circuit current. This is
necessary to project how the system and the current
limiting devices will perform.

Procedures and Methods

To start, obtain the available short-circuit KVA, MVA, or


SCA from the local utility company.

The

utility estimates the System can deliver a


shortcircuit of Y MVA at the primary of the
transformer. Since the X/R ratio of the utility
system is usually quite high, only the reactance
need be considered.
With this available short-circuit information,
begin tomake the necessary calculations to
determine the fault current at any point in the
electrical system.

Procedures and Methods


The calculation is not only limited to present system
requirements but also meet:
The future expansion schemes of the system such as
addition of new generating units
Construction of new transmission lines to evacuate
power.
Construction of new lines to meet the load growth and
or Construction of interconnecting tie lines

Procedures and Methods

Basically, there are two approaches to fault


calculations. These are:
(a) Actual reactance or impedance method
(b) Percentage reactance or impedance method or per
unit (p.u) reactance or impedance method.
Machine and Transformer impedance or reactance are
always noted in percentage values on the nameplate.
Hence the latter method is considered for our
calculation.

Per Unit and Percentage System


Definitions
The per unit value is defined as the ratio of the actual
quantity to a reference quantity which is often referred
to as base quantity. The base quantity is an arbitrary or
convenient reference value but of the same unit as the
actual value.
i.e. per unit = Actual quantity
Base quantity(value),

Per Unit and Percentage System


formulae

Both the actual and base quantities can be scalar or


complex value but should be of the same units e.g
Amps, Ohms, Watts, Vars and VA. The per unit values
are therefore scalar quantities i.e. non- dimensional.

Per Unit and Percentage System


formulae
Base value
For a three phase power system, let Ib, KVb and MVAb
be the base current, line voltage and power respectively.
The base impedance, Zb
= KVb
3 x Ib
The base MVA,
= 3 x KVb x KVb
3 x Zb
Zb
= (KVb)2
MVAb

MVAb

= 3 x Ib x KVb

Per unit

Let Z be the actual impedance in ohms,


Z per unit(pu)
= Z
Zb
=
Z x MVAb
(KVb)2
Changing of base
Let Ib1, KVb1 and MVAb1 be the old base values and
Ib2, KVb2 and MVAb2 the new base values.

Per unit
Z1(pu)

Z x MVAb1
(KVb1)2
where; Z = actual value and
Zb = (KVb1)2
MVAB1
therefore,
Z = Z1(pu) x MVAB1
(KVb1)2
Z2(pu) =
Z x MVAb2
(KVb2)2

Per unit
Z2(pu)

1)

2)

= = Z1(pu) x (KVb1) 2 x MVAb2


MVAB1
(KVb2)2

If KVb1 = KVb2

then, Z2(pu) = Z1(pu) MVAb2


MVAb1
If MVAb1 = MVAb2 then, Z2(pu) = Z1(pu) (KVb1) 2
(KVb2)2

Examples
Example1
(1) To calculate the p.u impedance and % impedance of
a transmission line at 100 MVA
base Line voltage
330 KV
Line length
200 Kms
Line resistance /Km = 0.06 ohms/Km
Line reactance /Km = 0.4 ohms/Km

Examples
Z=
R + jX
For the 200kms line length
Z =
200 (0.06 + j 0.4)
=
12 + j 80
|Z| = [(12) 2 + (80) 2] = 80.895 ohms

Examples
Zp.u

%Z

Zx

80.895 x 100
(330) 2
0.0743 p.u
0.074 x 100
7.43

=
=
=

MVA base
(KV) 2 base

Examples
Example2
To calculate the p.u impedance to a 100 MVA base
Given four generators; 90MVA, 11KV of 15%
impedance each connected to step up transformers of
90MVA 11KV/330KV of 14% impedance. Calculate the
fault current at F.

Examples
Assumed MVA = 100
%Z generators
= 15 on 90 MVA base
or Zg p.u
= 0.15 on 90 MVA base
Zg p.u on 100 MVA base will be:
(Zg p.u) base2 =

(Zg p.u) base1 x MVA base2

MVA base1
(Zg p.u) 100 =

0.15 x 100

90
0.167

Examples
%Z transformers = 14 on 90 MVA base
or Zt p.u
= 0.14 on 90 MVA base
Zt p.u on 100 MVA base will be:
(Zt p.u) base2

(Zt p.u) base1 x MVA base2


MVA base1

(Zt p.u) 100

= 0.14 x 100
90
= 0.156

Examples
The system reduces as follows

Examples
Ztotal

= 0.323
4
= 0.08075

Total p.u impedance at F = 0.08075 = Ztotal


Fault MVA at F =
=
=

Base MVA
Ztotal
100 MVA
0.08075
1238.4 MVA

Examples
Current at F =

Fault MVA x (10) 3


3 x system voltage (KV) at point of fault

=
=

1238.4 x (10) 3
3 x 330
2166.638Amps

Examples
Example2
To calculate the fault MVA and fault current of a system
at 33KV given the fault level at the 330KV bus as
5000MVA

Examples
Assume 100 MVA base
Fault MVA = Base (MVA)
Z p.u
5000
= 100
Zp.u
Z p.u
= 100 =
0.02 p.u
5000 (source impedance in p.u)
Zp.u of each 330/132KV 80MVA Transformer at 100MVA base
Zp.u =
12
x
100 = 0.15
100
80

Examples
Z1 of 132KV Trans. line

= 15 + j 60 = R + jX
= [(15) 2 + (60) 2 ]
=
61.85 0hms

Z1 p.u. of this line

=
=
=

(Z) MVA base


(KV) 2
(61.85) x 100
(132) 2
0.355 p.u

Examples
Impedance of 132/33 KV, 25MVA transformer on 100
MVA base at %z =10
Zt1
=
100 x 10%

or Zt1 =

25
40%
0.4 p.u

Examples

The system now reduces as follows:

This can be further reduced to:

Examples

Total system impedance up to F


= 0.85p.u
Fault MVA at F
=
100
0.85
=
117.6 MVA
Fault current at F =
117.6 x 1000
3 x 33
=
2057.466 Amps
or 2.058 KA