Sie sind auf Seite 1von 25

Power Distribution 132kvEHT,Connecting

Transformer Bus-Bar
Indicator
Temperature HT11kv.Bushing &
Connecting Bars
Conservator
Tank
Oil Cooling
Buchholz Radiator
Relay

Tap-Changer Bushing
& coupling
connecting Pressure
gears Relieve Valve

TAP
Transformer Transformer
Yard KESC TRAINING CENTRE
Side View of the
Power Transformer
Cooling Radiator Provided both side
Transformer
On every Section the Fan are provided
Setting of the Fans

KESC TRAINING CENTRE


BUSHING OF THE
TRANSFORMER

11KV(LT BUSHING) OF
THE TRANSFORMERS
132KV(HT BUSHING OF THE
POWER TRASFORMER)

KESC TRAINING CENTRE


Buchholz Relay
Relieve
valve

Box
Oil pipe CONTACT
from BOX
conservator
s Test
contact

Pipe to Main
Tank
buchholz

Calibration

Oil level
glass
KESC TRAINING CENTRE
TAP-CHANGER
Remote
Tap-Changing Mechanism Position

Automate DC
Switch

Counter Dial (Tap Number)


House for
Handle

KESC TRAINING CENTRE


Tap-Changer

KESC TRAINING CENTRE


BREATHER

Window to View the


color of the silica gel
Blue Color Show the
Healthiness of silica-
gel
After moisture
absorption the color
become PINK

KESC TRAINING CENTRE


11KV BUS-BAR

LT-BUSHING
11KV CABLE
CONNECTED
WITH BUSBAR.
RED
YELLOW
BLUE

KESC TRAINING CENTRE


Oil Temperature Indicator
Oil temperature indicators is
use to monitor oil
temperature.
Usually Three Types of
temperature indicators are
used
Without Contacts
With two Contact First Alarm
and Tripping
With 04-CONTACT 1ST Fan
Off,2nd Fan On,3RD alarm
&Trip

KESC TRAINING CENTRE


KESC TRAINING CENTRE
OIL TEMPERATURE INDICATOR

Resetting Temperature
Knob
Of the Oil

KESC TRAINING CENTRE


FORCED COOLING FANS

Position of the
forced fan
installed
Below the
Radiators
automation

KESC TRAINING CENTRE


Frequency,power,kilovolt meter
Installed at the cubical of control
panel

KESC TRAINING CENTRE


Control panel of power transformer

KESC TRAINING CENTRE


SLECTOR (SWITCH)
Automatetic
Manual
Off

Parallel
Individual

KESC TRAINING CENTRE


PRESSURE RELIEF DEVICE
TAP Changer MAIN_TANK PRESS RELIFE
Transformer Device. VALVE of Power Transformer

MR-Moving Mechanism
(TAP Transformer) KESC TRAINING CENTRE
Pressure Relief Device
Pressure relief device
is used to give a relief
to the oil pressure
built up in case of
short circuit occurs
inside the
transformers
The danger of
explosion or Tank
deformation exist.

KESC TRAINING CENTRE


Hand valve between conservator
to tap changer

Oil Pipe of the


Conservator tank
to Main Tap
Hand Valve of
conservator to
main TANK to
attain control
during shutdown.

KESC TRAINING CENTRE


OIL INDICATOR FOR TAP
CHANGER

P
R
E
S
S
U
R
E

R
E
L
I
E
V
CONTACT ON
PRESSURE
RELIEV Tap Changer position on top
of transformers

KESC TRAINING CENTRE


KESC TRAINING CENTRE
Oil drain Position, of the
power-transformer
Sample oil
TOP OILDRAIN- FROM TANK

MIDDLE

BOTTOM CONNECTION OF
CENTEFUGING
MACHINE

KESC TRAINING CENTRE


Surge Arrestors & Cable
Termination

Arraster(surge)

EHT Bushing
(connected to tras
B/B)

Surge Counter 132kv cable


Termination

KESC TRAINING CENTRE


Mounting of Bushing on the
transformers

11kv Bushing
mounted EHT HOUSING

EHT
bushing
connected
to Main
Tank EHT Torture Short-Circuit

KESC TRAINING CENTRE


Home Assignment for viva
1-How many types of relays installed
at
a-Transformer b-Breaker c-Feeders
Signal Indication.
2-Essential Parts Of
Power Transformer and Breakers
3-Equipment Installed at Grid-station.
4-Purpose & Function of equipment
installed at EHT Grid-Station.

KESC TRAINING CENTRE


Question related TEST point of view.

KESC TRAINING CENTRE

Das könnte Ihnen auch gefallen