Sie sind auf Seite 1von 24

Sepam 1000+

Advanced UMI

Integrated or remote Advanced UMI,

Metering
Graphic LCD
display

Switchgear
diagnosis
Alarm
display

Entry of 2
passwords

Access to
parameters

Advanced UMI eng. S1000+.ppt

Reset

Access
Lamp
to settings test

Alarm
acknowledgment

2 /24

Advanced UMI
9-key keypad
BLACK current operation keys
BLUE parameter/protection setting keys
3 dual-function keys:
Operating functions
Navigation in parameter/protection setting mode
Universal icons, consistent with LV products

Advanced UMI eng. S1000+.ppt

3 /24

Advanced UMI
3 categories of users
Operator:
Access to all data in read mode only
Clear/Reset actions
Personnel qualified to set protection functions
Know the Setting code (1 key)
Operator + access to protection settings
Personnel qualified to set Sepam parameters
Know the Parameters code (2 keys)
Operator + access to protection settings + access to
Sepam parameters

Advanced UMI eng. S1000+.ppt

4 /24

Advanced UMI
Graphic LCD display
128 x 64 pixels, number of lines, size of characters and
symbols according to language versions and screens
2 versions of screen backgrounds available:
resident factory version: English
additional customized version (language / customer),
customization using SFT2840:
of the position of the system zones
of the content of the text zone

Advanced UMI eng. S1000+.ppt

5 /24

Advanced UMI
Access to measurements and
parameters
Series 20

Example: measurement loop

Advanced UMI eng. S1000+.ppt

6 /24

Current operation (blue keys)


Series 20

I1=162A RMS
I2=161A RMS
I3=163A RMS

Advanced UMI eng. S1000+.ppt

I1 I2 I3
Io
I1 I2 I3
Iav1 2 3
Imax1 2 3
T1 T8
V1 V2 V3
U12,32,13
Vo
F

RMS current measurement


residual current, digital and bargraph
phase current bargraph
average current value
peak current demand
temperature sensor
phase-to-neutral voltage
phase-to-phase voltage
residual voltage
frequency

7 /24

Current operation (white keys)


Series 20

tripI1,I2,I3,Io tripping currents (phase and residual)


unbalance
unbalance ratio (negative sequence current)
breaking dev. trip circuit supervision,nb of operation,
operating and charging time
kA
cumulative breaking current
E
thermal capacity percentage
time before starting authorization
st I stT
motor starting current and time
Nb st,waitT start inhibit time /nb of starts before inhibition
Ch
running hour counter
Vd
positive sequence voltage

Advanced UMI eng. S1000+.ppt

8 /24

Current operation (white keys)


Series 20

The Alarm key may be used to


consult the 16 most recent
unacknowledged alarms.
N.B.
The alarms are not saved in the event
of a power outage.

Advanced UMI eng. S1000+.ppt

9 /24

Current operation (white keys)

Advanced UMI eng. S1000+.ppt

10 /24

Current operation (white keys)

Advanced UMI eng. S1000+.ppt

11 /24

Current operation (white keys)

I1=162A RMS
I2=161A RMS
I3=163A RMS

Advanced UMI eng. S1000+.ppt

12 /24

Parameter and protection setting (blue keys)

main
settings
sepam info
MES
modbus
MSA
CT / VT
O1
I/O
LDC

Advanced UMI eng. S1000+.ppt

lang.,frequency,active group,remote setting,


setting mode,modif, passwords
type, version
input/output module option
communication parameter setting
analog output module option
nb , type, ratio of sensors
parameter setting output O1
input reading, output reading and testing
CB control, logic discr., choice of use of inputs

13 /24

Parameter and protection setting (blue keys)

Advanced UMI eng. S1000+.ppt

14 /24

Parameter and protection setting (blue keys)

Advanced UMI eng. S1000+.ppt

15 /24

Parameter and protection setting (blue keys)

Advanced UMI eng. S1000+.ppt

16 /24

Parameter and protection setting (blue keys)

Advanced UMI eng. S1000+.ppt

17 /24

Parameter and protection setting (blue keys)

Advanced UMI eng. S1000+.ppt

18 /24

Advanced UMI
Series 40
The same as with Sepam series 20, the
measurements and parameters are
accessed via the metering, diagnosis,
status and protection keys, but through
a first menu which is then used to select
a series of screens as presented in the
diagram opposite.

Example: Measurement loop

Advanced UMI eng. S1000+.ppt

19 /24

Advanced UMI
Metering menu

Series 40
To begin with, the
key provides access to the
metering menu.
The
and
keys are
used to move the cursor up and
down to select the chosen type
of measurements.
Use the
key again to scroll
the chosen measurement loop.

Advanced UMI eng. S1000+.ppt

20 /24

Advanced UMI
General settings menu

Series 40
The
key is used to access
to the menu containing the
different general settings entered
in Sepam.
The
and
keys are
used to move the cursor up and
down to select the chosen type
of parameter.
Use the
key again to scroll
the chosen measurement loop.

Advanced UMI eng. S1000+.ppt

21 /24

Advanced UMI
Series 40

Protection menu

The
key provides access to
the menu containing the different
Sepam protection functions.
The

Protections
I Phase
IDirectionnal
F.P

and

keys are used

I Rsidual

to move the cursor up or down to

Voltage

select the type of protection

Recloser

function.
Use the
key again to scroll
the chosen measurement loop.

Advanced UMI eng. S1000+.ppt

22 /24

Advanced UMI
Series 40

Diagnosis menu

The
key provides access to
the Sepam diagnosis menu.
The

keys are used

to move the cursor up and down

Diagnosis

Advanced UMI eng. S1000+.ppt

and

Diagnosis

Trip 0

Trip -1

Trip -2

Trip -3

Trip -4

to select the chosen type of data.


Use the
key again to scroll
the chosen measurement loop.

23 /24

Advanced UMI
Alarms menu

Series 40
The
key provides access to
the list of alarms.

Alarms
List

Details

Use the
key again to display
the last 16 alarms that have not
been erased yet (date/time and
name of alarm and faulty phase)
N.B.
The alarms are saved in the
event of a power failure

Advanced UMI eng. S1000+.ppt

24 /24