Beruflich Dokumente
Kultur Dokumente
OPERATION
BOILER CONTROL
BOILER LIGHT UP
START UP CURVES
Operating Flexibility
This temperature remain constant till all the water converted to steam
When all liquid converted to steam than again temperature starts rising.
Sub critical boiler typically have a mean ( Boiler Drum) to separate Steam And
Water
The mass of this boiler drum, which limits the rate at which the sub critical
boiler responds to the load changes
Too great a firing rate will result in high thermal stresses in the boiler drum
When Water is heated at constant pressure above the critical pressure, its
temperature will never be constant
No distinction between the Liquid and Gas, the mass density of the two
phases remain same
No Stage where the water exist as two phases and require separation : No
Drum
The actual location of the transition from liquid to steam in a once through
super critical boiler is free to move with different condition : Sliding Pressure
Operation
For changing boiler loads and pressure, the process is able to optimize the
amount of liquid and gas regions for effective heat transfer.
No Religious Attitude
FUR ROOF
I/L HDR
HRH LINE
MS LINE
411C,
277Ksc
411C,
275 Ksc
SEPARATOR
T
A
N
K
G
LPT
C
O
N
D
E
N
S
E
R
LPT
IPT
FINAL SH
FINAL
RH
DIV PANELS SH
LTRH
PLATEN
SH
VERTICAL WW
ECO
JUNCTION
HDR
305C, 49 Ksc
S
T
O
R
A
G
E
HPT
Sp
ate
lw
a
ir
all
rw
ECONOMISER
ECO I/L
FEED WATER
BWRP
FRS
Steam
Complete or Once-through
Generation
Water
Heat Input
Heat Input
Water
Water
SEPARATOR TANK
PENTHOUSE
F28
F28
F8
S2
TYPE OF TUBE
Vertical
Spiral
Advantage
Disadvantage over Vertical water wall
Reduced Number of evaporator wall tubes & Ensures minimum water flow
DISADVANTAGE
More the water wall pressure drop : increases Boiler Feed Pump Power
2 NoS ( AXIAL )
11 kv / 1950 KW
228 mmwc
1732 T / Hr
PA FAN
2 Nos ( AXIAL)
11 KV / 3920 KW
884 mmwc
947 T / Hr
ID FAN
2 Nos ( AXIAL)
11 KV / 5820 KW
TOTAL AIR
2535 T / Hr
46 Ksc / 568 C
1742 T / Hr
ECONOMISER INLET
MILL OPERATION
7 / 10
COAL REQUIREMENT
471 T / Hr
SH / RH SPRAY
89 / 0.0 T / Hr
BOILER EFFICIENCY
87 %
3020 T / Hr
Coal Analysis
1.
High erosion
potential for
pulverizer and
backpass tube is
expected due to
high ash content.
2. Combustibility
Index is relatively
low but
combustion
characteristic is
good owing to
high volatile
content.
Ash Analysis
1.
Lower
slagging
potential is
expected due
to low ash
fusion temp.
and low
basic / acid
ratio.
2. Lower fouling
potential is
expected due
to low Na2O
and CaO
content.
6 Pass
No Of Fields / Pass
18
No Of Hopper / Pass
36
1058 T/ Hr
PAPH # A
TO PULVERISER SYSTEM
AIR MOTOR
AIR MOTOR
PA FAN # A
FD FAN # A
SAPH # A
M
M
AIR MOTOR
AIR MOTOR
M
M
FD FAN # B
SAPH # B
PA FAN # B
PAPH # B
TO PULVERISER SYSTEM
ECONOMISER
BACK PASS
LTRH
FINAL SUPERHEATER
FINAL REHEATER
PLATEN COILS
DIVISIONAL PANEL
FURNACE
AIR PATH
LDO / HFO
30 %
2123 Kg / Hr
42.1 %
52.5 %
HFO Temperature
192 C
outlet
2. Blow down
4% (max.)b
28.8 m3
Economizer
253.2 m3
41.5 m3
13.8 m3
Concentration
g/L.
Formation
oxide
This
All Volatile
Treatment
Oxygenated
Water
Treatment
40
DOSING POINTS
41
42
43
U#1
VENT HDR
WATER LINE
N2 FILL LINE
N2 FILL LINE
N2 FILLING LINE
VENT LINE
SAMPLE COOLER
SAMPLE COOLER
SEPRATOR #1
DRAIN LINE
SAMPLE COOLER LINE
SEPRATOR #2
2
VENT HDR
VENT HDR
FUR WW HDR
DRAIN HDR
MIXING PIECE
WR
VENT HDR
ZR
BRP
TO DRAIN HDR
BOILER FILLING
2.
CLEAN UP CYCLE
3.
4.
5.
If the water system of the boiler is empty (economizer, furnace walls, separators),
then the system is filled with approximately 10% TMCR ( 223 T/Hr) feed water flow.
When the level in the separator reaches set-point, the WR valve will begin to open.
When the WR valve reaches >30% open for approximately one minute, then
increase feed water flow set-point to 30% TMCR ( approx 660 T/Hr).
As the flow increases, WR valve will reach full open and ZR valve will begin to
open.
After completion of Filling, the feed water flow is again adjusted to 10 % TMCR for
Clean up cycle operation
The boiler circulating pump is started following the start of a feed water
pump and the final clean-up cycle.
This pump circulates feed water from the evaporator outlet back to the
economizer inlet.
Boiler Clean-up
When
this time, constant feedwater flow of 10% TMCR ( 223 T/Hr) or more
is maintained.
Water
MODE OF OPERATION
WET MODE :
DRY MODE :
2.
It measures Flow at BFP Booster Pump Discharge and compare it with a calculated flow
from its downstream pressure via a function and maintains the difference 0
3.
Remains Closed
4.
Closes when Flow through BFP Booster Pump discharge > 2.1 Cum
Open When Flow through BFP Booster Pump Discharge < 1.05 Cum
( Minimum Flow will be determined by BFP Speed via BFP Set limitation Curve)
BFP Scoop
5.
6.
7.
UG Valve
WR / ZR Valve
3 Nos Level Transmitter has been provided for Storage tank level measurement
At 17.9 Mtr level it will trip all FW Pumps also MFT will act
FCV ( 30 % )
2.
WR / ZR Valve
Storage Tank
BRP
BRP Recirculation System
2.
3.
START UP SYSTEM
Separator Storage Tank level will be monitored by Separator storage tank wet leg level
control valve ( 3 Mtr)
2.
Primary purpose is to keep the final super heaer spray control valve in the desired
operating range
3.
This Demand goes through Boiler Transfer Function where it is matched with the actual
Evaporator Heat Transfer to minimize the temperature fluctuations
2.
FIRST CONTROLLER
Its Output represents the desired heat transfer / steam generation to maintain
the desired steam parameters and Flue gas parameters entering the Platen
section
SECOND CONTROLLER
The combined Feed Forward and Feed back demand ( as calculated in dry mode operation)
will be compared with minimum Economizer Flow
This ensures the minimum flow through Economizer during the period when start up system
is unavailable
2.
Output of the first controller is subjected to the second controller which monitors the
Separator Storage tank level ( Since the system is in Wet Mode now)
3.
The output of the second controller is the set point of Feed water master controller.
4.
The Feed back to this controller is the minimum value measured before the start up system
and Economizer inlet.
Primary Eco - Secondary Eco - Ring HDR - Spiral W/W - W/W Intermediate HDR - Vertical
W/W - Separator - Backpass Wall & Extended Wall - SH Division - Platen SH - Final SH - HP
TBN - Cold R/H Line - Primary R/H (Lower Temp R/H)- Final R/H - IP and LP TBN - Condenser
DIV SH
406
451
PLATEN SH
440
FINAL SH
480
486
DSH1
15%
DSH2
3%
540
The Steam Pressure And Flow rate is controlled by the load directly
Valve throttling losses occur because the boiler operates at constant pressure while the
turbine doesn't.
The most obvious way to avoid throttling losses therefore is to stop operating the boiler
at constant pressure!
Instead, try to match the stop valve pressure to that existing inside the turbine at any
given load.
Since the turbine internal pressure varies linearly with load, this means that the boiler
pressure must vary with load similarly.
If the boiler pressure is matched to the pressure inside the turbine, then there are no
valve throttling losses to worry about!
While sliding pressure is beneficial for the turbine, it can cause difficulties for the boiler.
ADVERSE AFFECT
As the pressure falls, the boiling temperature (boiling point) changes. The boiler is
divided into zones in which the fluid is expected to be entirely water, mixed steam /
water or dry steam. A change in the boiling point can change the conditions in each
zone.
The heat transfer coefficient in each zone depends upon the pressure. As the pressure
falls, the heat transfer coefficient reduces. This means that the steam may not reach
the correct temperature. Also, if heat is not carried away by the steam, the boiler tubes
will run hotter and may suffer damage.
CHALLANGES
The heat transfer coefficient also depends upon the velocity of the steam in the boiler tubes.
Any change in pressure causes a change in steam density and so alters the steam velocities and
heat transfer rate in each zone.
Pressure and temperature cause the boiler tubes to expand. If conditions change, the tubes will
move. The tube supports must be capable of accommodating this movement.
When it is used, coal fired boilers in the 500 to 1000 MW class normally restrict
sliding pressure to a limited load range, typically 70% to 100% load, to minimize
the design challenge. Below this range, the boiler is operated at a fixed pressure.
This achieves an acceptable result because large units are normally operated at
high load for economic reasons.
In contrast, when sliding pressure is used in combined cycle plant, the steam
pressure is varied over a wider load range, typically 50% to 100% load or more
In this range, the boiler pressure is held at a value 5% to 10% above the turbine
internal pressure. Consequently, the governor valves throttle slightly.
The offset is provided so that the unit can respond quickly to a sudden increase in
load demand simply by pulling the valves wide open.
This produces a faster load response than raising the boiler firing rate alone.The
step in load which can be achieved equals the specified margin ie 5% to 10%.
The throttling margin is agreed during the tendering phase and then fixed.
The throttling margin means that the full potential gain of sliding pressure is not
achieved.
Nevertheless, most of the throttling losses which would otherwise occur are
recovered.
ADVANTAGES
In a uniformly heated tube, the transitions from preheat to evaporation and from evaporation to
superheat shift automatically with load such that the main steam temperature always remains
constant.
Sliding Pressure
At loads over 25% of rated load, the water fed by a feed-water pump
flows through the high pressure feed-water heater, economizer
,furnace water wall, steam-water separator, rear-wall tubes at the
ceiling, and super heaters, The super heaters steam produced is
supplied to the turbine.
24.1 Mpa
9.0 Mpa
60
40
80
Efficiency Change %
+1
0
-1
-2
-3
-4
Variable Pressure
re
P
nt
a
st
n
Co
re
u
ss
100
Reducing the thermal stresses on the component : Low Maintenance & Higher
Availability
Drum : (most critical thick walled component) under highest thermal stresses
Mode Basis
Restart
Hot
Warm
Cold
Stopped time
2Hr Within
6~12Hr
56Hr Within
96Hr Above
SH Outlet Temp
465 above
300 above
100 above
100 below
Separator Tank pr
120 200 /
30 120 /
30 / below
0/
Starting Time
STARTING TIME
Startup Mode
Light off
Full Load(minutes)
Cold
120
420
Warm
90
180
"
Hot
Restart
30
90
PURGE CONDITIONS
MFT CONDITIONS
All Feed Water Pumps Are Off For More Than 40 Sec
2 / 3 Pressure Transmitter indicate the furnace pressure High / Low for more than 8 sec ( 150
mmwc / -180 mmwc))
2 / 3 Pressure Transmitter indicate the furnace pressure High High / Low - Low ( 250 mmwc
/ - 250 mmwc)
EPB Pressed
Economizer Inlet Flow Low For More Than 10 Sec (223 T/Hr)
Furnace Vertical Wall Temperature High For more than 3 Sec (479 C)
Start one ID fan, then the corresponding FD fan and adjust air flow to a min. of
30% TMCR
Adjust fan and SADC to permit a purge air flow of atleast 30% of TMCR and
furnace draft of approx. -12.7 mmWC.
When fans are started, SADC should modulate the aux. air dampers to maintain
WB to furnace DP at 102 mmWC(g).
PARTS
AIR FAN
FIRING SYSTEM
START
UP SYSTEM
FAN
SAPH
WIND
BOX / SADC
PASS A , B
FAN
VACCUME SYSTEM
SEAL STEAM SYSTEM
TURBINE ON BARRING
#A
Spiral wall
Key source
NTPC SIPAT
DOSSAN BOILER
BGR ENERGY
THANK
YOU