GENERATOR

PROTECTION
August 22, 2

PMI Revision 00

Presentation outline
Introduction

Faults and abnormal conditions in Generators

Generator Protection schemes

Conclusion
August 22, 2

PMI Revision 00

GENERATOR PROTECTION:
INTRODUCTION
Core of an electrical power system is generator

PROTECTION EMPLOYED DEPENDS ON


1. Size of unit.

2. The type of connections adopted

GENERATOR PROTECTION COMPRISES


1. Generator proper & its excitation system
2. Generator transformer
3. Unit transformer
4. Auxillaries and their changeover to service
transformer supply.
August 22, 2
PMI Revision 00

FAULTS INVOLVING GENERATOR CAN BE


CLASSIFIED AS

1. FAULTS IN GENERATOR:
Faults involving more than one phase
Inter turn fault
Phase Earth Fault
Over load
Negative phase sequence
Rotor Faults

August 22, 2

PMI Revision 00

FAULTS INVOLVING GENERATOR CAN BE


CLASSIFIED AS

2. Faults involving Generator but affecting the


network.
Loss of excitation
Under excitation
Pole slipping
Motoring
Over Voltage
Under frequency
August 22, 2

PMI Revision 00

FAULTS INVOLVING GENERATOR CAN BE


CLASSIFIED AS

3. Mechanical faults :
Bearing
Shaft stress,
Vibration, Rotor Distortion
Faults in the turbine
Faults in Boiler

August 22, 2

PMI Revision 00

TYPICAL PROTECTIONS PROVIDED IN


TURBO GENERATORS
Differential protection
Gen Earth fault , GT HV Earth fault
Overload , Over voltage
Negative Sequence
Inter Turn Fault
Loss of excitation
Rotor Earth fault
Pole Slipping
Reverse power / low forward power
Back up impedance
Bus bar protection interlock

August 22, 2

PMI Revision 00

GENERATOR DIFFERENTIAL PROTECTION

GEN WDG
I1

I2

87

August 22, 2

PMI Revision 00

August 22, 2

PMI Revision 00

10

August 22, 2

PMI Revision 00

11

August 22, 2

PMI Revision 00

12

GT OVERALL DIFFERENTIAL PROTECTIION

50Z

Igt

Iuat1

GT

Ig

Iuat2

GENERATOR
87 GT

August 22, 2

PMI Revision 00

13

EARTH FAULT PROTECTION


Three ways of providing E/F protection:
Voltage relay connected across grounding resistor
A current relay connected to CT provided in
grounding transformer
Voltage relay connected to open delta in generator
VT

August 22, 2

PMI Revision 00

14

August 22, 2

PMI Revision 00

15

STATOR INTER-TURN FAULT PROTECTION


S1

S2

August 22, 2

PMI Revision 00

16

NEGATIVE PHASE SEQUENCE PROTECTION


Principle of Negative sequence current protection:

August 22, 2

PMI Revision 00

17

FIELD FAILURE PROTECTION


Generator runs as induction generator
heavy reactive loading of stator
slip freq induced currents in rotor

Methods of detecting Field failure :


Under current relay in field circuit
Reactive power monitoring
Impedance relay

August 22, 2

PMI Revision 00

18

FIELD FAILURE PROTECTION


X

-R

-X

August 22, 2

PMI Revision 00

19

POLE SLIPPING PROTECTION


X
B2

B1

-R

-X

August 22, 2

PMI Revision 00

20

OVERLOAD PROTECTION
O / c relay
Over heating detection by RTDs
OVER VOLTAGE
o/v relay 115 %

ROTOR OVER HEATING


Indirect measurement V / I
Rotor E/F monitoring
REVERSE POWER / LOW FORWARD POWER
BACK UP IMPEDANCE

August 22, 2

PMI Revision 00

21

WHAT HAPPENS WHEN


GENERATOR PROTECTION OPERATES

Circuit breaker opening to isolate the fault

Trip command to turbine and boiler

De excitation

Supply changeover : unit to station supply

Initiation of alarm, SOE

August 22, 2

PMI Revision 00

22

CONCLUSION
Protection Engineers Role
Examining and validating the schemes,
proper maint., spares, testing as per plan
modification in system parameters, if needed
Protection documentation and trending

handle work pressure with cool mind

August 22, 2

PMI Revision 00

23

THANK YOU