Beruflich Dokumente
Kultur Dokumente
We have now reached the point where we can begin to discuss the
actual design of the electrical system itself.
All electrical systems have the common purpose of providing electrical
energy to the utilization equipment as safely and reliably as
economically possible.
The system must be adequate to deliver to the location of each piece
of equipment the necessary energy on a continuous basis, without any
component overheating or causing unacceptable voltage drops.
Contd
The initial planning of a system involves the preparation of a
one-line diagram showing all the interconnections and basic
components, such as shown below:
The service equipment is the main control and means of cutoff for the
supply.
In the case of a large premise, the electrical power is usually supplied by
the electric utility at medium-voltage level, requiring a transformer to step
down the voltage to the utilization level.
Contd
The term conductor refers properly to the copper or
aluminum wire that actually carries the electrical
current.
An insulated conductor is one that is encased within
electrical insulation material.
The term cable then refers to the complete wire
assembly including the conductor, the insulation, and any
shielding and/or outer protective covering where used.
Cables can have just a single conductor or they can have
more than one conductor, each separately insulated, but
all enclosed in one overall covering.
the current in amperes a conductor can carry continuously under the conditions of
use without exceeding its temperature rating.
As current flows in the conductor of the cable, heat is generated because of the
resistance of the the conductor (I2R)
The rate at which heat can be dissipated is not only dependent on the insulating
material of the cable but also on the environment that surrounds the cabel, for
example the air temperature.
Size of Conductor
The size of a conductor is a measure of its cross-sectional area.
There are two methods of indication conductor sizes.
1. The smaller sizes are designated AWG number: the lower the number, the greater
the cross-sectional area (thus a No. 12 conductor is larger than a No. 14). For
general power wiring in a building, the smallest size of copper conductor that can be
used for low-voltage wiring is No. 14( rated for a maximum loading of 15 amperes)
2. Unfortunately, when AWG designation was adopted many years ago, presumably it
was not foreseen that conductors larger than No. 1 would be in common use. For the
next larger size the designation 0 was adopted. Then the next three larger sizes
were designated as 00, 000, and 0000, respectively. It is common practice to
identify these conductor sizes as 1/0, 2/0, 3/0 and 4/0 (pronounced as one-aught,
two aught, and son).
For conductors larger than 4/0, the cross-sectional area in thousands of circular mils (MCM)
is used to designate their size. Thus the next size above 4/0 (211.6 MCM) is 250 MCM.
Note that M is used here to designate 1000. This is not consistent with the SI system, which
uses k for 1000. Thus MCM should be more properly designated kcmil.
A circular mil is the area of a circle that is 1 mil or 1/1000th of an inch in diameter.
The circular mil area of a conductor is then equal to its diameter in mils squared.
Thus a solid conductor, 1 inch (1000 mils ) in diameter, has a circular mil area of 1000 times
1000 or 1000,000, which is designated 1000 MCM. Its area in square inches is PiD2/4 = 0.785
square inches.
It is not practical to use solid conductors for the larger sizes as they would be very difficult
to bend. Therefore, smaller strands of wire are twisted together to form one large
conductor.
mm
in.
mm
NECcopper wire
ampacitywith
60/75/90C
insulation (A)[4]
250
126.7
0.500
12.70
300
152.0
0.548
13.91
350
177.3
0.592
15.03
400
202.7
0.632
16.06
500
253.4
0.707
17.96
600
304.0
0.775
19.67
700
354.7
0.837
21.25
750
380.0
0.866
22.00
800
405.4
0.894
22.72
900
456.0
0.949
24.10
1000
506.7
1.000
25.40
1250
633.4
1.118
28.40
1500
760.1
1.225
31.11
1750
886.7
1.323
33.60
2000
1013.4
1.414
35.92
Copper Conductors
ize
60 C
(140 F)
Types
75 C
(167 F)
Types
90 C
(194 F)
Types
90 C
(194 F)
Types
TW
RHW
TBS
TW
RHW
TBS
UF
THW
SA
UF
THHW
SA, SIS
THWN
SIS
THW
THHN,
THHW
XHHW
FEP
THWN
THW-2
USE
FEPB
XHHW
THWN-2
ZW
RHH
USE
RHH,
AWG
Kcmil
THHN
RHW-2
THWN
USE-2
XHHW
XHH, XHHW
Unless otherwise
specifically permitted
elsewhere in this code, the
load current rating and the
overcurrent protection for
conductor types marked
with an obelisk () shall not
exceed 15 amperes for 14
AWG, 20 amperes for
12 AWG, and 30 amperes
for 10 AWG copper; or 15
amperes for 12 AWG and
25 amperes for 10 AWG
aluminum and copper-clad
aluminum after any
correction
factors for ambient
temperature and number at
conductors have been
applied (ref. NEC 240-3d).
Aluminum Conductors
Copper-Clad Conductors
Copper Conductors
21-25 C,
70-77 F
1.08
1.05
1.04
1.08
1.05
1.04
26-30 C,
78-86 F
31-35 C,
87-95 F
0.91
0.94
0.96
0.91
0.94
0.96
36-40 C,
96-104 F
0.82
0.88
0.91
0.82
0.88
0.91
41-45 C,
105-113 F
0.71
0.82
0.87
0.71
0.82
0.87
46-50 C,
114-122 F
0.58
0.75
0.82
0.58
0.75
0.82
51-55 C,
123-131 F
0.41
0.67
0.76
0.41
0.67
0.76
56-60 C,
132-140 F
0.58
0.71
0.58
0.71
61-70 C,
141-158 F
0.33
0.58
0.33
0.58
71-80 C,
159-176 F
0.41
0.41
Naturally,
the larger the cross-sectional area (the size) of the conductor,
Conductor Material
The
tow conductor materials in common use are copper and aluminum.
Copper has historically been used for conductors of insulated cables because of its
desirable electrical and mechanical properties.
Aluminum has had restricted use but is considered where its ampacity rating to weight
ratio and its relative cost are favorable.
The use of aluminum requires a larger conductor size in order to have the same ampacity
rating as copper.
For example, from the table, a No. 1 AWG copper conductor with 90 temperature rating
has a rating of 150 amperes. An aluminum conductor with the same temperature rating
has to be size 2/0 (two sizes larger) to have the same rating of 150 amperes.
Unlike copper, aluminum has a few undesirable properties when used as the conductor
material. An oxide film forms on the surface of aluminum.
This aluminum oxide is essentially an insulating film, causing poor electrical contact at
connections.
To help overcome this problem, the aluminum must be cleaned immediately prior to being
connected.
On the other hand, the oxide film that forms on copper is a relatively good conductor,
causing no real problem at connections.
Aluminum conductors can break after bending much more readily than copper conductors and
therefore aluminum conductors must be handled very carefully during installation.
Aluminum deforms at lower pressure than copper and can become loose at connections after a
period of time. The resulting poor electrical contact can cause excessive heat buildup, leading
Ambient Temreture
The
ambient temperature refers to the temperature of the medium through which the
wiring is to be run (air or earth).
As the ambient temperature increases, there is less temperature differential between
the conductor and the surrounding medium, and the rate at which the heat is
dissipated from the conductor decreases.
This means that the conductor can carry less current before it reaches its maximum
operating temperature.
The first table is based on an ambient air temperature of 30 () as noted in the heading.
There
can be areas within a building where the ambient temperature exceeds 30 such as in
enclosed ceiling areas adjacent to heating pipes and in rooms with heating equipment.
For wiring installed in areas with ambient temperatures higher than 30 the ampacity of the
conductors must be reduced, called derating.
Conversely, if the ambient temperature is lower than 30, the ampacity can be increased.
The second table is based on an earth ambient temperature of 20. The appropriate
correction factors are shown at the bottom of the ampacity tables.
For example, for a conductor with 90 insulation operating in an ambient temperature of 40,
the correction factor is 0.91. thus a No. 6 copper conductor, 90, has an ampacity rating of
75 amperes at 30 and only a rating of 0.91 times 75 or 68 amperes at 40.
Note
that the first table applies to conductors in raceways installed in free air.
However, this table can also be applied where conduits are installed in walls and
structural floor slabs that are above grade level.
Where conduits are run adjacent to each other, sufficient spacing must be
maintained between them to permit proper cooling.
The second table, on the other hand, applies to 75 rated conductors installed in
underground electrical ducts.
The ampacities are based on ambient earth temperature of 20 (68). Ratings are shown
for arrangements where from 1 to 6 electrical ducts are run in the same duct bank.