INSTRUMENTATION

PRESSURE MEASUREMENT:

TWO Nos. PRESSURE TRANSMITTERS PROVIDED IN THE


UPSTREAM OF HP BYPASS PRESSURE CONTROL VALVES, IN
THE MAIN STEAM LINE.
RANGE : 0 TO 200 kg/sq.cm

TEMPERATURE MEASUREMENT:

TWO Nos. K-TYPE DUPLEX THERMOCOUPLES ARE PROVIDED


IN EACH LINE, LOCATED AT THE DOWNSTREAM OF EACH HP
BYPASS PRESSURE CONTROL VALVES.
RANGE : 100 TO 450C.
PROCESS MONITORING

PRESSURE / TEMPERATURE MEASUREMENT:

The 4 to 20 mA analog signals received from the Pressure

transmitters and the mV signals received from Thermocouples

are digitally processed in the DCS. These signals are monitored

to generate internal and external digital signals for interlocks

and alarm generation.


ALARMS, INTERLOCKS and
PROTECTION
ALARMS:
The following are the main Alarms generated in the system:
Pressure/Temperature transmitters failure.
Main steam pressure too high.
Downstream temperature high/very high.
Tracking Pressure set point failure.
Pressure control valves opened more than 2%.
Pressure control valves closed less than 2%.
Hydraulic Oil pressure too low.
Any fast opening criteria operated.
Any closing criteria operated.
ALARMS, INTERLOCKS and
PROTECTION
INTERLOCKS:
The following are the important interlocks provided in the
system:
When the Pressure control valves are closed less than 2% and
in Manual mode, a forced close signal is provided to prevent
the valve from drift open.
When the Main steam pressure is too high, then the Fast
opening device is activated.
Whenever the pressure control valve is opened more than
2%, then the associated Spray control valve will switchover
to Auto mode, if it was in Manual mode before.
When the system is in auto mode and if the process signal is
failed, then the associated control loop will be switched to
manual mode.
ALARMS, INTERLOCKS and
PROTECTION
PROTECTION:
The following are the important interlocks provided in the
system:

When the down stream temperature of Pressure control valves


is too high or when the condenser vacuum is low, then the
Pressure control valves are closed on priority.

When the Turbine trips or when the Generator CB is open,


the opening device is activated to prevent Boiler trip.
HP / LP BYPASS SYSTEM
HRH

MSL

BP

BOILER HPT MPT LPT

CRH NRV
CRH
LBP LPC CO
N

BPE

LBP
E
BD

BFP
LEGEND
BP : HP BYPASS VALVE BD : HP SPRAY ISOLATION VALVE CON : CONDENSOR
LBP: LP BYPASS VALVE BPE : HP SPRAY VALVE LBPE : LP SPRAY VALVE
BFP: BOILER FEED PUMP CRH : COLD REHEAT LINE LPC : LP COOLER
HPT: HIGH PRESSURE TURBINE HRH : HOT REHEAT LINE LPT : LOW PR. TURBINE
MSL: MAIN STEAM LINE MPT : MEDIUM PR. TURBINE
HP BYPASS CONTROL SCHEME
MAIN STEAM LINE To TURBINE

P
= BD
TEMPERATURE
SET POINT
STATION

MASTER
BPE
PRESSURE
CONTROLLER

PRESSURE
SET POINT = TEMPERATURE
STATION T CONTROLLER
To CRH
Reheater Protection Logic