MiCOM Px30 protection devices

railway protection

Jens Eilart
Dipl.-Ing.

April 2004
MiCOM Px30- protection devices
railway protection devices

P438/P436 catenary protection


P638 transformer protection

P138 overcurrent
protection

2 MiCOM Px30, railway protection August 2005 2


Elementary functions

3 MiCOM Px30, railway protection August 2005 3


MiCOM Px30- protection devices
configuration parameters

GERT / DVICE: protection-, control devices


EING / INP: binary inputs ( opto isolated inputs )
MESSE / MEASI: analog input ( 20 mA, PT 100 ) *)
AUSG / OUTP: binary outputs ( output relay )
MESSA / MEASO: analog outputs ( 20 mA, BCD ) *)
LED / LED: LED indicators
VOB / LOC: local control panel
PC / PC: PC interface ( front interface )
KOMMx / COMMx: communication interfaces *)

*) optional

4 MiCOM Px30, railway protection August 2005 4


MiCOM Px30- protection devices
global functions

L_AZ / OL_RC: overload recording


L_ME / OL_DA: overload data acquisition
ST_AZ / FT_RC: fault recording
ST_ME / FT_DA: fault data acquisition
GRUND / MAIN: elementary, main functions
PSU / PSS: parameter subset selection
SELB / SFMON: self-monitoring
BT_AZ / OP_RC: operating data acquisition, journal
W_AZ / MT_RC: monitoring signal recording

5 MiCOM Px30, railway protection August 2005 5


MiCOM Px30- protection devices
rail overcurrent protection

MiCOM P138
(16 2/3, 25, 50, 60 Hz)

tank- or fast overcurrent protection


directional overcurrent protection with dependent and independent
characteristics
Thermal overload protection with coolant temperature measuring
over-, undervoltage time protection
over-, underfrequency protection
circuit breaker failure protection
with minimal current monitoring
programmable logic
firmware 604, use from III / 2003 on

6 MiCOM Px30, railway protection August 2005 6


MiCOM Px30- protection devices
rail overcurrent protection
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

P A T X X X X X X V
2J 6I 6I 4I
1U 8O 8O 6O 6O 6O 6O 8O

alt.

Y
4I

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21

elementary equipment optional equipment


P processor module A communication board
T transformer module Y analog module
2 x current, 1 x voltage X binary in-, output Bi6Bo8
V power supply X binary output Bo6, Bo6T

case 84 TE, example ring terminals

7 MiCOM Px30, railway protection August 2005 7


MiCOM Px30- protection devices
rail overcurrent protection
01 02 03 04 05 06 07 08 09 10

P A T Y V X
2J 4I 4I
1U 8O 6O

01 02 03 04 05 06 07 08 09 10

elementary equipment optional equipment


P processor module A communication board
T transformer module Y analog module
2 x current, 1 x voltage X binary in-, output Bi6Bo8
V power supply X binary output Bo6, Bo6T

case 40 TE, exclusively pin terminals

8 MiCOM Px30, railway protection August 2005 8


MiCOM Px30- rail overcurrent protection
elementary functions

UMZ_E / DTOCN: Tank protection or fast short circuit protection


UMZ_1 / DTOC1: Directional definite time overcurrent protection
AMZ / IDMT: Directional IDMT time protection
LSV_X / CBF_X: circuit breaker failure protection ( OS / US )
U<> / U<>: under-, overvoltage time protection
f<> / f <>: under-, overfrequency protection
THERM / THERM: thermal overload protection

9 MiCOM Px30, railway protection August 2005 9


definite time ground fault protection
(tank protection)

10 MiCOM Px30, railway protection August 2005 10


MiCOM Px30- rail overcurrent protection
definite time ground fault protection

Non-directional DTOC protection, single-level


fixed allocation for IE (input converter T4)
fixed sampling frequency: 20 samplings per period (independent of frequency)
accelerated processing during time-delay tIE> = 0,00 ms:
Trip signal tIE> fter 2 positive samples
Command times 10 ms
adjustable time-delay
extern blocking opportunity of time level
via an appropiately configurated binary input
by blocking scheme via a binary input
via the programmable logic

11 MiCOM Px30, railway protection August 2005 11


DTOC protection

12 MiCOM Px30, railway protection August 2005 12


MiCOM Px30- rail overcurrent protection
DTOC protection

DTOC1: directional independent overcurrent time protection


two-stage
adjustable time-delay for each level
adjustable dependence of direction

Stomzeitdiagramm UMZ-Schutz

1200
1000
800
t [ms]

600
400
200
0
0 1 2 3 4
I [A]

13 MiCOM Px30, railway protection August 2005 13


IDMT protection

14 MiCOM Px30, railway protection August 2005 14


MiCOM Px30- rail overcurrent protection
IDMT protection

dependent overcurrent time protection, single-level


selection of 12 different characteristics
extern blocking opportunity for the AMZ-Funktion
via an appropiately configurated binary input
per blocking scheme via a binary input
via the programmable logic

15 MiCOM Px30, railway protection August 2005 15


MiCOM Px30- rail overcurrent protection
IDMT protection

tripping characteristics ( 1 / 2 )
characteristics in additional
accordance to characteristics
IEC 255-3
100 10

t/s t/s

10
Long time inverse

RI-type inverse
Normally inverse

1
Very inverse
RXIDG-type
inverse
Extremely inverse
0.1 1
1 10 I/I B 100 1 10 I/I B 100

16 MiCOM Px30, railway protection August 2005 16


MiCOM Px30- rail overcurrent protection
IDMT protection

tripping characteristics ( 2 / 2 )
characteristics in characteristics in
accordance accordance to ANSI
100 ANSI / IEEE C37.112 100

t/s t/s

10
10
Long time
inverse
1

1 Moderately inverse Normally


Very inverse 0.1 inverse
Short time
Extremely inverse inverse
0.1 0.01
0.1 1 10 I/I B 100 0.1 1 10 I/I B 100

17 MiCOM Px30, railway protection August 2005 17


directional characteristic
DTOC- and IDMT protection

18 MiCOM Px30, railway protection August 2005 18


MiCOM Px30- rail overcurrent protection
directional DTOC and IDMT protection
directional characteristic:

= 50...220
forward
= -130...40
V

backward

19 MiCOM Px30, railway protection August 2005 19


under-, overvoltage time protection

20 MiCOM Px30, railway protection August 2005 20


MiCOM Px30- rail overcurrent protection
over-/undervoltage protection

independent overvoltage time protection, two-stage


independent undervoltage time protection, two-stage
with minimum voltage
Transient signals can be integrated in the trip command
adjustable resetting ratio (hysteresis)
adjustable time-delay for each level
extern blocking opportunity for all time levels
Via an appropiately configurated binary input
per blocking scheme via a binary input
Via the programmable logic
shortest operating times: ca. 0,8 periods

21 MiCOM Px30, railway protection August 2005 21


frequency protection

22 MiCOM Px30, railway protection August 2005 22


MiCOM Px30- rail overcurrent protection
over-/underfrequeny protection

over-/underfrequency protection, four-stage


all for levels operate independent of each other
operating modes:
over-/underfrequency monitoring
over-/underfrequency monitoring combined with
differential frequency gradient supervision (df/dt)
for decoupling application
over-/underfrequency monitoring combined with a
mean frequency gradient supervision (f/ t)
fr load shedding application
adjustable time-delay for each level
extern blocking opportunity for all time levels
Via a appropiately configurated binary input
per blocking scheme via a binary input
via the programmable logic
23 MiCOM Px30, railway protection August 2005 23
MiCOM Px30- rail overcurrent protection
over-/underfrequency protection
Time-delayed over-/underfrequency monitoring

f
fn o m t
starting
fx

triggering

tx

24 MiCOM Px30, railway protection August 2005 24


MiCOM Px30- rail overcurrent protection
over-/underfrequency protection
Time-delayed df/dt-frequency monitoring

f
fn o m t
starting
fx

d fx/d t
triggering

tx

25 MiCOM Px30, railway protection August 2005 25


MiCOM Px30- rail overcurrent protection
over-/underfrequency protection
f/t-frequency monitoring

f
fn o m t
starting
fx

fx

triggering

tx

26 MiCOM Px30, railway protection August 2005 26


thermal overload protection

27 MiCOM Px30, railway protection August 2005 27


MiCOM Px30- rail overcurrent protection
thermal overload protection

I 2
t
a a,max

t 0 0 * 1 e aus *

IB max a,max

exact execution of the thermal state of the equipment in


consideration of the temperature of the coolant
monitoring of the temperature of the coolant via
PT 100 - measuring
20 mA measuring and preparation

28 MiCOM Px30, railway protection August 2005 28


circuit breaker failure protection

29 MiCOM Px30, railway protection August 2005 29


MiCOM Px30- rail overcurrent protection
circuit breaker failure protection

MiCOM P138
M iC O M

T R IP

A LA R M

O U T O F S E R V IC E

H E A L TH Y

E D IT

C = C LE A R
CG G

= R E A D G
= E N TE R

G G

G
G

2 systems as
transformer reserve
protection M iC O M

T R IP

A LA R M

O U T O F S E R V IC E

H E A L TH Y

E D IT

C = C LE A R
CG G

= R E A D G
= E N TE R

G G

G
G

MiCOM P436
M iC O M

T R IP

A LA R M

O U T O F S E R V IC E

H E A L TH Y

E D IT

C = C LE A R
CG G

= R E A D G
= E N TE R

G G

G
G

MiCOM P138

With circuit-breaker minimum-current monitoring

30 MiCOM Px30, railway protection August 2005 30


limit value monitoring

31 MiCOM Px30, railway protection August 2005 31


MiCOM Px30- protection devices
limit value monitoring

> t>
0 1

> > t> >


measurements:
0 1 signals:
currents,
start I>
temperature, < t<
tI< elapsed,
20 mA DC, 0 1 ...
...

< < t< <


0 1

32 MiCOM Px30, railway protection August 2005 32


measured data inputs,
measured data outputs

33 MiCOM Px30, railway protection August 2005 33


MiCOM Px30- protection devices
measured data input (optional)

DC current input 0 ... 24 mA ( I nom = 20 mA )


load: 100
maximal short-time loading: 50 mA
resolution: 25 A
open-circuit recognizing 0 ... 3 ... 10 mA
overload capacity 24,8 mA ( fester Wert )
zero suppression 0 ... 0,2 I nom

measured-value linearization over 20 branches


limit value monitoring via functional group GRENZ

functional group MESSE / MEASI

34 MiCOM Px30, railway protection August 2005 34


MiCOM Px30- protection devices
measured data input (optional)

PC /
M K G REN Z TH ERM
KO M M 1

ID C I D C , lin x x T

E i n g a n g s s tr . A ID C ,n o m I D C ,n o m
x
x

x
ID C [m A ] D x
I D C , lin /
ID C / m A ID C / ID C ,n o m
ID C ,n o m

M e g r e n a n - L in e a r is ie r u n g S k a lie r u n g
p a ssu n g

p h y s ik a lis c h e
A n z e i g e w e r t: ID C = 0 .. . 2 4 .0 0 m A ID C = 0 . . . 1 .2 0 ID C ,n o m I D C , lin = 0 . . . 1 . 2 0 I D C , n o m
G r e

functional group MESSE / MEASI

35 MiCOM Px30, railway protection August 2005 35


MiCOM Px30- protection devices
measured data output (optional)

2 DC current output 0 ... 20 mA


maximal load: 50
resolution: 20 A
BCD coded output
adjustable scaling
minimal / maximal current
break point of characteristics ( for expansion of measuring range )

adjustable hold time, signal value valid


all operation-, overload- and failure measurements

functional group MESSA / MEASO

36 MiCOM Px30, railway protection August 2005 36


MiCOM Px30- protection devices
measured data output (optional)

2 0 ,0

m A

1 0 ,0

0 ,0
0 ,0 0 0 M e w e rt 1 ,0 0 0

functional group MESSA / MEASO

37 MiCOM Px30, railway protection August 2005 37


programmable logic

38 MiCOM Px30, railway protection August 2005 38


MiCOM Px30- protection devices
programmable logic

Expansion of known functions


hand over transfer functions
triggering of fault detection
group signal
Customer application design of new functions
possible without firmware update
reaction time like protective functions
Boolean Algebra as basis
high transpaency
simple definition
minimal effort to work in

39 MiCOM Px30, railway protection August 2005 39


MiCOM Px30- protection devices
programmable logic

old MiCOM Px30 - devices

protectionservice
protection service

commu- parameteri-
nication zable logic
communication

40 MiCOM Px30, railway protection August 2005 40


MiCOM Px30- protection devices
programmable logic

control inputs functions trip command


and signals

Feste Logik
Konfiguration: (Schutzlogik): Konfiguration:
DIST, DIFF, UMZ ....
AUSG
EING VOB
VOB LED
PC PC
KOMM1 KOMM1
KOMM2 Programmierbare KOMM2
KOMM3 Logik: KOMM3
LOGIK

41 MiCOM Px30, railway protection August 2005 41


MiCOM Px30- protection devices
parameterizable logic

Interne Meldungen und


Signale

...
LOGIK: fkt.zuord.
Ausgang 1

LOGIK: Trigger 1 LOGIK: Fkt.zuord.. LOGIK: Zeit t1


Ausgang 1 Ausgang 1

Nicht ausfhren LOGIK: Zeit t2


8x Ausgang 1

...
&
Ausfhren ...
32 x t t 32 x

...
1 1 2 LOGIK: Ausgang 1(t)

...
...
LOGIK: 1 gesetzt ...
&
LOGIK: Ausgang 1
Nein
8x 1
Ja
...

...

16 x
LOGIK: Eingang 1 EXT 1
...

42 MiCOM Px30, railway protection August 2005 42


applications,
sample utilisation

43 MiCOM Px30, railway protection August 2005 43


protection functionalities
catenary protection

U<>
Z<
I>>>
I (t)
I therm
LSV
U<>
I>>>
I (t) ->
I therm
LSV

LS (bg.)

single feeding system


44 MiCOM Px30, railway protection August 2005 44
protection functionalities
main installation protection

I >>>
I (t) ->
LOGIK

DB Energie GmbH normal switchgear


45 MiCOM Px30, railway protection August 2005 45