MiCOM P821

Breaker failure relay

Henri GRASSET
P821 Product Champion

Venue date
Introduction

P821
P821 is a fast, stand alone breaker
failure protection relay
Undercurrent detectors, for reliable
indication of CB poles open
Phase-segregated - suitable for
single and three pole tripping
applications
All timers included
A one-box breaker fail solution
Simple and easy to programme -
standard MiCOM Px20 setting
procedure
Minimal commissioning

3 3
Market

4 4
MiCOM P821 Breaker failure protection
Market
The customers are:
Transmission
Generation
Distribution
Industry
Voltages:
Medium Voltage
High Voltage
Extreme High Voltage

World-wide Market

5 5
Product Description

6 6
Hardware

7 7
MiCOM P821 Breaker failure protection
Hardware

Mechanic:
Case 4U (152 x 177 mm) - 20 TE (103 mm)
Weight: 2.1 Kg
Extractability
2 rear terminal blocks
Front panel protection: IP 52

Standard Housing

8 8
MiCOM P821 Breaker failure protection
Hardware
78
97 11.6
24.6 52

All dimensions
in mm.

168 158

Panel cut-out
Flush mounting fixing de

4 holesO/ 3.4 99 4 holes O


/ 4.4 (M4 screw)
103 25.1 226
MiCOM P821

IA = 214.50 A
Trip

Alarme C
Equip. fail

Auxiliary
supply
177 151.2 max.
AUX. 1

AUX. 2

AUX. 3

AUX. 4

Flush mounting

9 9
MiCOM P821 Breaker failure protection
Hardware

2 tactile button keypad for


reading and clearing 2 x 16
alarms and messages alphanumerical
backlit display

Trip Led
Alarm Led Retractable flaps
Equipment failure to withdraw
Auxiliary supply
Led Led the active part

Programmable Leds 5 tactile buttons


keypad for setting
and consulting

Battery
RS 232

10 10
Single Line Diagram
Busbar

L1
52 Trip L2 Logic inputs (5)
L3
L4
L5
Phase CTs
Watchdog
3 RL 2
RL 3
RL 4 Logic outputs (8) *
Earth CT RL 5
RL 6
RL 7
RL 8
SCADA
system
Vaux
Front panel PC

Key: * Plus Watchdog


11 11
MiCOM P821 Breaker failure protection
Hardware

12 12
MiCOM P821 Breaker failure protection
Hardware
2 blades 4,8mm x 0,8mm+ 1 M4 screw
by connection point

Com Relay 5 Com Relay 1 0V

55 53 51 49 47 45 43 41 39 37 35 33 31 29

56 54 52 50 48 46 44 42 40 38 36 34 32 30
1

2
Relay 5 NC Relay 1 RS 485 - RS 485 +
3

4
Com Relay 6 NO Relay 1 P. Supply + P. Supply -
5

6
Relay 6 Com Relay 2 NC Relay 0 Com Relay 0
7

28 26 24 22 20 18 16 14 12 10 8
Com Relay 7 NC Relay 2 NO Relay 0
27 25 23 21 19 17 15 13 11 9

Relay 7 NO Relay 2
Com Relay 8 Com Relay 3 Ph A 5A Ph A 5A Com
Relay 8 Relay 3 Ph B 5A Ph B 5A Com
Opt Input 3+ Com Relay 4 Ph C 5A Ph C 5A Com
Opt Input 3- Relay 4 Ph N 5A Ph N 5A Com
Opt Input4+ Opt Input 1+ Ph A 1A Ph A 1A Com
Opt Input 4- Opt Input 1- Ph B 1A Ph B 1A Com
Opt Input 5+ Opt Input 2+ Ph C 1A Ph C 1A Com
Opt Input 5- Opt Input 2- Ph N 1A Ph N 1A Com

13 13
MiCOM P821 Breaker failure protection
Electronic
Hardware
3 boards (extended UC F206, IO/power supply, IO board optional)
4 Current analogue inputs (1 and 5 A)
3 ranges of auxiliary power supply
- 24 to 60 Vdc
- 48 to 150 Vdc
- 130 to 250 Vdc and 100 to 250 Vac (50/60Hz)
8 output relays + 1 watch dog relay (changeover)
5 optically isolated logical inputs
- 24 to 60 Vdc
- 48 to 150 Vdc
- 130 to 250 Vdc and 100 to 250 Vac (50/60Hz)
1 front RS 232, 1 rear RS485
1 LCD (2*16), 8 leds, 7 function keys

14 14
Functions

15 15
MiCOM P821 Breaker failure protection
Functions
MiCOM
Functions Common Names
P821
CB FAIL 50BF (Ph), I< X
CB FAIL Earth 50BF (N), IN< X
Stage 1 Timer tBF1 X
Stage 2 Timer tBF2 X
Dead Zone (End Zone) DBI X
Pole discrepancy Poles Not Together X
Circuit Breaker monitoring,
X
control and statistics
Auxiliary timers tAUX 2
Latching output contacts 86, Lockout X
Setting groups 2
Measurements (True RMS) Metering 4
Event records SOE 75
Fault records 5
Disturbance records Oscillography 5 x 3 sec
RS 232 front communication Comms X
RS 485 rear communication Comms X

16 16
MiCOM P821 Breaker failure protection
Functions
Protection function 1
Breaker failure protection
- Phase

Stage 1 => 1/3 Phase (one delay by phase 0 - 40 s)


Stage 2 => 3 Phase (delay from start of fault 0 - 40s but active
only if stage 1)
Detects undercurrent in less than 15 ms
- Neutral (Io> element)

Earth stage 1 with same delay as phase


As 1/3 Phase activate stage 1

2 main functions, Retripping and Backtripping

17 17
Why use Undercurrent? -
Need to detect that a breaker has opened
Options for open pole detection:
CB Auxiliary Contact 52a:
But... the contacts may be
defective.
Contacts may be faster than the
breaker primary contacts, so would
not detect jamming mid-travel.
Reset of protection trip:
Would not detect a jam mid travel,
where the current/impedance
might have changed sufficiently for
the main protection to reset

Fault not cleared = stability problem for transmission


Risk of further damage, localised overheating
Insufficient protection redundancy
18 18
Using Undercurrent

Diagram shows CB jammed mid-


travel
Dangerous arc within OCB
Closed
Fault not cleared
Contacts
Using undercurrent:
ARC The CB pole should have
opened, the only reliable way to
check that the breaker has
Oil opened 100% is to check that all
current - load, fault and
charging, has gone
Set low, at 5%, 10% or 20%
Can use 3 phases, or ANC
connection to match older
Open Contacts overcurrent relays

Initiate Retripping or Backtripping


19 19
MiCOM P821 Breaker failure protection
Functions

CB Fail Logic
External Trip X =
DT X IDTX

I ph X I > Is
AND
S t BF1 X
Back trip 1 =
DTX

R
OR

RESET AND
S= Set
Configuration R= Reset

DTA

DTB OR tBF2 tBF1 DTG


DTC
DTN

20 20
MiCOM P821 Breaker failure protection
Functions

CB opens before tBF expires

21 21
MiCOM P821 Breaker failure protection
Functions

CB fails to opens before tBF expires

22 22
MiCOM P821 Breaker failure protection
Functions
Typical breaker fail current settings (National Grid UK -
275/400kV)
General
20% In (minimum fault current >55% In)
Resistor Current >10%In
80% In (20% if fault current <160% In)
Generator circuits

5% In
Resistor used to reduce switching overvoltages due to large inductive loads.
Main CB opens 1st and resistor reduces current to a low level. Aux CB is
opened 1 or 2 cycles later.
BF relay should not remain operated by resistor current, I BF relay > 2 x I
resistor

24 24
MiCOM P821 Breaker failure protection
Functions
Typical breaker fail time settings (National Grid UK -
275/400kV)

25 25
MiCOM P821 Breaker failure protection
Functions
Protection function 2&3
Dead zone protection
- Presence of current (I>Idzp) and circuit breaker open (52b=1)
Pole discrepancy protection
- One phase > Ipdp max and one phase < Ipdp min

Automatism function
2 setting groups
Local trip circuit supervision
Test of output relays by external wiring
Latch of the output relays

Versatile

26 26
MiCOM P821 Breaker failure protection
Functions

Dead zone logic


IA IA or DZ
IB or
IB IC
>
I_DZ AND t_DZ T_DZ
IC

52b

Pole discrepancy logic


IA IA or
IB or PD
IB IC
<
IC I_PD <
AND t_PD T_PD
IA IA or
IB or
IB IC
>
I_PD>
IC

27 27
MiCOM P821 Breaker failure protection
Functions
Wiring Security (Replaces the 2 out of 3 scheme)
This function protects the trip circuit against the short-circuiting of an output relay.
This prevents a spurious trip in case of a de-energised relay that would be short-circuited.
This protection is made using the redundancy of the tripping command (AND gate of tripping Relay(s) and security Relay):
Example 1Example 2

+ Vcc + Vcc

Relay for security 1 Relay for security 2

Opto input security 1 OR Opto input security 2

Secure Secure Secure


Trip Trip Trip
Relay Relay Relay Secure trip relay 3ph
Ph A ph B Ph C

As long as Relay 1 or 2 is healthy, there will be no spurious trip. If one of them has been short-
circuited, the opto input would be energised and an alarm would be raised

28 28
MiCOM P821 Breaker failure protection
Functions
Auxiliary function
2 auxiliary timers
Trip statistic
Frequency, phase and earth current measurement
5 disturbance recorders (max. 3s)
5 fault records
75 event records

Communication available Digital Control


Systems
Modbus
IEC 103
Courier
DNP3

Full communication

29 29
MiCOM P821 Breaker failure protection
Accuracy

Accuracy
Breaker failure protection (sample)
+/- 2% of threshold if threshold > 0.4In
+/- 5% of threshold if threshold > 0.16In
If less: +/- 8% (with a 0.0125In drop off stability assured)
Dead zone and Pole discrepancy protection (module)
+/- 2% of threshold if threshold > 0.2In
+/- 5% of threshold if threshold > 0.1In
if less: +/- 8% (with a 0.005In drop off stability assured)

Accurate

30 30
Atmospheric
environment

31 31
MiCOM P821 Breaker failure protection
Atmospheric environment

Temperature
IEC 60255-6
- Operating : - 25C + 55C
- Storage : - 40C + 70C

Humidity
IEC 60068-2-3
56 days at 93 % at 40C

Resistant

32 32
Reference number
CORTEC

33 33
MiCOM P821 Breaker failure protection
CORTEC
CORTEC Code in EAI Database and Cameleon

34 34
MiCOM S1

35 35
MiCOM P821 Breaker failure protection
MiCOM S1
CONTROLS to MiCOM relays
Settings
CB Opening
Setting group change
Data extraction
Settings
Measurements
Events records (75 events)
Faults records (Last 5 faults)
Disturbance records (5 records)

Communicates

36 36
HMI

37 37
MiCOM P821 Breaker failure protection
DEFAULT DISPLAY
HMI 1/4
IL1 = 1245 A

OP PARAMETERS CONFIGURATION

Password
Display CT Ratio LED 5 / 6 / 7 / 8 Group Select Alarms Inputs
****

Description Default Display Line CT primary Led n Change Group Inst. Self-reset ? Inputs : 54321
P821-1 RMS IL1 1000 TRIP Phase A Input = EDGE No 00001
Ext. Y/N
TRIP Phase B
Reference Phase A Text Line CT sec Ext. Y/N Setting Group Alarm Battery = Voltage Input
ALST L1 1 TRIP Phase C 1 No DC
Ext. Y/N
TRIP 3Phases
Software version Phase B Text E/Gnd CT primary Ext. Y/N
V1.A L2 1000 T Ph. A
Stage 1 Y/N
T Ph. B
Frequency Phase C Text E/Gnd CT sec Stage 1 Y/N
50 Hz L3 1 T Ph. C
Stage 1 Y/N
T Earth
Active Group = E/Gnd Text Stage 1 Y/N
1 N T Stage 1 Y/N
T Stage 2 Y/N
Problem
Input 54321 Secu 1 Y/N
Status 00101 Problem
Secu 2 Y/N
T DZ Y/N
Relay 87654321 T PD Y/N
Status 00001011 T Aux1 Y/N
T Aux2 Y/N
CB Open Time
Ext. Y/N
Date
CB Open Time
04/03/02
St. 1 Y/N

Time
CB Operation
Nb Y/N MiCOM P821 - V1 Software
SUM A N Y/N
14 : 15 : 34
Menu content
38 38
MiCOM P821 Breaker failure protection
HMI 2/4
DEFAULT DISPLAY
IL1 = 1245 A
PROTECTION
CONFIGURATION MEASUREMENTS EVENT COUNTERS COMMUNICATION
G1/G2

Frequency Reset Counters Communication


50.01 Hz RST=[C] Yes

IL 1 Ext Trip 3Ph Baud Rate


257.05 A NB 0 19200 Bd

IL 2 Ext Trip Ph A Parity


258.80 A NB 0 Wthout

IL 3 Ext Trip Ph B Stop bits


257.50 A NB 0 1

IN Ext Trip Ph C Relay Address


20.00 A NB 0 1

Trip Ph.A Stage1 Date format


NB 0 PRIVATE

Trip Ph.B Stage1


NB 0

Trip Ph.C Stage1


NB 0

Trip Earth St.1


NB 0

Trip Stage 1
NB 0

Trip Stage 2
NB 0

39 39
MiCOM P821 Breaker failure protection
HMI 3/4
DEFAULT DISPLAY
IL1 = 1245 A

PROTECTION
AUTOMAT. CTRL
G1/G2

TRIP COMMAND LATCH TRIP ORDER OUTPUT RELAYS


CB FAIL DEAD ZONE POLE DISCREPANCY

Trip t Phase A Latch t Phase A tPh.A :87654321


CB Fail Dead Zone prot. Pole Discrepancy
Stage1 Yes stage1 No Stage1 00000000
Funct Yes Funct Yes Funct Yes

Trip t Phase B Latch t Phase B tPh.B :87654321


CB Fail Phase I_DZ > I PD>
Stage1 Yes stage1 No Stage1 00000000
Yes 1.0 In 0.8 In

Trip t Phase C Latch t Phase C tPh.C :87654321


I> BF T_DZ > I PD <
Stage1 Yes stage1 No Stage1 00000000
0.1 In 100 ms 0.4 In

Trip t Earth Latch t Earth tEarth :87654321


CB Fail Earth T_PD
Stage1 Yes stage1 No Stage1 00000000
Yes 10 ms

Trip Stage 1 Latch Stage1 TStage2 :87654321


I0> BF
Yes No 00000000
0.05 In

Trip Stage 2 Latch Stage2 tDEAD :87654321


Delay Stage1
Yes No Zone 00000000
10 ms
Trip T_DZ Latch T_DZ Tpole :87654321
Delay Stage2
Yes No Discre. 00000000
40 ms

Trip T_PD Latch T_PD T Aux1 :87654321


External Reset CB Open:87654321
Yes No 00000000
stage1 No ST.1 00000000

Trip tAux1 Latch tAux1 T Aux2 :87654321 CBNb.Op:87654321


Yes No 00000000 00000000

Trip tAux2 Latch tAux2 CB Open:87654321 San :87654321


Yes No Ext 00000000 00000000

40 40
MiCOM P821 Breaker failure protection
DEFAULT DISPLAY
IL1 = 1245 A HMI 4/4
AUTOMAT. CTRL RECORDS

LATCH OUTPUT CB Monitoring Fault Record Disturb Record


Inputs 1/2/3/4/5 CB SUPERVISION WIRING SECURITY
RELAYS

Latch Relay 2 Input 1 CB Opening Time Wiring Security CB Opening Time Record Number Pre-Time
No 0 ms 5 0.1 s
None Superv Yes Yes

Latch Relay 3 Input 2 CB Opening Time Wiring Security CB Operations Fault Time Post-Time
No None 100 ms Rel.1 RST = [C] 0 12:05:23:42 0.1 s

Latch Relay 4 Input 3 CB Operation NB Wiring Security Amps (n) Fault Date Disturb Rec Trig
No None Superv Yes Rel.2 RST= [C] 09/ 01/ 01 ON TRIP

Latch Relay 5 Input 4 Amps (n) IA Active Set Group


CB Operation NB CB Operation NB
No None 0 E0 2
0 0

Latch Relay 6 Input 5 Amps (n) IB Faulted Phase


SUM A n Superv SUM A n Superv
No None Yes 0 E0 EARTH
Yes

Latch Relay 7 tAux 1 Amps (n) IC Threshold


SUM A n SUM A n
No 0 ms 0 E0 Ie>
0 E6 0 E6
Latch Relay 8 Magnitude
tAux 2 N N
No 1200 A
0 ms 1 1

T Trip T Trip IA Magnitude


None 1200 A
Rst Led 100ms 100ms
Secu2 IB Magnitude
Secu1
500 A
Dist Trig
Chang.Grp
tAux 1 IC Magnitude
tAux 2 480 A
Unlatch
52 b IN Magnitude
52 a 103 A
Trip Ext3
Trip ExtC
Trip ExtB
Trip ExtA
MiCOM P821 - V1 Software - Menu content
41 41