Beruflich Dokumente
Kultur Dokumente
SENTHIL, PSS_SAP_TECHNOLOGY
ABB Group
April 22, 2017 | Slide 1
Power transformer in Power system
ABB Group
Power transformer in Power system
ABB Group
Power transformer in Power system
ABB Group
Different vector group & Neutral connection
ABB Group
Different winding arrangements
ABB Group
Special transformer applications
ABB Group
Power transformer application
x x
U
V
ABB Group
Power transformer in Power system
ABB Group
Factors contributing to Internal faults
ABB Group
Types of internal faults
Earth-fault
Short-circuit
Turn-to-turn Fault
(Very high fault current in the shorted turns; Low fault current at the
transformer terminals)
Flash-over from HV to LV winding
(High voltage rise; Usually high fault current)
Core Fault
Tank Fault
Reduced cooling
ABB Group
Consequences of Internal Fault
Danger to people
Damage of winding, core and insulation
Damage of the tank and bushings
Escape of oil, possibility of fire
Damage to surrounding equipment
Disturbance to the power system
Possible loss of the transformer for a long time
Costly repair or replacement
ABB Group
Delta-Wye transformer
ABB Group
Wye autotransformer with Unloaded tertiary winding
ABB Group
Wye autotransformer with loaded tertiary
ABB Group
Three winding transformer
ABB Group
Three winding transformer
ABB Group
Statistics from IEEE guide
ABB Group
Detection of transformer internal faults
Phase-phase fault
Transformer Differential Protection
Buchholz Relay
Overpressure Device
Underimpedance/Distance Protection
Overcurrent Protection (non directional, directional)
HV Fuses
Earth-fault, Low impedance earthing
Restricted Earth-fault Protection
Transformer Differential Protection
Buchholz Relay
Underimpedance/Distance Protection
Overcurrent or Earth-fault Protection (non directional, directional)
HV Fuses
ABB Group
Detection of transformer internal faults
ABB Group
Factors that affect transformer protection
ABB Group
Power transformer in Power system
ABB Group
Sources of error in differential protection
ABB Group
Sources of error in differential protection
ABB Group
Differential characteristics
K = 0.5 or 1
ABB Group
Blocking of differential protection
Harmonic blocking
Wave shape blocking
DC blocking
Low current blocking
ABB Group
Harmonic blocking
ABB Group
DC blocking
ABB Group
Low Current level
ABB Group
Sources of Magnetizing inrush current
Energizing of a transformer
Abrupt change of voltage at the transformer terminals
Occurrence of fault, Removal of fault, Change in character of a fault
Out of Phase synchronizing
ABB Group
Magnetizing inrush current
ABB Group
Transformer inrush current
current
in pu phase L3 current
10.0
5.0 CB
closes
iL1
iL2
0.0
iL3
-5.0
phase L1 current
0 20 40 60 80 100
time in ms
ABB Group
Factor affecting inrush current
ABB Group
Consequences of inrush current
The inrush current has a large DC component that may saturate the CTs
DC saturation of phase and neutral CTs may cause a false residual current
and a false differential current
There is a risk that sensitive differential protections, residual overcurrent
protections and neutral point overcurrent protections may operate incorrectly
ABB Group
Over excitation Protection
ABB Group
Over excitation protection
ABB Group
Over excitation protection
Use a V/Hz relay to block the tripping of the differential relay, or to desensitize
the differential relay when V/Hz reaches a certain level.
Overexcitation manifests itself with the production of odd harmonics. As the third
harmonic (and other triplens) may be effectively cancelled in delta transformer
windings, the level of fifth harmonic is often used as a restraining quantity in the
differential relay.
Use of a modified differential scheme that extracts and uses the third-harmonic
exciting current from the transformer delta winding to restrain the differential
relay.
ABB Group
Earth fault protection
ABB Group
Low impedance restricted earth fault protection
ABB Group
High impedance restricted earth fault protection
ABB Group
D-Y transformer ground fault protection
ABB Group
Thermal overload protection
ABB Group
Thermal overload protection
The temperature increase of the conductor, when nominal current is applied, can
be defined as a function of time by the so-called thermal time constant, T, as
shown in Figure.
The temperature rises to 63% of the final value in a time equal to T and reaches
98% of the final value in time 4T.
If the current is reduced to 71% of the nominal value, the temperature decreases
and settles at about half of the final value (0.712 = 0.50) because the increase in
temperature is proportional to the square of the current.
ABB Group
Residual overcurrent protection
ABB Group
Monitors
Monitors are very important devices which detect faults and abnormal service
conditions which may develop into fault.
Sudden gas pressure protection
Buchholz protection
Oil level monitoring
The oil thermometer
The winding thermometer
ABB Group
Monitors
Temperature monitors for winding or oil temperature are typically used to initiate
an alarm requiring investigation by maintenance staff.
Gas detection relays can detect the evolution of gases within the transformer
oil. Analysis of the gas composition indicates the mechanism that caused the
formation of the gas; e.g., acetylene can be caused by electrical arcing, other
gases are caused by corona and thermal degradation of the cellulose
insulation. The gas detection relays may be used to trip or alarm depending on
utility practice.
Sudden-pressure relays respond to the pressure waves in the transformer oil
caused by the gas evolution associated with arcing.
Oil level detectors sense the oil level in the tank and are used to alarm for minor
reductions in oil level and trip for severe reductions.
ABB Group
Protective Relays Used (Transformers > 5 MVA)
ABB Group
Protective Relays Used (Transformers < 5 MVA)
ABB Group
External fault scenarios
ABB Group
Examples of connections in general use
ABB Group
Vector group of three phase transformers
ABB Group
Vector group of three phase transformer
ABB Group
ABB Group