Beruflich Dokumente
Kultur Dokumente
This Insulator?
It can handle steady state and transient voltages
The shape of the insulator was designed to maximize
surface area
Voltage breakdown through air across the insulator
unlikely
Clearance Distance through Air Considers Dielectric
Strength of Air
Voltage breakdown across the surface of the insulator
unlikely
Creepage Distance Across Insulator Greater Than or Equal
to Air Distance
Tracking of Voltage Across Insulator Considered
There are safety factors built into this design, based on
nominal voltage, but considering transient voltages
10, 15, 20 X nominal voltage (????)
Somebody tested it
Nominal Voltages
Nominal voltage denotes the reported voltage in
use in the majority of residential and commercial
establishments in the country or city.
Alternating current (AC) is normally distributed either
through a 3-phase wye (or star) or delta
(triangle) 4-wire secondary power distribution
system.
In the wye or star distribution systems, the nominal
voltage examples are 120/208V (e.g., United States
and Canada), 127/227 V (e.g., Mexico), 220/380V
(e.g., South Korea), and 230/400 V (e.g. Europe).
The higher voltage is 1.732 (3) times the lower
voltage.
3-Phase/4-Wire Wye (Star) Circuit
Europe 400 V
IN=-(IA+IB+IC)= 0 A
Neutral Conductor Carries the Unbalanced Current
IA + IB + Ic +IN =0
Unbalanced 3-phase:
Let IA= 1200 = 120 + j0
IB= 8= -40 + j69.28
Ic= 100= -50 - j86.60
30 - j17.32
IN=-(IA+IB+IC)= -30+j17.32
=34.64 A
Neutral Conductor in 120/240 V AC, 3-Wire Secondary
IA + IB +IN =0
IA + IB +IN =0
IA + IB +IN =0
IA= 10 A
IB= -6 A
IN=-(IA+IB)= -(10-6) =-4 A
D. Gies | Transients and Surge Protection Considerations in Electrical Equipment Offense and
Defense|2013 ISPCE
RC, RL, LC Circuits
Under transient conditions, and especially under abnormal fault conditions,
the inductance and capacitance can react to a sudden change in current or
voltage, causing very large spikes in voltage or current.
This is more pronounced under unloaded conditions.
Capacitors, RC Inductors, RL LC, Natural Frequency, Surge Impedance
di
iC
dV V V0 e t RC V L
dt
i i0 e tR L f0
1 L
Z 0 ( )1 2
dt 2 ( LC )1 2 C
D. Gies | Transients and Surge Protection Considerations in Electrical Equipment Offense and
Defense|2013 ISPCE
Surge Impedance
C
I (t ) V ( )1 2 sin w0t V
L
= =
or
For mid-term, need to know surge impedance, but do not need to derive it
1
f0 Natural Frequency
2 ( LC )1 2
L
Z 0 ( )1 2 Surge Impedance
C
=
With regard to transient responses, the basics of the RLC equivalences
are:
The capacitor cannot accept an instantaneous change in voltage,
and the current is proportional to the change in voltage over the
change in time
The inductor cannot accept an instantaneous change in current,
and the voltage is proportional to the change in current
Together, the inductance and capacitance oscillate at the natural
frequency f0
Resistance has a dampening effect for the above.
If inductances are hit with a fast rise in current
The voltage across them swings very high.
If capacitances are hit with a fast rise in voltage
The current across them swings very high.
D. Gies | Transients and Surge Protection Considertions in Electrical Equipment Offense and
Defense|2013 ISPCE
Capacitor
Charging V V0 (1 e t RC )
Inductor
Charging
I I 0 (1 e tR L )
Laplace Transforms
Inductor impedance
Capacitor impedance
Resistance is
Quadratic Formula
Table of Laplace Transform
Pairs
1
3
3
Step
Step
Ramp
Ramp
Exponential
Exponential
Sine
Sine
Cosine
Cosine
Damped
Damped Ramp
Ramp
Damped Sine
Damped Cosine
Significance of Laplace Transform Pairs
(a) (b)
[1]
RLC Damping
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
The peak of the undamped wave sets the vertical scale for the curves, and
knowing we have determined which curve represents our solution. Equation
4.3 .1 simplifies the obtaining of a time scale. An example will help to
clarify this procedure.
Figure 4.5 illustrates the problem discussed at the beginning of Section
4.2. In that section an expression was derived for the current in the inductor
when the switch S is closed. We will now make use of that analysis and the
dimensionless curves of Fig. 4.4 to obtain a numerical solution for the values
shown in Fig. 4.5.
The operational solution for IL was given in Eq. 4.2.5:
The structure of the transform tells us that our curves in Fig. 4.4 are
appropriate. The first step is to calculate the surge impedance of the circuit:
Next, obtain
Current Suppression Circuit: The circuit breaker and an unloaded transformer (a) and the
effective equivalent circuit (b).
Suppose that in the current suppression circuit, at the time that the switch is opened on the
unloaded transformer, the instantaneous current is I0. The magnetic energy in the core of the
transformer is
Abnormal Switching Transients Current Suppression
Let us assume that I1% of normal full load current, and assume that L m is quite high
Lets assume that the current has no place to go, so the energy has to be diverted into the
capacitance, and the stored capacitive energy is:
When the current is diverted into the capacitance, the energy from the
magnetic field of the transformer is transferred into the electric field of the
capacitance. Voltage can be calculated if the capacitance and inductance
are known, using the equations below.
or
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
Abnormal Switching Transients Current Suppression
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
Abnormal Switching Transients Current Suppression
Effective capacitance can vary with the type of winding and the insulation,
whether oil, air, or other material, but would typically be in the range of
1000-7000pF.
If C=5000pF, then:
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
Abnormal Switching Transients Current Suppression
5.6 FERRORESONANCE
What is Ferroresonance?
45
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
COPYRIGHT 2013 ALCATEL-LUCENT. ALL RIGHTS RESERVED.
5. FERRORESONANCE
What is Ferroresonance?
46
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
COPYRIGHT 2013 ALCATEL-LUCENT. ALL RIGHTS RESERVED.
Voltage across the inductor is dependent upon the
frequency and the current through a function f(I)
f(I)
VL is plotted as a function of current in Fig. 5.25. The
voltage will lead the current by 90. Voltage across the
capacitor is given by VC=
Fig. 5.25 Voltage and current relationships in a
ferroresonant circuit. For Mid-Term, you do not have
to remember this
Total Voltage:
V=VL+VC= (5.6.3)
Or VL =V+
VL has a fixed constituent V and one proportional to I.
Eq. 5.6.3 is plotted in Fig. 5.25 as the inclined straight
line.
(Not on mid-term)
In
Fig. 5.28 the first term (on right) of equation
5.6.5 is an ellipse. It is plotted for three different
values of R, first by itself, and then inclined in
combination with I/.
What is Ferroresonance?
51
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
COPYRIGHT 2013 ALCATEL-LUCENT. ALL RIGHTS RESERVED.
5. FERRORESONANCE
OBSERVATIONS FROM INCIDENTS OF FERRORESONANCES
Roger Dugan (IEEE Fellow) says that the potential for ferroresonance has
caused nearly all utilities in the U.S. to apply grounded wye-wye transformers
at 25 and 35 kV classes.
Also, there may be a perception that ferroresonance cannot happen in 15 kV
class systems.
While it is less likely, it is still possible.[2]
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
COPYRIGHT 2013 ALCATEL-LUCENT. ALL RIGHTS RESERVED.
5. FERRORESONANCE
CORRECTIVE MEASURES
Eliminate fuses.
Rely on feeder breaker for fault interruption.
D. Gies | Transients and Surge Protection Considerations Offense and Defense|2013 ISPCE
COPYRIGHT 2013 ALCATEL-LUCENT. ALL RIGHTS RESERVED.
These sections do not have to be memorized for midterm
From Dugan:
SHOPPING MALL INCIDENT
Many utilities first encountered instances of ferroresonance
when they began to build 34.5 kV underground distribution
systems. They had built 15 kV underground systems for years
without having a known problem. When the same designs
were attempted at the higher voltage levels, problems were
soon encountered. One incident containing several interesting
elements involved a shopping mall that suffered some
damage as a result.
Utility personnel were called to the scene in response to a
complaint about a "power surge" and a noisy transformer.
They were immediately drawn to a padmounted service
transformer that was making loud, irregular growling noises.
They also observed a spot on the top of the tank where the
paint had bubbled and charred. This was presumably caused
by the magnetic flux heating the tank as the core alternately
saturated during ferroresonance. However, the transformer
was tested and found not harmed internally. It was eventually
returned to service.
The root cause was an automobile accident that had resulted
in an open conductor fault on the overhead line tap just upline
from the cable drop to the shopping mall (refer to Figure 1).
The line had separated and fallen in such a way that there was
not a short circuit fault. This yielded the traditional circuit
configuration for ferroresonance, which continued for at least
30 minutes before crews arrived. Most of the 3-phase load in
the mall tripped off line due to the low or fluctuating voltage.
This only made matters worse for the loads that remained
connected because there was insufficient load to damp out the
ferroresonance. The weakest link in the chain then were the
surge suppressors (usually simple MOV arresters) on the low
voltage system in the mall. Failures were reported in cash
registers and computer equipment.
The fused cutouts on the UD cable drop were opened,
removing the transformer from service. Then the overhead
line was repaired and the transformer tested. It was
subsequently placed back into service. The disposition of the
These
failedsections do not haveisto
load equipment beknown.
not memorized for midterm
These sections do not have to be memorized for midterm
SINGLE-PHASING DISTRIBUTED GENERATION
Distribution generation (DG) protection requirements are
creating some interesting protection conflicts. Most utilities
require DG above a certain size to have a separate
service transformer and these are frequently served
underground as shown in Figure 2. Many commercial
buildings are served with a similar arrangement. The
stage is thus set for a serious case of ferroresonance
should one of the fuses blow when there is no permanent
fault in the cable. This can occur due to an animal
climbing the pole or simply a fuse element failure.
DG is required to disconnect immediately after detecting a
problemThesewith thedoutility
sections system.
not have If the problem
to be memorized is an open
for midterm
riser pole fuse, the transformer could very well go into
ferroresonance since there is no load to damp it out. Only
the generator is connected and its breaker is open. It
could remain in ferroresonance for quite some time before
it is reported depending on how closely the site is
The solution is to have three-phase switchgear on the primary side of the
transformer. This is not a problem for larger DG installations. However, it is
prohibitively expensive for small generators.
In general, I advise against line fuses in series with DG. This is not economically
avoidable in some cases. How the rules for this evolve with DG advocates
increasing the pressure to apply DG to distribution systems will be interesting.
There have been a number of incidents nearly identical to this with large
commercial building. It is common for hospitals, banks, and other commercial
buildings to have backup power installed. It is also common for such installations
to be fed underground with a cable drop of 1000 feet, or so. The standard
protection is a set of three fused cutouts on the riser pole. Sometimes the
implementation is such that as soon as a problem with the utility service is
detected, nearly all the load is transferred to backup power. This leaves the service
transformer energized and isolated without load to damp ferroresonance. Thus,
any loads that remain connected are subject to excessive duty. Low-voltage surge
suppressors commonly succumb to this duty. Also, UPS systems that monitor the
fluctuating voltage may cycle on an off repeatedly. This is not necessarily
damaging, but can disrupt IT operations.
These sections do not have to be memorized for midterm
These sections do not have to be memorized for midterm
Again, the solution is to use three-phase switchgear such as reclosers or
sectionalizers at the riser pole. Alternatively, the fused cutouts may be replaced
with solid blades, which will cause the feeder breaker or recloser to operate to clear
faults. This will be an inconvenience to other customers
DELTA-CONNECTED PADMOUNTS ON 15 KV CLASS UNDERGROUND DISTRIBUTION
SYSTEMS
The potential for ferroresonance has caused nearly all utilities in the U.S. to apply grounded
wye-wye transformers at 25 and 35 kV classes. However, many utilities continue to use delta-
connected primaries on underground transformers at 12.47 kV for decades with no known
difficulties. There may be a perception that ferroresonance cannot happen in 15 kV class
systems. While it is less likely, it is still possible. One factor is the proportion of losses. Newer,
low-loss transformer designs are making it more likely than previously.
In one case, a utility that was constructing a new 12.47 kV underground service for a multi-
building complex. As each cable run and padmount transformer was connected, the system was
energized from the riser pole cutouts to test it. At some point, the number of transformers and
cable capacitance was sufficient to support strong ferroresonance.
The problem in this case was first noticed when the unloaded system was being de-energized
after testing. When the second cutout was pulled, leaving one, the transformers started making
an unusual loud noises. When the final cutout was pulled, a large arc was drawn that could not
be extinguished simply by pulling the cutout open with a hot stick. This would suggest that a
large current was flowing, much the surprise of the line personnel, who believed the system to
be unloaded.
Subsequent measurements with a power quality monitor showed very unusual voltage
waveforms. These were easily duplicated by simulation and found to be the expected line-to-line
voltages during delta winding ferroresonance with two cutouts open. This demonstrates that
ferroresonance is not just a 25 kV or 35 kV system phenomenon, but can occur at any voltage
with the appropriate combination of cable capacitance, transformer connection, and losses.
These sections do not have to be memorized for midterm
The transformers were not damaged despite the impressive display of audible noise
and arcing. However, some surge protectors on the low voltage side were blown off the
wall. It is not known if this happened during the ferroresonant activity or after. It may
have occurred when the cutouts were pushed back in after the third one failed to clear.
This type of failure often occurs when the surge protectors have become overheated.
Re-establishing full power makes available enough fault current to cause catastrophic
failure.
Normally, ferroresonance is no longer a problem once the system is loaded. However,
ferroresonance from the two-phase open condition on a delta transformer often requires
more load to damp it out than the one-phase open case.
OBSERVATIONS
Some points common to all three of these cases include:
The event was caused by opening one or two phases, either intentionally or
accidentally
The basic situation is established by the commonplace UD cable service drop from an
overhead line.
The cable system had either light load or no load.
The transformers were not permanently damaged (to Dugans knowledge).
Damage did occur to load side equipment.
VI. CORRECTIVE MEASURES
Corrective measures include:
Use three-phase switchgear instead of fuses. This is not economical in many cases.
Open or close all three cutouts as simultaneously as possible.
Ensure the transformer is loaded while being switched.
Eliminate fuses. Rely on feeder breaker for fault interruption.
Various measures to prevent inadvertent fuse operation.
Obviously, each of these measures have certain costs associated with them. Distribution
engineers may simply choose to accept the risk or adapt operating procedures to minimize it.
There may be no economical way of dealing with certain accidental occurrences.
Chapter 14 - Lightning
14.1 THE SCOPE OF THE LIGHTNING PROBLEM
Lightning
6. lightning
Formation
Clouds acquire charge or at least become polarized, so that electric fields of considerable
strength are created within the cloud and between the cloud and adjacent masses, such
as earth and other clouds.
When these fields become excessive, to the extent that the dielectric of the intervening
space can no longer support the electric stress, a breakdown or lightning flash occurs.
This is usually the high-current discharge that we are all familiar with.
The lightning strokes that create problems for the utility engineer are those that terminate on or nearby power
lines.fields effectively close a giant switch between the cloud and the power line or
These
adjacent earth. This is either a direct connection to the line, or it completes a circuit with
loose mutual inductive coupling to the line.
Frequently the line will be raised to such a potential that further flashes will occur to
grounded structures.
Else, the grounded structures may be raised to such a potential that they flash over to the line.[1]
Lightning Formation
6. lightning
The Mechanisms of Lightning
The updrafts tend to carry up to the top of the cloud the positive air and smaller
drop that the wind can blow against gravity.
Meanwhile, the falling heavier raindrops bring negative charge to the base of the
cloud.[1]
One Theory
6. lightning
The Mechanisms of Lightning
Another theory on the formation of lightning: When water droplets break
up, they acquire a positive charge and in the process negative charges is
imparted into the air around
The electric flux lines start on a positive charge and terminate on a
negative charge
The field pattern on the ground and in the cloud accord with the
distribution of charge shown in the figure to the right.
Another Theory
6. lightning
The Mechanisms of Lightning
Another Theory
6. lightning
The Mechanisms of Lightning
As the charges build up within the cloud and by
induction on the earth below, a point is reached
locally within the cloud where the electric field is
sufficient to cause breakdown.
Another Theory
6. lightning
Video: Lightning Stroke In Slow Motion
Lightning Video
D. Gies | Transients and Surge Protection Considerations in Electrical Equipment Offense and
Defense|2013 ISPCE
6. lightning
Lightning Data from NASA-Kennedy Space Center
NASA gathered the following lightning data from a lightning protection system
(LPS) installed on one of its launch complexes that was well instrumented with
meteorological and lightning data acquisition systems from late 2010 until mid-
2011: [3]
About 63% of the direct flashes were multiple-stroke flashes (5 of 8) and only
20% of them (1 of 5) had all of its return strokes (3) terminating at the same
location.
Rocket science!
D. Gies | Transients and Surge Protection Considerations in Electrical Equipment Offense and
Defense|2013 ISPCE
Pre-Strike Theory
The leader has a pestle shape and that it contains
far more charge than originally supposed.
Before the leader reaches the ground, a discharge
somewhat similar to it rises from the ground to
meet it.
Similarities between the lightning stroke in its
formative stages and phenomena observed in
negative point-to-plane corona.
This has been shown to be a pulsating discharge;
current which is choked off by field distortion
produced by negative ions, develops again as the
ions disperse.
But it has also been shown that at high fields, a
pulse-free mode can exist.
Once the stepped leader has established a connection
to earth, there is general agreement that a power return
stroke moves swiftly up the ionized channel prepared
by the leader.
This is very intense and travels much more quickly than
the leader.
What we are witnessing is the neutralization of the
charge in the leader channel, or the progressive
discharge of the channel to ground.
The rate of propagation and the quantity of charge
involved is of great practical concern when the ground
termination of the stroke is at a transmission line tower,
conductor, or ground wire.
When the leader commences its progress towards earth,
other leaders may well push out within the cloud to
other centers of charge so that the sequence of events
just described is frequently not confined to one location
in a thundercloud.
Alternatively, the discharge to ground may disturb
the
potential balance within the cloud to the point that
an internal discharge is triggered. The
consequence of either of these events is that quite
often they will precipitate further strokes to ground
down the original.
It is well established that what appears to the eye
as a single flash of lightning is frequently the
integrated effect of several strokes, at intervals of
50 ms or so.
Figure 14.3 shows three such flashes in a stroke.
It has been analyzed that while 76% of flashes are
single stroke events, almost 3% have more than
ten strokes in their flash.
Chapter 14 Lightning Part 2
Cloud
Stroke