THROUGH SCADA
K Kumar
DGM(T&I), PL . HO
TANKS
DENSITY
METER
MAINLINE
PUMPING SECTION
SUMP
PUMP &
TANK
MOV PRESSURE/TEMPERATURE
INSTRUMENTS SCRAPPER
LAUNCHING
NRV
BARRELTION
HOV
PIPELINE OPERATIONS THROUGH SCADA
TANK AND MANIFOLD INTERLOCKS LOGIC
LS,
LT
TANK LINEUP CONDITIONS:
PI PS PI PI PS PI PI PS
PI
PS PS PS PS PS
BP PS
PID LOOP
SET POINT
CONTROLLERS
FP
LOW
GOVERNOR /
VFD / CONTROL
SP SIGNAL
VALVE
SELECTOR
DP
SRB
SD
PCV
PT
BP LOW
S
DPI
T
R.
SIGNAL
FC
SELECTO
R
T T LS,
M M LT
PS PT
DM
Digital I/Os
Analog I/Os
CPU & Communication interface
Field Instruments
PIPELINE OPERATIONS THROUGH SCADA Independent Control System Irrespective of SCADA
CONTROL SYSTEM
During the scan, a PLC
Monitors Inputs
Changes Outputs
20
PIPELINE OPERATIONS THROUGH SCADA
TYPICAL SCADA ARRANGEMENT
MCC
COMMUNICATION
SERVER
COMMUNICATION LINK
DUAL REDUNDANT
100 MBPS ETHERNET LAN
In owners OFC
based
Interface between communication
RTU / PLC Printers & Dual LAN
system provision
CPU, Memory, P C C I P C C I shall be made for
comm. Module, I/O S P O O S P O O
Ethernet Interface
controller, power U U M C U U M C
supply
DOT MATRIX
point to point
PRINTER redundant
communication
Communication Server with each PLC of
/ FES
Ethernet
SCCs
LASERJET
PRINTER
I/O MODULES
Multi drop
redundant
communication
with RTUs of
MODBUS Interface FIELD DEVICES
block valves
to third party V.28/Ethernet
devices e.g. flow
computers, RTG,
VFD etc.
Control processing/commands
Trend generation
Qin Qout
Pu
Pressure
PDCALC
Pipe Length
UPD
With ideal pressure control upstream PDMEAS
UPD = PDCALC - PDMEAS
UPD is Unexpected Pressure Downstream
PDCALC is Calculated Pressure Downstream
PDMEAS is Measured Pressure Downstream
UPD = 0 implies no leak
Pu
Pressure
Pd
Pipe Length
QUMEAS
UFU
QUCALC
Flow
Pipe Length
QU
QD
Flow
Pipe Length
response
. threshold
time
t1 t2
event periods
leak level 1 level 2 level 3 level 4 response levels
occurs
detection time
2% + 10 km 20-30 mins
5% + 5 km 15-20 mins
10% + 2 km 5 mins