Sie sind auf Seite 1von 1

Water Quality for Pigging Aug

2017
Objective to determine water quality for
pigging on Aug 2017
Sampling Location & Date Potable Water
Plant of Jasa Tirta Surabaya (by Sucofindo
Lab Cibitung on 17 July 2017)
Analysis and Reporting by Sucofindo Lab
Cibitung on 19 - 21 July 2017
Water
Particle Size Analysis by Sub-Con of
Water Appearanc Sucofindo Lab Cibitung (In progress)
Sampling e
Conclusion All water parameters
Parameter Unit
Spec*
Sucofindo Jasa Trita
are on spec except Sulphate which is
GPA 06-29 used to increase pH in the treated
Sampling date 17-Jul-17 9-May-17 9-May-17 water
Chloride mg/L < 250 33.6 29.5 36.9
Sulphate mg/L < 10 42.8 20.58 24.27 Suggestion Need to ask Jasa Tirta
Total Salt (TDS) mg/L < 500 343 328 266 to optimize Sulphate injection in the
pH on site - 6.5-7.5 6.74 6.86 7.33 water processing. High Sulphate in
Dissolved Oxygen mg/L < 10 - - - water would provide food for growth
Organic Matter mg/L <2 < 0.17 - - of microbial corrosion
Solid in Suspension mg/L < 20 10 - -
Particle Size micron < 50 IP - - Next Plan Sampling during water
Total Bacteria colony/mL < 106
1.4 x 101
- - loading into ship in Perak - Surabaya
Sulphide colony/mL zero < 0.001 - - on approx. 24 25 July 2017
Note : *Hydrotest CRA