Beruflich Dokumente
Kultur Dokumente
MAINTENANCE PRACTICE
THE POWER TRANSFORMER
DET 310
POWER TRANSFORMER
INTRODUCTION
THE POWER TRANSFORMER
BSEN 60076 1 :
THE POWER TRANSFORMER
Oil Transformer
Nameplate
Terminal and Bushings
Conservator Tank
Breather
Oil gauge
Oil Temperature Indicator
Bucholz Relay
Explosion vent
On load/ Off load Tap Changer
Serial Number
Class
Dimension
KVA Rating
Voltage Rating
Vector Group
Basic Insulation Level
Percentage Impedance
Insulation Class
Terminal and Bushings
2) If the gas contained more then 20%, the fault are due to both
breakdown of oil and insulation
Tap Changer
- VA Rating
- Impedance
- Winding and Vector Group
- Voltage
- Basic Insulation Level
- Insulation Class
VA RATING
Every transformer has a maximum output current that it can
deliver at its standard output voltage. This VA rating (KVA or
MVA for large power transformers) is dependent on the
ambient temperature or cooling provided. Exceeding the VA
rating will cause over-heating of the core and windings
and subsequent damage.
The rated power for the three phase case given by IEC
definitions is:
Rated power = 3 * rated winding voltage * rated winding
current
S = 3 x Vr x I r (VA)
Vr= rated voltage at no load (V)
Ir = rated output current (A)
De-Rated capacity factor
Ambient Temperature
Higher ambient temperatures require a corresponding reduction
in temperature rise, and thus affect price or rated power as
follows:
High altitude :
Windings fall into three main type: star, delta and zigzag
For any given rating and voltage the size and weight of a
transformer are functions of its percentage reactance. A small
percentage reactance means a large main flux requiring larger
iron cross-section.
Transformer Impedance
And in MVA
Transformer Impedance
Example:
consists of:
- Data collection
- checks and inspection
- insulation tests
- winding resistance test
- vector group test
- ratio, magnetizing current test
- oil tests
- nuetral earthing resistance
- breather test
Data Collection
- serial Number
- rating-normal and assisted
- nominal voltages
- full load current at nominal tap
- percentage impedance
- vektor group
- tap changer type, range and no of tap
General check and Inspection
-Coordinating Gaps
-Labelling
-Earth Connections
-Breathers
-Valves in operational position
-Tightness of fastening
-Insulators undamaged and clean
-No oil leaks
-Correct oil levels in conservators
Insulation Tests
Power Transformer
Hv Side Lv Side
IR tester
2) Carry out IR test between HV to Earth with 5kV IR tester
3) Carry out IR test between HV to LV with 5kV IR tester
Duration of test is 10 minutes
Divide the value obtained with value for 1 min test
This test is not always carried out, but the results are helpful
during fault investigation. The resistance of each winding is
obtained and compared with manufacturers data.
Example:
R r
415V 3
supply
Y y
B b
Primary Secondary output voltage Tap No Voltage
Voltage
AB: 200 an bn cn
BC: 200
THE POWER TRANSFORMER
Example:
a) At tap changer no 1:
VAB = 200V (Delta)
1 433
Vab VAB x 200x 7.5V (line)
a 11550
7.5
Van 4.32V ( phase)
3
Therefore the ratio is correct.
Impedance test:
Vm I r
%Impedance x x100%
I m Vr
Impedance test (continue)-
THE POWER TRANSFORMER
Resistance Test
S = 3 x V x I;
I = 1574.6 A;
Procedures:
Z0 = 3V/I
No load and no load current
The iron losses and no load current are measured in this test.
The 433V winding is charged at 433V supply & the 11KV
winding is left open .