How to handle the CB close command in

Feeders with Busbar/Breaker/CT arrangements

REB500 Busbar
Protection System
2003 ABB. All rights reserved.
ABB Switzerland Ltd - 1

ABB
Basic Arrangement of a Feeder Bay

Busbar /Breaker /CT Feeder


Breaker position is configured and
therefore taken into account in order
to have selective tripping in case of
an End-Fault.
By only taken the aux. contacts of the
breaker it is possible that an Arc
causes tripping in case the Arc is
coming earlier as the aux. contacts.
Therefore the Close-Command is
also taken into account for the
measurement. This ensures that the
CT is already assigned to the busbar
2003 ABB. All rights reserved.

protection before the arc occurs


ABB Switzerland Ltd - 2

ABB
REB500: Breaker Closed

Busbar (Protection) zone till CT


CT is assigned to the Busbar Protection
End-Fault blocked as Breaker is closed
2003 ABB. All rights reserved.
ABB Switzerland Ltd - 3

ABB
REB500: Breaker Open

Busbar (Protection) zone till open Breaker


CT is NOT assigned to the Busbar Protection
End-Fault causes tripping of the REMOTE END
2003 ABB. All rights reserved.
ABB Switzerland Ltd - 4

ABB
REB500: Breaker Open to Closed with CB_Close

Breaker Open,
CT NOT assigned

CB Close Command applied towards REB500


CT is assigned towards the busbar

Possibility of an Arc before aux. contacts report


closed
No problem as CT is already assigned

Aux. contacts report closed ,


CT will remain being assigned to busbar.
2003 ABB. All rights reserved.
ABB Switzerland Ltd - 5

ABB
REB500: Breaker Open to Closed without CB_Close

Breaker Open,
CT NOT assigned

CB Close Command applied towards REB500


CT is assigned towards the busbar

Possibility of an Arc before aux. contacts report


closed
Current in Feeder and CT is NOT assigned -> TRIP

Aux. contacts report closed ,


CT is assigned towards the busbar.
2003 ABB. All rights reserved.
ABB Switzerland Ltd - 6

ABB
Conclusion

Close Command should be applied in case


Busbar /Breaker /Feeder arrangements,
AND
Breaker position is configured and used by
the BBP

Close Command can be initiated by:


Local Manual Close Command Switch
Auto-Reclosing Device
SCS
Therefore make sure that all this commands
2003 ABB. All rights reserved.

are applied towards REB500.


ABB Switzerland Ltd - 7

ABB