Busbar protection relay -RADSS

HIGH SPEED PERCENTAGE RESTRAINT

BUS DIFFERENTIAL PROTECTION AND

ITS APPLICATION FOR DIFFERENT

BUS CONFIGURATIONS

ABB India
Utilities - Automation
BSP / KAK 1
Busbar protection relay -RADSS

NEED FOR BUS PROTECTION

IN ITS ABSENCE FAULT CLEARANCE TAKES PLACE IN


ZONE-II OF DISTANCE RELAY BY REMOTE END TRIPPING.

THIS MEANS SLOW AND UNSELECTIVE TRIPPING AND


WIDE SPREAD BLACK OUT.

EFFECT OF DELAYED CLEARANCE

GREATER DAMAGE AT FAULT POINT.

INDIRECT SHOCK TO CONNECTED EQUIPMENTS LIKE


SHAFTS OF GENERATOR AND WINDINGS OF TRANSFORMER
ABB India
Utilities - Automation
BSP / KAK 2
Busbar protection relay -RADSS

HIGH IMPEDANCE BUS DIFFERENTIAL RELAY


BASIC FEATURES

SETTING VR > IF ( RCT + 2 RL)


VK > 2 VR
RL

RCT FOR VR TO BE ZERO FOR


VR EXTERNAL FAULT
A B
nA = nB 1 + RA / ZA
1 + RB / ZB

n = TURNS RATIO
R = RCT + 2 RL
Z = MAGNETIZING IMPEDANCE
ABB India
Utilities - Automation
BSP / KAK 3
Busbar protection relay -RADSS
LIMITATIONS OF CONVENTIONAL HIGH IMPEDANCE
DIFFERENTIAL RELAY

A. PUTS STRINGENT REQUIREMENTS ON CTs

NEED FOR DEDICATED CT CORES.


IDENTICAL CT RATIO, MAGNETIZING IMPEDANCES.
AUX CTs FOR RATION CORRECTIONS UNACCEPTABLE.

B. INABILITY TO COPE WITH INCREASING FAULT CURRENT

C. SLOW RESPONSE

BASIC OPERATING TIME EXCLUDING RELAY TIME IS 15 - 20 ms.

ABB India
Utilities - Automation
BSP / KAK 4
Busbar protection relay -RADSS
ADVANTAGES OF PERCENTAGE BIASED
BUS DIFFERENTIAL RELAY - RADSS

FREE OF ANY NEED FOR MATCHED CT CHARACTERISTIC OR


RATIOS, LOW LEAKAGE REACTANCE OR RESISTANCE.

OTHER PROTECTIVE RELAYS CAN BE INCLUDED IN THE SAME


CIRCUIT.

STABLE FOR INFINITE FAULT LEVEL.

INSENSITIVE TO CT SATURATION.

DTECTS FAULTS WITHIN 1-2ms AND INITIATES TRIPPING


WITHIN 5-7ms.

ABB India
Utilities - Automation
BSP / KAK 5
Busbar protection relay -RADSS

T MD
n MD

ABB India
Utilities - Automation
BSP / KAK 6
Busbar protection relay -RADSS
INTERPRETATION OF IMPORTANT EQUATIONS ARRIVED
ON ANALYSIS
1. FOR EXTERNAL FAULTS

OPERATING CURRENT Id1 = SIt3


SLOPE S = RS
ndRd3 + RS / 2

FOR EXTERNAL WITH ONE CT SATURATED


CRITERION FOR STABILITY

RL > S
1-S
FOR S = 0.8, RL = 1024 Ohms

ABB India
Utilities - Automation
BSP / KAK 7
Busbar protection relay -RADSS

i.e,

OPERATING CURRENT FOR EXTERNAL FAULT VARIES


AS THROUGH FAULT CURRENT DOES, UNLIKE IN HIGH
IMPEDANCE RELAY.

SLOPE S IS PURELY FUNCTION OF CERTAIN CIRCUIT


PARAMETERS.

MAXIMUM PERMISSIBLE CT LOOP RESISTANCE IS


MUCH HIGHER THAN CONVENTIONAL PROTECTIONS.

NO RESTRICTION PLACED ON MAX. FAULT CURRENT.

ABB India
Utilities - Automation
BSP / KAK 8
Busbar protection relay -RADSS
2. INTERNAL FAULT

Id1 (min) = 0.092


1-S

SET S = 0.8 Id1 = 0.46 A

SENSITIVITY IS ADJUSTABLE.

OPERATES IN 1 - 2 ms BEFORE ANY CT CAN GO INTO


SATURATION.

ABB India
Utilities - Automation
BSP / KAK 9
Busbar protection relay -RADSS
RADSS CHARACTERISTICS APPLYING TO EXTERNAL AND INTERNAL FAULTS RELAY SLOPE S = 0.8

ABB India
Utilities - Automation
BSP / KAK 10
Busbar protection relay -RADSS
700 A 200 A 500 A

1000/5 200/5 500/5

3.5 A 5A 5A

5/1 5/0.2 5/0.5


0.7 A 0.2 A 0.5 A

Diff. relay

ABB India RADSS IN SINGLE BUS


Utilities - Automation
BSP / KAK 11
Busbar protection relay -RADSS
SINGLE BUSBAR SYSTEM WITH SECTIONALIZING ISOLATOR

ABB India
Utilities - Automation
SINGLE ZONE DISCONNECTION UNIT
BSP / KAK 12
Busbar protection relay -RADSS
SINGLE BUSBAR SYSTEM WITH SECTIONALIZING BREAKER

ABB India CT DISCONNECTION UNIT


Utilities - Automation
BSP / KAK 13
Busbar protection relay -RADSS
SINGLE BUSBAR SYSTEM WITH AUX. BUS & CT ON LINE SIDE
SINGLE BUS BAR SYSTEM WITH
AUX BUS & CT ON LINE SIDE

ABB India
Utilities - Automation
BSP / KAK 14
Busbar protection relay -RADSS
USE OF DIRECTIONAL RELAY IN BC CIRCUIT FOR AUX. BUS SELECTIVITY
USE OF DIRECTIONAL RELAY IN BC CIRCUIT
FOR AUX BUS SELECTIVITY

ABB India
Utilities - Automation
BSP / KAK 15
Busbar protection relay -RADSS

TYPE AB

ABB India
Utilities - Automation
BSP / KAK 16
Busbar protection relay -RADSS
REQUIREMENTS ON THE ISOLATOR AUXILIARY CONTACTS

Isolator Aux. Contacts


should close before the
primary contact closes
ISOLATOR AUX CONTACTS
and open after the
SHOULD CLOSE BEFORE
primary contactTHE
opens.
PRIMARY CONTACT CLOSES
AND OPEN AFTER THE
PRIMARY CONTACT OPENS

ABB India
Utilities - Automation
BSP / KAK 17
Busbar protection relay -RADSS
DOUBLE BUS
DOUBLE BAR SYSTEM
BUSBAR SYSTEM WITH TRANSFER
TRANSFERBUS
BUS

ABB India
Utilities - Automation
BSP / KAK 18
Busbar protection relay -RADSS

APPLICATION OF RADSS TO ABC BUS CONFIGURATION

AUX CTs FOR RATIO CORRECTION

CHANGEOVER RELAYS FOR CT & TRIP CIRCUITS

SINGLE ZONE RECONNECTION UNIT TO CONNECT TWO


ZONES TO SINGLE ZONE WHEN BOTH BUSES ARE
INTERCONNECTED THROUGH ISOLATORS.

BUS COUPLER CT DISCONNECTION UNIT FOR FAULT


BETWEEN BUS COUPLER BREAKER AND CT

DIRECTIONAL RELAYS FOR FAULTS ON TRANSFER BUS

HIGH SPEED TRIP RELAYS


ABB India
Utilities - Automation
BSP / KAK 19
Busbar protection relay -RADSS
1- BREAKER SYSTEM
1 1/2 - BREAKER SYSTEM

ABB India
Utilities - Automation
BSP / KAK 20
Busbar protection relay -RADSS

RADSS AND ITS REQUIREMENTS ON THE CTs

VARIOUS CT RATIOS

STANDARD CT CORES MAY BE USED

OTHER PROTECTIONS MAY BE CONNECT TO THE SAME


CT CORE

STANDARD CT PILOTWIRES MAY BE USED

ABB India
Utilities - Automation
BSP / KAK 21
Busbar protection relay -RADSS
RADSS FEATURES
SHORT OPERATING TIME
STABLE FOR THROUGH FAULTS
VARIOUS CT-RATIOS
NORMAL CT CORES MAY BE USED
OTHER PROTECTIONS MAY BE CONNECTED TO SAME CT-CORE
ALARM FOR OPEN SECONDARY CIRCUIT
CHECK FEATURE IN THE FORM OF OVER CURRENT START
UNLIMITED NUMBER OF LINES
EASY COMMISSIONING
EASY ROUTINE TESTING
ABB India
Utilities - Automation
BSP / KAK 22
Busbar protection relay -RADSS
PARAMETERS OF IMPORTANCE FOR BUSBAR PROTECTION
- RADSS

DIFFERENTIAL PROTECTION

SINGLE LINE DIAGRAM

CT RATIOS

RATED CURRENT AT BUSBAR

MINIMUM FAULT CURRENT

KNEEPOINT VOLTAGE OF THE CTs

TOTAL LOOP RESISTANCE


ABB India
Utilities - Automation
BSP / KAK 23
Busbar protection relay -RADSS
TO ORDER

SPECIFY :

RADSS - LINES, 3 - PH, 1 - ZONE


NUMBER OF LINES : 6 OR 12, 18 OR 24L
SLOPE (S) : 0.5 OR 0.66 OR 0.8
START RELAY Id1 (SR) = 0.88 A (STANDARD)
Rd11 : 0 OR 136 OHMS (MAX)
AUXILIARY DC SUPPLY VOLTAGE
ORDERING NUMBER (IF AVAILABLE)

TYPE OF AUXILIARY CTs :

CURRENT RATIOS AND


TURNS RATIOS
ABB India
Utilities - Automation
BSP / KAK 24
Busbar protection relay -RADSS
RADSS SETTINGS AND APPROXIMATE OPERATING VALUES

SLOPE (S) 0.5 0.66 0.8 0.85

Id min (A) 0.2 0.3 0.46 0.61

RLX (OHMS) 301 602 1204 1705

ABB India
Utilities - Automation
BSP / KAK 25
Busbar protection relay -RADSS
CT KNEE POINT VOLTAGE REQUIREMENT

VOLTAGE REQUIRED TO CAUSE OPERATION OF SR RELAY


UT3 = Id1 (SR) (RdT + 28) + nd Vd3

= 0.88 (301 + 28) + 10 x 2 = 310 V

MINIMUM VK REQUIRED = 1.3 x 310 = APPROX. 400 V

MINIMUM VK OF MAIN CT REQUIRED


IA RL + UT3
nmA (RL = 5 Ohms)

= 0.88 x 1.3 x 1 x 5 + 400 x 0.325


0.325

= 17.6 + 130 = 147.6 V


ABB India
Utilities - Automation
BSP / KAK 26
Busbar protection relay -RADSS
CALCULATIONS
CALCULATIONS FOR A TYPICAL
FOR A TYPICAL STATION
STATION

. Overall CT ratio 1200/1A


Total maximum incoming current 4000A
Maximum circulating current in the relay (IT3n) = 3.3A
This is less than max. permissible circulating current of the relay viz 4A.
ABB India
Utilities - Automation
BSP / KAK 27
Busbar protection relay -RADSS

WITH S = 0.8 Id1 (SR) = 0.88

RdT = 165 + Rd11 = 165 + 136 = 301 Ohms

Id1 min = 0.46 A

MAXIMUM PERMISSIBLE LOOP RESISTANCE ON CT SEC SIDE

= 1204 = 127 Ohms


(1/0.325)2

ABB India
Utilities - Automation
BSP / KAK 28