Beruflich Dokumente
Kultur Dokumente
BY
1)Live Zero or True Zero(4 ma) is standard adopted by ISA over Dead Zero(0 mA) because it
will allow receiver to differentiate between NO INPUT and FAULT CONDITION(Open circuit,
Broken wire)
2)According to ISA Standard 20 mA is Ensuring safety for Field Instruments, I/O Modules &
Human, as 20 mA signal and 24vdc power supply is not enough to produce spark or leakage
current .
Process Variable:-The specific quantity we are measuring in a process. Examples:
Pressure, Level, Temperature, Flow, Moisture Electrical conductivity,
PH,Voltage,Current,Resistance, Position, Speed, Vibration
,
Temperature Pressure Flow Speed Vibration Position Level PH,
Conductivity,Silica
Measurement is the process of estimating the magnitude, value and attribute of
Process Variables
one can control only what is measured
Pressure
1)When Pressure is applied to Transmitter, its diaphragm will compress and its
Piezoelectric sensor(quartz) changes its vibration frequency with reference to change in pressure.
2) Change in frequency is sensed by microprocessor and convert it into proportional voltage signal and
signal conditioning unit to convert it into electrical signal(4-20 ma) which is proportionally equivalent to the
Input Process Variable
When pressure is applied at the Primary End of Gauge, deformation of Bourdon take Place
which is Directly proportional to the applied deforming or applied force.
It requires Primary sensing element (an Orifice or flow nozzle) to create a pressure difference for measuring
flow.
2)Differential pressure created is directly proportional to the square of flow.(DP is directly prop to square of flow)
2)That pressure difference created by flow element is given to DP transmitter.
4)Differential pressure applied between two diaphragm in transmitter directly proportional to the change in
capacitance ,Inductance, piezoelectric voltage which will be converted into equivalent electrical signal(4-20mA)
Application:-Turbine inlet MS Flow.
.
Magnetic Float Level Switch
2)When an Electrical Conductor(water) moves perpendicular to magnetic field ,a voltage is induced in the
conductor perpendicular to both magnetic flux lines and direction of motion which is proportional to the average
flow velocity - the faster the flow rate, the higher the voltage. This voltage is picked up by sensing Metal
electrodes mounted in the meter tube and sent to the transmitter which takes the voltage and calculates the flow
rate based on the cross sectional area of the meter tube making it readable to an electronic circuit(4-20 mA)
3)It is velocity based Flowmeter which doesnt require Primary Flow Element as opposite to DP flow.
4)It is not suitable for Measurement of Flow measurement in non conductivity medium.
5)Application:-DM Plant(DMF outlet flow meter).
.
Rotameter.
3)PLC is a single dedicated controller, network and 3) DCS offer redundant controllers, networks, and large
limited number of I/Os capability. I/o capability .
4)PLC is FAST(Input-Compute-output Time) 4)DCS is slow (Input-Compute-output Time) as
compared to PLC.
5)PLC doesnt allow Inter controller communication 5) DCS allow Inter-controller communications
6)PLC is a Sequential Logic Controller, which will affect 6) DCS is Distributed Control System, where control
or stop the whole system if any process variation occur. elements are distributed in such a manner such that
change in particular process will not Stop the whole
system.
7)PLC Is Mostly used for Discrete Control System 7) DCS is used with Continuous and Discrete Control
System
8) PLC doesnt require too much operator intervention 8)DCS is operation need continuous monitoring by
and monitoring. operator.
9) PLC is Economical . 9)DCS is Costlier than PLC.
SFD(DCS to Field and Vice Versa)
Communication Architecture
1) Redundant Ethernet Switches(1+1) are provided for Uninterrupted Communication between operating
stations(HMI) and Hardware ( DPUs. DPU) at high speed of 100mbps
2)All Max station can communicate with any other Maxstation(OWS or ESOS) through NET A and
NET B.
OWS-04 ESOS-01 LINK ESOS-02
OWS-03
OWS-01
OWS-02
NET B (HMI B)
NET A (HMI A)
110VAC Supply is taken from UPS and converted into 24VDC by PSU Field Instrumenta
Separate PSUs for DC Supply distribution :-
1)System Power Supply:-24vdc For(Panel Auxiliaries){PSS-10,PSS20}
Level-0
(Transmitters, Actuators, SO
2) Field Power Supply:-24vdc For(Field Instruments){PSF-10,PSF-20} Dampers Switches etc.
4)I/O Modules:- Input Output Modules provides a method for transferring and exchanging
information(Interface) between internal storage devices (DPU) and external I/O Devices(Field Instruments) .
Max DNA DCS has following I/O Modules :-
1)Analog Input Modules: It will Transfer Analog Input Signals from Field to DPU.(Example:-Transmitters,
speed & vibration signals ,CV position Feedbacks)
2)Analog Output Modules:- It will Transfer Analog Output Signals from DPU to Field(Analog Commands
for opening and closing to Control valves.
3)Digital Input Module:-It will Transfer Digital Input signal(Binary) from Field to DPU(Position Feedbacks
of MOV,Limit Switches) Pump/Motor Run &Trip Status, RTS.
4)Digital Output Module:- it will Transfer Digital Output signal from DPU to Field(Digital Commands from
DPU to MOV, SOV, RELAY, Annunciator for alarms, Pump/Motor start & stop .
5)RTD Module:- It will Transfer RTD Signal from Field to DPU
6)TC Module:- It will Transfer TC signal from Field to DPU
MAX DNA DCS
(CDQ Power Plant)
BOP Turbine Generator
Control Control Control
AO
a.) Air TO Open(Air Fail to Close)
b.) Air to Close( Air Fail to Open)
I/P
AI
AFR convertor
Instrument Air
C.Valve
AFR Air Lock
Supply Air Controlled Air Relay
Positioner
Feedback Link
C) There are Three elements that must be defined by the user for the control process.
I. Process Variable Sensing device
a.) Flow transmitter b.) Level transmitter c)Pressure transmitter d.) D.P Transmitter e.) Temp. Transmitter
II. Controller Type
a.)Proportional b.)Proportional Integral c.) Proportional Integral Derivative
III. Final Control Element (Final controlling mechanism)
a) Control valve b.) Actuator (MOV)
Sense
Decide
Control schemes in CDQ Measuring controller
device
Influence
React
Final control
process device
1)Feedback control scheme:- Feedback control is the simplest control scheme where Process variable is
measured and the controller output is calculated based on its deviation from set point .It is applied to those
applications where disturbances are not severe. Example:- PRDS Control
2)Split range Control:- In Split range control scheme, Process variable is controlled by using two FCE (final
control elements),by splitting the range of controller output .(4-12mA/0-50%) &(12mA-20mA/50-100%) .It is
used to control critical process variable where slightly exceeding and reducing a process variable limit can
adversely affect the process. Ex:-Gland sealing pressure control
3)Backpressure Feedback control:-The most common application for a Back pressure feedback control
scheme is the elimination of Sudden high pressure from a process that will effect the process.
Example:- HP Bypass pressure control.
Process control is the act of controlling a final control element to
change the manipulated variable to maintain the process variable at a
desired set point.
CONTROL SYSTEM: An arrangement of elements interconnected and interacting in such a way that it can
maintain some condition of a process or machine in a prescribed manner
Process is broadly defined as an operation that uses resources to transform inputs into outputs.
Set Point (SP):- The set point is a value for a Process variable that is desired to be maintained.
Transducer:-It is a sensing device used to convert one form of energy to another.
Feedback:-It is a function of Process Variable sent to summing point to identify the deviation from its
desired Set point to obtain the actuating signal.
Controlled Output Signal(CO) :-It is the processed and controlled signal (4-20ma) sent by the controller to
the Final control element to bring the process variable at desired SET POINT.
Manipulated Variable :- The factor that is changed by FCE to keep the Process Variable at its set point is
called the manipulated variable.
A final control element (FCE) is a device changes the value of the manipulated variable in accordance to
Controller output Signal to change the process output.
Disturbance (D):-It is defined as uncontrolled changes in the process inputs or resources.
Actuating signal:-It is the Difference between reference input signal(SP) and feedback signal(PV) also known
as ERROR Signal. It can be positive, negative or zero.
Controller:-It is a microprocessor based device used to monitor and physically alter the operating condition at
a given dynamic system by its controlled output.
Process Variable (PV):-It is a measure of the Process output that changes in response to changes in the
manipulated variable and disturbances.
Summing Point: It is the Junction where difference between SET POINT and PROCESS VALUE
to produce an Actuating Signal
Closed Loop Control System:-A Closed Loop Control (CLCS) is one
where a Process Variable is measured, compared to a Set Value and action is taken to
correct any Deviation or Error from Set Value. The continuous Measurement of PV and its
comparison to Set Point closes the Loop.
Disturbances
Summing Point
PV
Transducer
Feedback Signal (Process sensing
Element)
In open loop control:- An Open Loop Control(OLCS) is one where
the PV is not compared with Set Value and action taken, but action
is taken without regard to conditions of PV
In open loop control we are not concerned that a particular set point to be maintained, the
controller output is fixed at a value until it is changed an operator
Many processes are stable in an open loop control mode and will maintain the process variable
at a value until a DISTURBANCE(uncontrolled change in the process inputs or resources)
Occur.
Example :- SWBP Suction Pressure Control, Manual Mode, CBD& IBD operation.
Process Variable
Set Point FCE Process
Vacuum Breaker Open Loop Control System
TG
Set Point Controller
1oo2
PSHH
Condensor
1)HP Bypass Pressure Control Valve Closed Loop
Significance:-
1)Used to Control Upstream TG Inlet MS Pressure during Turbine Trip and Normal Condition.
2) Used to Save Precious Steam During Cold Startup and Turbine Trip Condition
Process Sensing Elements(Transducers):- Two Pressure Transmitter-(MSTPT008A-,PT-MSTPT008A)
Upstream HP bypass PCV. One Pressure Transmitter (PT-) at Downstream HP bypass PCV
Final Control Element:-HPPCV
Set Point:- 90 KSC
Controling Scheme:-Back pressure Closed Loop Feedback Control .
Controller Direction&CV Action:-Direct(PV increases ,Controller Output Increases),
Control valve action:-Air to Open
Override Control:-Under given conditions override the Loop and CLOSE the Valve Immediately
a)Exhaust Pressure above 0.2 Abs
b) Instrument Air Failure(Auto Shut off thru air Cylinder output)
c) HP by pass line Temperature More than 200
d)Both CEP Pump Trips
e)Downstream Pressure more than 6 KSC
f) Maximum Permissible Flow Capacity to Condenser exceed 162.5 TPH.
HP Bypass Pressure Control Loop
Controller
1oo2
PT PT PT FT
Condensor
HP Bypass Temperature Control Valves-(Main and Dump TCV)
Significance:-
1)Used to Control Downstream Temperature when HP PCV is in Operation( condenser tubes Protection)
2) It will Not allow to Dump Steam to condensor at high temperature otherwise vacuum will drop abruptly.
4)It will Decrease the temperature from 530 to less than 200 degree during Turbine Trip.
Process Sensing Elements:-Two Temperature Transmitter(TT001A,TT001B) at Downstream of HP Bypass
Temp Control Valve
Set Point:-62 deg C
Final Control Element:-TCV 1617 and TCV 1616
Control Scheme:- Closed Loop Feedback Control
Controller Direction:-Direct (PV Increases, Controller Output Increases)
Control valve Direction:-Air to Open(without Air lock Relay)
Over ride Control:-1)Instrument Air or Control Signal Fail
2)Both CEP Pump Trips
HP Bypass Temperature Control Loop
1oo2
Controller
TT
Condensor
PRDS Pressure Control Valve
Significance:-
1)It is utilized for Auxillary Steam Pressure distribution to (GSPC, Ejectors) for Maintaining Vaccum
2) It will be in line during Cold startup or low load condition(0-21MW approx) for providing steam to
auxillary equipments(Ejectors,Gland sealing,GSC and four boilers(Drum and Deaerators)
Process Sensing Elements:-Two Pressure transmitter (MSTPT009A,MSTPT009B)
Final Control Element:-PRDS PCV01
Set Point:-(11.5-12.5 KSC)
Controller Direction:-Reverse (PV Increases, Controller Output Decreases)
Control Valve Action:-Air to open(Fail to close)
Control Loop:- 1) It is Closed loop feedback Process Control .
Override control Interlocks:-
1)Instrument Air Failure
2) When Differential pressure Across Wander Extraction and HP Extraction will be more than 0.7 KSC, it
will give close command to PRDS PCV ,it will happen when load is Approx 21 MW.
PRDS Pressure Control Loop
Controller
Main steam Line to TG
1oo2
LP Header Line
PT PT
Significance:-
1) It is used to control the PRDS Steam Temperature after Desuperheater.
Process Sensing Elements:-Two Temperature transmitters :-(ASTT001A,ASTT001B)
Final Control Element:-PRDS TCV01
Set Point:-(250 Deg C)
Controller Direction,:-Direct (PV Increases, Controller Output Increases)
Control valve action:-Air to open(no Air lock relay)
Control Loop:- 1) It is Closed loop feedback Process Control
Override Control:- 1)Control system fault
3)Instrument Air Failure
PRDS Temperature Control Loop
Controller
1oo2
PRDS to LP Header Line
TT TT
LP Header Line
PRDS to LP Header Line
CEP SWBP
Hot well Level Makeup Control Loop
Significance:-
1)used to Compensate or Nullify the Level of Hotwell tank due to steam loss (MS Line
vent,drains,Extractions.)
2)Normally it will be in Manual mode when the demand in any of the boiler will rise leads to the drop in Hot well
level continuously will bring us in condition to put in Auto mode to achieve a desired set point.
Process Sensing Elements:-Two Level transmitters are Provided in HOTWELL Tank(HWLT1601,HWLT1602)
Final Control Element:-LCV01(Low Capacity),LCV02(High Capacity)
Set Point:-(840mmwc)
Controller Direction:-Reverse (PV Increases, Controller Output Decreases)
Control valve action:-Air to close(Air fail to open)
Control Loop:- 1) It is Closed Loop feedback control scheme
Operation:-Level transmitters will send current level feedback to summing point and controller will analyse the
magnitude of error and send controlled output to low capacity bypass control valve, which will take necessary
action to control the level.
When Level will decrease at an alarming rate and low capacity valve will open ,then its 90%open feedback to the
controller will give open command to High capacity control valve to regulate the desired level.
Override control Interlocks:-
1)Instrument Air Failure& Control system fault
3)If Differential error between two transmitters is high,controller will change PID action from AUTO to MANUAL
mode.
HOTWELL Make up Control
Controller
Condensor
1oo2
LT Hotwell LT
Tank
DM Water Discharge
Wander Extraction Temperature Control Valve
Significance:-Extraction Temperature control is necessary to save auxiliaries from Thermal Expansion due to
overheating (GSC,Ejector).
Process Sensing Elements:-Two Temperature Transmitters (ASTT001A,ASTT001B) via Thermocouples-2
Final Control Element:-TCV-04
Set Point:-250 deg C
Controller Direction:-Direct (PV Increases, Controller Output Increases)
Valve Action:-Air to open
Control Loop:- 1) It is Closed loop feedback Process Control
Override control Interlocks:
1)Control system fault
2)Instrument Air Failure
3) Differential error between two transmitters is high,controller will put the PID from AUTO to MANUAL mode.
Wander Extraction Temp Control
1oo2
Controller TT TT
SWB
CEP
P
HP Wander Extraction Pressure Control Valve
Significance:-1)It is given to utilize Turbine Excess steam for auxillary purpose
2)It will be in line during (23-53 MW) Approx
Process Sensing Elements:-One Pressure Transmitter(PT220 Provided in HP Process line),DPT 216A(B/W
HP Extraction and wander Extraction)
Final Control Element:-PCV216A
Set Point:-11.5 KSC
Controller Direction:-Reverse (PV Increases, Controller Output Decreases to close the control valve)
Valve Action:-Air to open
Control Loop:- 1) It is Closed loop feedback Process Control
Operation:-One Pressure Transmitter at Extraction line will give Feedback to summing point(SP-PV),which
will send the error signal to controller ,controller will generate necessary controlled output for control valve to
maintain desired pressure.
Override Control:-1)When DP Across LP Extraction control valve(DPT 216A) will be more than 0.7ksc
2)when ESV closed or Turbine trip
3)When DP across HP Extraction will be less than 0.2 KSC
4)Instrument Air Fail
HP Wander Extraction Pressure Control Loop
Controller
DPT
PT
LP Header Line
Wander Extraction to Process
DPT
LP Wander Extraction Pressure Control Valve
PT
LP Header Line
Wander Extraction to HP Process
DPT
GSPC Control Loop (Supply and Dump Control Valve)
Significance:-
1)It will maintain Gland seal header pressure by sealing the glands so that air will not ingress inside the turbine
glands (LP&HP) which is quite necessary to maintain vacuum.
Process Sensing Elements:-Two pressure transmitters(PT-01,PT-02)
Final Control Element:-(PCV01,PCV02)
Set Point:-500mmwc
Controller Direction:-PCV01(Reverse),PCV02(Direct)
Valve Action:- 1)Supply Control Valve -PCV01(Air to close),(4-12 ma)(0-50% controller o/p signal)
2) Excess to Dump Control Valve -PCV02 (Air to open),(12-20 ma)(50-100% controller o/p signal)
Control Loop:-Split range closed loop control system(controller O/P range(4-12ma),(12-20ma)
Operation:-Two pressure transmitters will sense the pressure and send it to summing junction of
controller,Controller will process the controlled output and send it to PCV01 or PCV02 to open or close as per
desired set point.At a time only one control valve will be in operation.
When the Header pressure is below 500mmwc,PCV01 will Open to control the pressure,PCV02 is closed.
When Header Pressure is more than 500mmwc,PCV02 will Open to maintain the pressure.PCV01 is closed
Gland Steam Header Pressure Control Loop
1oo2
PT PT
GSPC Header
CV
position CV
Position
Full Close(0%)
0%(4mA) 50%(12mA) 100%(20mA)
Controller O/P
Minimum Recirculation Flow Control Loop
Significance:-
1)It is used to regulate the CEP minimum discharge flow.
Process Sensing Elements:-CEP Discharge Flow Transmitter(FT-206)
Final Control Element:-FCV
Set Point:-(125 TPH)
Controller Direction:-Reverse
Valve Action:-Air to Close
Control Loop:-Closed Loop Feedback Control .
Operation:-Flow Transmitter will sense the flow and send signal to Summing point it will generate an error
which will be compared with the set point in controller and controller will send its controlled output based on
magnitude of error to Flow control valve.Final Control element will open/close based on controlled signal given
by controller.
CEP Minimum recirculation control Loop
FT
Controller
CEP Hotwell
Tank
Condensate Export Control Valve
Significance:-
1) It is used for Continuous recirculation of condensate water to CDQ Boilers-1,2,3,4 for steam generation by
taking reference of Normal Hotwell Level .
Process Sensing Elements:- Two Level Ttransmitter are Provided in HOTWELL Tank(HWLT1601,HWLT1602)
Final Control Element:-FCV01
Set Point:-840mmwc
Controller Direction:-PV increases, controller output increases(Direct)
Valve Action:-Air to open
Control Loop:-Closed Loop Feedback Control System
Override Control:-1)If Differential error between two transmitters is high,controller will put the PID from AUTO to
MANUAL mode.
2)Instrument Air Failure
Condensate Export Control loop
GSC
Condensate Export to Boiler Ejector
O/L
Controller
CEP
1oo2
LT LT CEP
Hotwell
Tank
Types Of Controller for Closed Loop Control System
Proportional Controller :-It only measure how much correction has to be made?
1)Its Controlled output(m) is the product of error and proportional gain
3)Its output is not a function of time Interval but of magnitude of error.
2)Its function is {m=Kp x error +bias) where Kp=1/PB,
Kp=PV% /Controller Output %
It is represented by
m=kp.e
SP e error Kp m process
PV
Sensor
3)Fast Process Need less Gain(As large change in input is required to produce small change in output)
& Slow process Need high gain (As small change in input is required to produce large change in input)
4)It will respond to minimize the magnitude of error only ,but it will not remove the OFFSET from desired SP.
5) Application:-It can be used for Discrete(ON-OFF) Level Control System for Preventing LOW LOW & HIGH HIGH
condition for Pump Start and Stop.
Proportional Integral :- :-It is a defined as a change in PV
at a speed proportional to the magnitude of deviation.
Its Integral function will continuously Integrate the errors by taking past values into account
It measures ,How much(P) and how long (I) the correction should be applied?.
It is a function of duration of error to remove offset.
Output is a repeat of the proportional action as long as error exists by Increase/Decrease in RESET
Time(RPM) or Rate(MPR)
It is used for Fast response process variables (Pressure, level, Flow) to remove offset
It will continue to act till Error(offset) becomes zero
It is useful for only those applications where change in error is stable(with respect to time)
Its function is m=Kp.(e+1/Ti edt)
Error
SP Kp(.e+1/Ti edt) m
process
PV Sensor
Proportional Integral Derivative(PID):-It defines Magnitude, Time Duration and
Rate function of error
P depends on the present error, I on the accumulation of past errors, and D is a
prediction of future errors, based on current rate of change
PV Sensor
Calibration is a set of operations ,that compares the measurement performed by an
instrument to those made by a standard instrument for detecting ,reporting and
adjusting error met in the instrument tested.
1)Milliamp Source
2)HART Communicator
3) Temperature calibrator(RTD and TC)
4) Dead Weight Tester
5) Vacuum pump
6) Hand Held Pressure Calibrator
Thank you